1)  When the LCD Display registers a 

“Short Circuit” 

a number of faults could have occurred, 

namely: 

a)  A greater than normal spike through the Eskom plug that shorts the fuse, 
b)  A short on the battery terminals or bad connection, 
c)  A possible short on the PCB cards inside the UPS due to dust, bugs, leaking water, 

lightning strike, 

d)  The power output of the UPS has exceeded the 1kw limit possible in the case of the UPS 

being connected to 2 ATM’s or 

e)  The ATM has a built in 700 watt UPS that initializes once the ATM has been turned on. 

2)  When the

 “Short Circuit” 

occurs please follow the next instructions; 

a)  Ensure that the UPS is switched off in accordance with the procedure as listed above. 
b)  Once the unit is off check the fuse holder on the side of the UPS. It is easily unscrewed. 

Should the fuse be blown please call a technician and report the fault. If the fuse keeps 
blowing once changed a short circuit is materializing on the PC Boards. Please log a fault 
report. 

c)  If the fuse is not blown, please check that the ATM does not have a built in UPS system. 

Should there be an internal UPS System pull out the sliding tray that it rests on. There is a 
green light on the right front of the UPS. Depress this button for 3 seconds until the internal 
UPS turns off. Once this has been done check the back of the UPS for 2 power cables. One 
is black the other should be white. One is male and the other a female connection. In order 
to bypass this unit please unplug them both and reconnect them together. The internal UPS 
is now disconnected. Please follow the re-connection procedure listed above. 

d)  If the ATM has any liquid damage or lightning strikes please log a fault report. 
e)  Should the UPS still remain non-operational once the power has been re-connected please 

log a fault report. 

f) 

Should the UPS continue to stay in Short Circuit Mode please disconnect the UPS from the 
Eskom mains and plug the ATM and V-Sat into Eskom. Please log a fault report. 

3)  Should the UPS at any time register an 

“Internal Error” 

please log a fault report immediately? 

This fault only registers once the internal software of the unit has been compromised due to 
the faults listed above and needs to be rectified immediately. 

4)  Should the unit be completely non-operational ie, all the lights are off and it seems no power is 

getting through the UPS to the ATM. Turn the UPS off at the Eskom socket. Re-connect ATM 
and V-Sat back into Eskom socket and power up. Please log a fault report immediately. This 
fault could be due to the batteries having run flat due to: 

a)  A malfunction within the UPS software allowing the batteries to deplete 
b)  A short that has compromised the charging software 
c)  A lightning strike that has compromised the charging software or  
d)  Faulty batteries 

5) 

Should there be a fault with the UPS please do not disconnect Eskom from the 
unit or switch it off until a technician has contacted you.

 Please merely plug the 

ATM and V-Sat back into Eskom until we contact you to discuss the fault.  

6)  Please keep in mind that when the UPS is powering up 2 ATM’s the uptime during load 

shedding is diminished by half. This is obviously load dependent. 

 

COMMS ERROR: 

1)  Loose Ribbon Cables inside the UPS. 
2)  Ribbon Cables need to be pushed into the seating inside the UPS Correctly. 

 
 
 

Trouble-shooting ( Red Light will be on) 

Содержание 1kW24V

Страница 1: ...0 1Kw24V UPS Manual...

Страница 2: ...1 Contents 1 INTRODUCTION 2 2 SAFETY INSTRUCTION 2 3 SYSTEM DESCRIPTION 3 4 UPS OPERATION 4 5 UPS PROGRAMMING 9 5 FAULT TROUBLE SHOOTING 18...

Страница 3: ...self diagnostic function 4 High Power 3 stage Charger 5 High efficiency design to save electricity 6 Low heat dissipation in long time operation 7 Design to operate under harsh environment 1 3 Importa...

Страница 4: ...3 2 3 DOWN Key Use to move the display down 3 2 4 ENTER Key It is pressed with the UP Key to turn on the UPS Push the ENTER button to confirm or store DATA 3 2 5 Push the UP and DOWN keys together to...

Страница 5: ...ay then changes to The display then changes to UPS TURNED OFF CALIBRATING MICROCARE ON OFF ENTER Menu Down Menu Up OK Inverter Error MICROCARE 1 KW OUTPUT LOW MICROCARE ON OFF ENTER Menu Down Menu Up...

Страница 6: ...l change to indicate the amount of LOAD as a of the UPS unit being used in KW When the Up key and the Down Key are pressed simultaneously for 3 seconds the UPS will be turned Off LCD DISPLAY MENU With...

Страница 7: ...UPS is drawing from the battery If the battery Amps changes to CHR AMPS This shows the Charge Amps that are being put back into the battery bank from the charging source MICROCARE 1 KW OUTPUT 20 MICR...

Страница 8: ...draw from the grid power supply This shows the internal temperature of the UPS TEMPERATURE COOL MICROCARE ON OFF ENTER Menu Down Menu Up OK Inverter Error UPS VOLTS 222 UPS AMPS 7 0 MICROCARE ON OFF E...

Страница 9: ...umber of the Inverter The Serial number of the inverter needs to be noted and supplied when requesting any fault support information SERIAL NUMBER MCxx007 MICROCARE ON OFF ENTER Menu Down Menu Up OK I...

Страница 10: ...Push ENTER if you want to change the set up menu By pushing ENTER button you can change whether the inverter runs in NORMAL SENSE mode or SOLAR CONTROL mode NORMAL SENSE is to be selected whenever usi...

Страница 11: ...nstantly with mains fail prediction 8mS SOFTSTART Default 8 milli second transfer time and will ramp the RMS voltage up in less than 1 second with mains fail prediction GEN SOFTSTART 8 milli second tr...

Страница 12: ...ter a medium delay time period HIGH 3x RESET High sensitivity to short circuits will trip the inverter after a short delay time period with soft start to prevent in rush current MED 3x RESET Medium se...

Страница 13: ...will then change to The settings available are as follows NO DELAY As soon as Grid power is available the Inverter will synchronise and switch from battery to Grid DELAY 30Sec 30 seconds after Grid po...

Страница 14: ...display will show EXIT DO NOT SAVE SET UP MENU MICROCARE ON OFF ENTER Menu Down Menu Up OK Inverter Error RESTORE FACTORY SET UP MENU MICROCARE ON OFF ENTER Menu Down Menu Up OK Inverter Error EXIT AN...

Страница 15: ...how If no entry is made for 1 minute the display will return to the main menu Use the UP DOWN button to select BATTERY menu Push ENTER to access the Battery Setup Menu SAVING DATA TO INTERNAL MENU MIC...

Страница 16: ...5 of charge rate as per the list supplied below INVERTER CHARGE AMPS 1Kw24V 30A In regards to the battery charge level The Level selected will allow the battery charge to the batteries 25 OF RATED CHR...

Страница 17: ...UP button The menu will then change to This allows the user to select the TIME that the BOOST VOLTAGE will be held at before changing to FLOAT By pushing ENTER you can select 1 2 or 3 hours BATTERY B...

Страница 18: ...s If the charger is in FLOAT but you require it to go back into BOOST then the next menu will allow this Pushing the ENTER button allows the charge to be changed from AUTO to BOOST or FLOAT Push the U...

Страница 19: ...tteries 10 The UPS LCD display should state Please wait 11 The LCD display then states UPS Turned Off Calibrating 12 The LCD display then states UPS Turned Off 13 Then depress the center button green...

Страница 20: ...he re connection procedure listed above d If the ATM has any liquid damage or lightning strikes please log a fault report e Should the UPS still remain non operational once the power has been re conne...

Страница 21: ...erminals When considering any electronic breakage except due to lightning reverse polarity over voltage etc the state of the internal control circuitry determines the warranty This warranty will not a...

Страница 22: ...items purchased from J J Electronics and we require the following information 1 Details of the item s you would like to return 2 Our invoice number 3 The reason for the return 4 J J Electronics must...

Отзывы: