Push the ENTER button. The menu changes to:
SOLAR CONTROL Mode is not to be used on the UPS Unit.
To change the menu, push the UP button.
The menu will then change to:
The Settings available for this are as follows:
3mS NO
SOFTSTART
3 milli second transfer time and will restart load instantly -
with mains fail prediction.
5mS NO
SOFTSTART
5 milli second transfer time and will restart load instantly -
with mains fail prediction.
8mS +
SOFTSTART
(Default) 8 milli second transfer time and will ramp the
RMS voltage up in less than 1 second - with mains fail
prediction.
GEN +
SOFTSTART
8 milli second transfer time and will ramp the RMS voltage
up in less than 1 second - with
no
mains fail prediction.
GEN + SLOW
RAMP
8 milli second transfer time and will ramp the RMS voltage
up in 3 seconds - with
no
mains fail prediction.
UPS
MODE
SOLAR
CONTROL