Page 19
Commissioning
IF2030/PNET
5.4
Object Directory
Index
Subindex Data type
Name
RS485 RS422 Description
0x2000 0
Uint8
RW select sensor
Address of currently selected sensor
0x2001 0
Uint8[32] R
sensor addresses
Shows address list of available sensors
0x2010 0
Uint32[64] R
device error log
Reads out the last 32 error codes with time stamp
0x2020 0
Uint32
RW baud rate
IF2030 baud rate
0x2021 0
Uint8
RW minimum cycle time
Minimum time for one communication cycle in ms,
cycle time = 0: use estimated time
0x2022 0
Uint8
RW preferred sensor data
size
Desired useful data length in bytes per sensor, value
= 0: estimated/calculated value
0x2023 0
Uint8
RW serial sensor interface
0: RS485,
1: Reserved,
2: ASCII + RS422
0x2024 0
Uint8
W
clear device config
One byte deletes settings from flash, settings are
included in RAM until restart
0x2025 0
Uint8
W
clear sensor config
One byte deletes settings from flash, settings are
included in RAM until restart
0x2026 0
Uint8
W
reset device
One byte performs reset
0x2027 0
Uint8
RW enable/disable
HTTL Sync
0: Disable HTTL synchronization
1: Enable HTTL synchronization
0x2028 0
Uint8
RW enable/disable cyclic
status header
0: Disable 8 byte status header in cyclic data
1: Enable 8 byte status header in cyclic data