MCS
‐
BMS
‐
GATEWAY
Startup
Guide
Revision
2.0
Micro
Control
Systems
5580
Enterprise
Pkwy,
Fort
Myers,
FL
33905
USA
Web
:
www.mcscontrols.com
Tel
:
(239)
694
0089
Fax
:
(239)
694
0031
8
2.2.2
Setting
the
Serial
Baud
Rate
(DIP
Switch
B0
–
B3)
for
BACnet
MS/TP
&
Metasys
N2
DIP
Switches
B0
–
B3
can
be
used
to
set
the
serial
baud
rate
to
match
the
baud
rate
provided
by
the
Building
Management
System
for
BACnet
MS/TP.
Metasys
N2
is
always
defaulted
to
9600
baud
and
the
B
bank
is
disabled.
Figure
2:
B0
–
B3
DIP
Switches
2.2.2.1
Baud
Rate
DIP
Switch
Selection
Baud
B0
B1
B2
B3
Auto
Off Off Off Off
110
On Off Off Off
300
Off On Off Off
600
On On Off Off
1200
Off Off On Off
2400
On Off On Off
4800
Off On On Off
9600
On On On Off
19200
Off Off Off On
20833
On Off Off On
28800
Off On Off On
38400
On On Off On
57600
Off Off On On
76800
On Off On On
115200
Off On On On
Figure
3
Baud
Rate
Table