There are a few other models of Coleman air conditioners we should mention. The process of wiring
them is comparable to the Mach 1 and similar units. Use these diagrams along with the component
identification shown in the Mach 1 section to identify and connect EasyStart. Wiring colors are the same with
all models we have come across so far. The wires from the compressor are:
Black to the compressor overload and compressor run winding
White to the compressor run winding.
Red to the compressor start winding.
Additionally, purple supplies power to the system from the control relay and splices to EasyStart Black.
Mounting location varies for these models however it is always possible to find an appropriate
location. Mount the unit with the wiring exit on the box pointing down or mount the box parallel to the
ground. Never mount the box with the wires pointing up.