background image

 

Mianyang Weibo Electronics Co.,Limited 

No.7 Road Second part of Xianren Road, Youxian District, Mianyang City, P.R. China 

Tel: 86-0816-2971265 Fax: 86-016-2281934 

www.wb-my.com   [email protected] 

14.

 

Mounting : DIN Rail 35mm Mounting or screw mounting   

 

Instruction of Installation and Use 

1. The product has adopted structure compliance with EN50022; suitable for 

DIN rail mounting NS35/7.5, NS35/15. Installation steps are as following 
(please reference to dimensional drawing):   

Step 1: Immobilize one side of product‘s mounting trough to the DIN 

mounting rail; 

Step 2: Pull out the spring clasp; 
Step 3: Place whole mounting trough to the DIN mounting rail properly; 
Step 4: Release spring clasp to make sure the installation.   

2.

 

The product has calibrated before out of factory. After correctly wiring, it 
can be powered and used immediately. But for further precise signal 
sampling, user needs to warm-up the product for 3 minutes before use. 

3.

 

The auxiliary power requires isolation voltage

2000VAC, DC current 

output ripple

10mV. 

4.

 

Multiple transducers can share with one set auxiliary power together., and 
the wire shared between the transducers and power should be short. It's 
better to connect each transducer to the auxiliary power individually. 

5.

 

Wiring in terms of the terminal identification drawing strictly. 

6.

 

Basic testing method for accuracy 

(1)

 

According to the terminal definition table to connect the testing 
circuit; 

(2)

 

The testing must to be done by under the following conditions

 

Auxiliary power:

 

 

24V

±

5

%,

ripple

5mV 

Ambient temperature:

 25

℃±

5

 

Relative humidity

: RH(45

75)

 

Accuracy for Signal Power Source instrument:

 0.05 

 

Содержание WBI415S91

Страница 1: ...ying WB Series Electric Isolated Transducer and Digital Electrical Transducer since 1989 USER MANUAL WBI415S91 AC current transducer www wb my com wbwm wbdz cn Tel 86 0816 2971265 Fax 86 0816 2281934 ISO9001 ISO14000 ISO18000 Certified ...

Страница 2: ...hysical damage Before working in the terminal strip area the equipment must be isolated Proper and safe operation of the equipment depends on appropriate shipping and handling proper storage installation and commissioning and on careful operation maintenance and servicing The operating manual for the equipment gives instructions for its installation commissioning and operation However the manual c...

Страница 3: ... 5V It has adopted electromagnetic isolation principle for real time measurement ofAC current from electric net or electric circuit The product has certain advantages of total galvanic isolation between input output high accuracy low drifting by temperature and wide temperature bearable range etc Product Dimensional Drawing unit mm 9 Mianyang Weibo Electronics Co Limited No 7 Road Second part of X...

Страница 4: ...Responding Time 300ms 7 Over Load Capacity 30 times of nominal input 5 seconds 8 Auxiliary Power 12VDC 24VDC 9 Current consumption for static status 5mA 10 Isolation Voltage Input Output 2500Vdc for 1 minute 11 Output Ripple 4mV root mean square value output load is 250Ohm 12 Drifting by Temperature 200 10 6 13 Ambient Temperature Commercial grade 0 50 Industrial grade 25 70 Mianyang Weibo Electro...

Страница 5: ...ation 2 The product has calibrated before out of factory After correctly wiring it can be powered and used immediately But for further precise signal sampling user needs to warm up the product for 3 minutes before use 3 The auxiliary power requires isolation voltage 2000VAC DC current output ripple 10mV 4 Multiple transducers can share with one set auxiliary power together and the wire shared betw...

Страница 6: ...ed errorγof the transducer should be calculated as γ Uo Uz 5V 100 6 Repeating step 4 5 if calculated absolute value is less than the given accuracy value of the transducer it shows the transducer s accurate grade is qualified Caution 1 Pay attention to the auxiliary power information especially the auxiliary power grade and polarity other wise will damage the product 2 pay attention to the wire co...

Страница 7: ...lease pay attention to the shield of input wire and the output signal wire should be as short as possible For product intensive installation the space between each product should not be smaller than 10mm 5 Only use identified terminals 6 There is no lightening strike prevention circuit design in this product For out door and hazardous environment using please add protective alternatives 7 This pro...