70D0004

34

TPB Series Log Set

NOTE REGARDING VENTED PRODUCTS

This  product  must  be  installed  by  a  licensed  plumber  or 
gas  fitter  when  installed  within  the  Commonwealth  of 
Massachusetts.
Any  residence  with  a  direct  vent  product  must  have  a  CO 
detector installed in the residence.
Installation  of  the  fireplace  or  vented  gas  log  in  the  State 
of  Massachusetts  requires  the  damper  to  be  permanently 
removed or welded in the fully open position.
In addition, a naturally vented gas log may not be installed in 
a bedroom or bathroom in the State of Massachusetts.
Flex  line  installation  must  not  exceed  36  inches  and  must 
have a T shutoff valve. 

NOTE REGARDING VENT FREE PRODUCTS

This  product  must  be  installed  by  a  licensed  plumber  or 
gas  fitter  when  installed  within  the  Commonwealth  of 
Massachusetts.
In  addition,  vent  free  products  may  not  be  installed  in  a 
bedroom or bathroom regardless of size or type in the State 
of Massachusetts.
Flex  line  installation  must  not  exceed  36  inches  and  must 
have a T shutoff valve.

CARBON MONOXIDE DETECTOR REQUIREMENTS

() Revise  10.8.3  by  adding  the  following  additional 
requirements:
(a)  

For  all  side  wall  horizontally  vented  gas  fueled 

equipment  installed  in  every  dwelling,  building  or  structure 
used  in  whole  or  in  part  for  residential  purposes,  including 
those owned or operated by the Commonwealth and where 
the  side  wall  exhaust  vent  termination  is  less  than  seven 
(7)  feet  above  finished  grade  in  the  area  of  the  venting, 
including but not limited to decks and porches, the following 
requirements shall be satisfied:
1. 

Installation of carbon monoxide detectors. 

At the time 

of  installation  of  the  side  wall  horizontal  vented  gas  fueled 
equipment, the installing plumber or gas fitter shall observe 
that  a  hard  wired  carbon  monoxide  detector  with  an  alarm 
and battery back-up is installed on the floor level where the 
gas  equipment  is  to  be  installed.  In  addition,  the  installing 
plumber  or  gas  fitter  shall  observe  that  a  battery  operated 
or  hard  wired  carbon  monoxide  detector  with  an  alarm  is 
installed on each additional level of the dwelling, building or 
structure served by the side wall horizontal vented gas fueled 
equipment. It shall be the responsibility of the property owner 
to secure the services of qualified licensed professionals for 
the installation of hard wired carbon monoxide detectors
 

a.  In the event that the side wall horizontally vented gas 

fueled equipment is installed in a crawl space or an attic, the 
hard wired carbon monoxide detector with alarm and battery 
back-up may be installed on the next adjacent floor level.
 

b.  In the event that the requirements of this subdivision 

can not be met at the time of completion of installation, the 
owner shall have a period of thirty (30) days to comply with 
the above requirements; provided, however, that during said 
thirty  (30)  day  period,  a  battery  operated  carbon  monoxide 

Massachusetts Residents Only — Please read and follow these special requirements

detector with an alarm shall be installed.

Approved  Carbon  Monoxide  Detectors.

 

Each  carbon 

monoxide detector as required in accordance with the above 
provisions shall comply with NFPA 70 and be ANSI/UL 034 
listed and IAS certified.
3. 

Signage.

  A  metal  or  plastic  identification  plate  shall  be 

permanently  mounted  to  the  exterior  of  the  building  at  a 
minimum height of eight (8) feet above grade directly in line 
with  the  exhaust  vent  terminal  for  the  horizontally  vented 
gas  fueled  heating  appliance  or  equipment.  The  sign  shall 
read,  in  print  size  no  less  than  one-half  (1/)  inch  in  size, 
“GAS  VENT  DIRECTLY  BELOW.  KEEP  CLEAR  OF  ALL 
OBSTRUCTIONS.”
4. 

Inspection.

  The  state  or  local  gas  inspector  of  the  side 

wall  horizontally  vented  gas  fueled  equipment  shall  not 
approve the installation unless, upon inspection, the inspector 
observes  carbon  monoxide  detectors  and  signage  installed 
in  accordance  with  the  provisions  of  48  CMR  5.08()(a)1 
through 4.
(b) 

Exemptions:

  The  following  equipment  is  exempt  from 

48 CMR 5.08()(a)1 through 4:
1.  The  equipment  listed  in  Chapter  10  entitled  "Equipment 
Not  Required  To  Be  Vented"  in  the  most  current  edition  of 
NFPA 54 as adopted by the Board; and
. Product Approved side wall horizontally vented gas fueled 
equipment installed in a room or structure separate from the 
dwelling,  building  or  structure  used  in  whole  or  in  part  for 
residential purposes.
(c)  

Manufacturer requirements — Gas Equipment Venting 

System  Provided.

 

When  the  manufacturer  of  Product 

Approved side wall horizontally vented gas equipment provides 
a venting system design or venting system components with 
the equipment, the instructions provided by the manufacturer 
for installation of the equipment and the venting system shall 
include:
1.  Detailed  instructions  for  the  installation  of  the  venting 
system design or the venting system components; and
.  A  complete  parts  list  for  the  venting  system  design  or 
venting system.
(d) 

Manufacturer  requirements  —  Gas  Equipment 

Venting System Not Provided. 

When the manufacturer of 

a Product Approved side wall horizontally vented gas fueled 
equipment  does  not  provide  the  parts  for  venting  the  flue 
gases, but identifies “special venting systems,” the following 
requirements shall be satisfied by the manufacturer:
1. The referenced "special venting system" instructions shall 
be  included  with  the  appliance  or  equipment  installation 
instructions; and
. The “special venting systems” shall be Product Approved 
by the Board, and the instructions for that system shall include 
a parts list and detailed installation instructions.
(e)  

A copy of all installation instructions for all Product 

Approved side wall horizontally vented gas fueled equipment, 
all venting instructions, all parts lists for venting instructions, 
and/or all venting design

Содержание TPB18NV

Страница 1: ...neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agenc...

Страница 2: ...ostat 16 Connect Remote Receiver 17 Check System Operation 17 Log Placement 18 Place Rock Wool 1 Riser and Steel Bar Installation 22 Optional Cast Iron Grate Andirons Installation 23 Flame Appearance...

Страница 3: ...local codes with the National Fuel Gas Code ANSI Z223 l NFPA54 10 This unit complies with the latest revision of ANSI Z 1 11 Unvented Heaters and also complies with ANSI Z 1 60 Decorative Vented Appli...

Страница 4: ...he gas supply piping system at test pressures equal to or less than 1 psig 3 5 kPa 3 Do not use this room heater if any part has been under water Immediately call a qualified service technician to ins...

Страница 5: ...THERMAL GENERATOR The millivolt gas log pilot is fitted with a Millivolt thermopile generator to provide power for remote activation MAkE SURE YOU HAVE RECEIVED ALL PARTS Check your packing list to ve...

Страница 6: ...or less with openings gasketed or sealed b weather striping has been added on openable windows and doors and c caulking or sealants are applied to areas such as joints around window and door frames b...

Страница 7: ...front opening of the fireplace Some examples of barri ers are glass screen door frames and sunken recessed fireplaces Height of Minimum Depth of Restriction x Fireplace Firebox No Restriction 13Z v 0...

Страница 8: ...into a fireplace with no wooden mantel shelf or other combus tible projection above the fireplace open ing measure the heat resistant material height per Figure 5 then see TABLE A Heat resistant mater...

Страница 9: ...ial to at least 8 install hood and observe profiles Figure install hood and 7 OR extend heat resistant material to observe profiles in at least 1 and observe profiles in Figure 8 OR extend Figure 9 he...

Страница 10: ...eding the maximum acceptable distance of 1 The mantel also projects 7 at 141 above the opening exceeding the maximum acceptable distance of 6 If your mantel profile is unsafe you may either Raise the...

Страница 11: ...minimum of 14 of noncombustible material such as slate or marble is installed between the base of the fireplace and the combustible flooring Figure 12 13 8 M i n i m u m FP2003 min clear comb floor 1...

Страница 12: ...ce as directed in this manual INSTALLATION WARNING Before installing in a solid fuel burning fireplace The chimney flue and firebox must be cleaned of soot creosote ashes and loose paint by a qualifie...

Страница 13: ...ing noncombustible materials as described in Placement in a Fireplace with Restrictive Barrier on Page 7 ASSEMBLY PROCEDURE 1 Center the gas log unit on the fireplace or firebox Make certain the front...

Страница 14: ...lve must be installed upstream of the appliance Union tee and plugged 1 8 NPT pressure tapping point should be installed upstream of the appliance Figure 15 FP2007 gas connection FP 007 Pipe Coupling...

Страница 15: ...ter solution after completing connection DO NOT USE AN OPEN FLAME Check the gas pressure with the appliance burning and the control set to HIGH Millivolt Valve Control Figure 16 The valve regulator co...

Страница 16: ...er The Millivolt valve is a self powered combination gas control THAT DOES NOT REQUIRE 110V AC TO OPERATE CAUTION Label all wires prior to disconnection when servicing controls Wiring errors can cause...

Страница 17: ...tomatic valve still does not come on replace the control If the closed circuit reading A reading is less than 175 Millivolts determine cause for low reading proceed to Section B below B Thermopile Out...

Страница 18: ...o the safe and clean operation of this heater Sooting and other problems may result if the logs are not properly and firmly positioned in the appliance Never add additional logs or embellishments such...

Страница 19: ...018 TPB right base log Right Base Log LG1018 Figure 20 Place right base log on two pins on right side of grate Figure 20 LG1019 TPB left base log Figure 21 Left Base Log 3 LG1019 3 Place left base log...

Страница 20: ...wo pins on bottom right side of grate Figure 22 5 Place right end of left top log 5 on bottom center grate pin Place left end of left top log on top of the left base log Figure 23 6 Place right top lo...

Страница 21: ...the burner surface in between the logs Do not add additional rock wool Refer to Figure 24 for the approximate area to place rock wool Wash hands after placing rock wool Itching may occur WARNING Use o...

Страница 22: ...ight of the burner will hold the grate in place Figures 29 and 30 RISER and STEEL BAR GRATE INSTALLATION FP2869 riser Screw Hole Riser FP 869 Figure 25 Place Burner on Riser Screw Hole FP2870 on riser...

Страница 23: ...re 31 OPTIONAL CAST IRON GRATE and ANDIRON INSTALLATION FP2873 cast iron grate Cast Iron Grate Cast Iron Grate FP 873 Figure 29 Install Cast Iron Grate ANDIRON INSTALLATION Optional andirons are avail...

Страница 24: ...r near burners This may cause sooting Place volcanic rock only on the floor of the fireplace During initial operation of the new heater burning logs will give off a paper burning smell and orange flam...

Страница 25: ...harmful but may produce annoying smoke and smells as they are burned off during the initial operation of the appliance possibly causing headaches or eye or lung irritation this is a normal and tempora...

Страница 26: ...gas supplier call the fire department C Use only your hand to push in or turn the gas control knob Never use tools If the knob will not push in or turn by hand don t try to repair it Call a qualified...

Страница 27: ...30 seconds or longer to allow air to bleed out of the gas piping 7 With the control knob pushed in push in and release the piezo ignitor button to light the pilot 8 Continue pushing the control knob i...

Страница 28: ...becomes irritated wash gently with soap and water Refer to manual for correct log placement PERIODIC CLEANING Refer to parts diagram for location of items discussed below Do not use cleaning fluid to...

Страница 29: ...utoff valve closed Control knob not in PILOT position 3 Control knob not pressed in while in PILOT position 4 Air in gas lines when installed 5 ODS pilot is clogged 6 Gas regulator setting is not corr...

Страница 30: ...1 Burner orifice is clogged or dam aged Burner is damaged 3 Gas regulator is defective 1 Vapors from paint or curing process of logs 1 Turning control knob to HIGH posi tion when burner is cold Air i...

Страница 31: ...B30 Ref Description Qty Natural Propane Natural Propane Natural Propane 1 Piezo Ignitor 1 14D0503 14D0503 14D0503 14D0503 14D0503 14D0503 Piezo Wire 1 00K063 00K063 00K063 00K063 00K063 00K063 3 Burme...

Страница 32: ...1 70D003 70D0 3 Left Front Base Log 3 1 70D01 3 70D0033 70D0 3 4 Right Frong Log 4 1 70D01 7 70D0037 70D0 7 5 Left Top Log 5 1 70D0139 70D0065 70D0 9 6 Right Top Log 6 1 70D01 4 70D0034 70D0 4 WARNING...

Страница 33: ...Kit WT On Off Remote RCB RCM WMTD Thermostat Remote RSCT RCT WWTD Remote Receiver Cover Ember RRCE Remote Receiver Cover Metal RRCM On Off Touch Light Remote TLM Remote Touch Light T Stat TLT Cast Iro...

Страница 34: ...comply with the above requirements provided however that during said thirty 30 day period a battery operated carbon monoxide Massachusetts Residents Only Please read and follow these special requirem...