TPB Series Log Set
CLEARANCES and HEIGHT REQUIREMENTS
FP2865a
minimum mantel clearance no hood
10 ” o r l e s s
12”
28 ”
Heat
Resistant
Material
Heater in
Fireplace or
Firebox
FP865a
Figure 9 -
Minimum Mantel Clearance with No Hood
- TPB24/30
Figure 10 is an example of an unsafe mantel instal-
lation.
This mantel projects 4" at 8" above the opening,
exceeding the maximum acceptable distance of
1
/
"
The mantel also projects 7" at 14
1
/
" above the opening,
exceeding the maximum acceptable distance of 6".
If your mantel profile is unsafe, you may either:
• Raise the mantel to an acceptable height
OR
• Remove the mantel
Example:
The bottom
of the mantel may
project from the wall a
maximum of 10" at a
minimum of 8" above
the opening.
FP2002
mantel clearances unsafe
14
56O
”
2
56O
"
8 "
6 "
7 "
4"
Mantel
Minimum of 8"
Heat Resistant
Material
Hood
FP00
Figure 10 -
Minimum Mantel Clearance with Hood - TPB24/30
(Example of Unsafe Installation)