B36LA8 & B36RA8 Woodburning Fireplaces

COMBUSTION AIR ASSEMBLY

&0
OUTSIDEAIRDUCT

Step 1

 

Attach outside air starting collar to 
left or right side of fireplace with four 
(4) sheet metal screws provided.

Attach Outside Air Starting Col-
lar to Fireplace

FP2173

Figure 25

Step 2

 

Attach outside air duct to starting 
collar with duct clamp.

&0
/!#INSTALL

Figure 26

6” Dia. 
Hole

Clamp

Nail 
Holes

1

2

3

2“

App.

FP1906
Duct connector
8/08

Loop Disengaged

Clamp Around

Duct

Slip Band

Through
Housing

Snap Screw

Down and 

Tighten

Band

Screw

Figure 27

FP1906

&0
$UCTCONNECTOR

Approximately

2”

Duct Connector

Insulation

Duct Clamp

FP1907

Figure 28

Combustion Air Assy. Model OAC4
Installation of the Model 403 Duct Connector

1.  Push  the  insulation  back  approximately  2”  from  the 

end of  each duct.

2.  Slip each duct over the duct connector until an equal 

length of the connector extends into each duct.

3.  Place  a  duct  clamp  over  the  end  of  each  duct  and 

tighten it down snugly.

4.  Push the insulation back into place and over the duct 

clamp.

Model OAC4 Combustion Air Assembly

1.  Remove the cover cap from the 4” outlet opening loca-

tion on the left or right outside surface of the fireplace. 
DO  NOT  REMOVE  THE  COVER  IF  THE  OUTSIDE 
AIR WILL NOT BE CONNECTED.

2.  Fasten the 4” starting collar over the hole on the left or 

right side of the fireplace with the four (4) sheet metal 
screws provided. 

Figure 24

3.  Cut a 6” diameter opening for model OAC4 in the out-

side  wall  covering  where  the  model  OAC4  outside 
grille is to be located. 

Figure 26

FP1904

4.  Select  and  cut  a  piece  of  duct  of  sufficient  length  to 

attach to the fireplace and protrude at least 3” beyond 
the  face  of  the  wall  to  which  the  OAC4  inlet  air  box 
assembly will be attached. The duct may be cut with a 
standard pocket knife. Use FP-4-U duct for maximum 
efficiency and safety. Do not use a combustible duct. 
Always use UL listed Class 0 or 1 duct material.

5.  If  the  duct  is  the  insulated  type,  push  the  insulation 

back from one end of the duct approximately 2”. 

Figure 

27

6.  Slip the exposed end of the duct over the flange tube 

of the fireplace.

7.  Place the duct clamp around the exposed end of the 

aluminum duct.

8.  Slip the band through the housing, then pull the band 

tight around the duct.

9.  Snap the band locking screw down and tighten it with 

a screwdriver or nutdriver. 

Figure 27

10.Nail or screw the combustion air assembly to the sur-

face of the wall.

NOTE:

 If the wall covering is brick or stone, use appro-

priate masonry fasteners. Mount the combustion air as-
sembly  with  “TOP”  up  to  prevent  rain  from  entering  the 
assembly. Be sure the 6” diameter opening around the air 
duct is sealed with insulating material to prevent cold air 
from entering through the wall. If it is necessary to splice 
the duct, a model 403 duct connector should be installed 
as described in 

Figure 26

.

Содержание B36LA8

Страница 1: ...r Residential Installation 36 Built in Wood Burning Corner Fireplace with Optional Outside Air and Glass Doors WARNING This fireplace has not been tested with an unvented gas log set To reduce risk of...

Страница 2: ...installation you should check with local building officials to obtain required permits and assure compliance with local regulations and coded If you encounter problems with code requirements contact...

Страница 3: ...ed for supplemental heating only and is not intended for use as a primary heating system The fireplace is designed to sit directly on a combustible floor The fireplace must be installed with clearance...

Страница 4: ...the precautions and recommendations in the section of this manual pertaining to outside combustion air assembly The fireplace is also equipped with a flue damper which must be open when the fireplace...

Страница 5: ...provides for the installation of the model LF FS 2 firestop spacer in a residential installation Since the pitch of the roof influences the opening size required at the roof level table 1 should be u...

Страница 6: ...himney 1Z x Min Air space Clear ance to Combustibles Chimney Section SK81 1 ft pipe SK818 18 pipe SK83 3 ft pipe SK84 4 ft pipe Top Spacer Zero Clearance to Combustibles at Side Spacers Glass Doors Mo...

Страница 7: ...Model I658 Clearance from Fireplace Opening to Sidewall When Wall Shield is not Used B36RA8 Hearth Extension Model I627 Hearth Extension Model I658 Minimum Clearance from Fireplace Opening to Sidewal...

Страница 8: ...hearth extension and the face of the fireplace To help prevent the crack from developing the hearth extension materials must be firmly fastened in place Wall ties should be screwed to the face of the...

Страница 9: ...yramid style chimney cap used to terminate chimney through a chase Includes adapter Flashing not included CF8CA Adapter kit Unites square termination with chimney pipe 202036 Housing extensions Extend...

Страница 10: ...3 Min Storm Collar Flashing Roof Joist Shields Attic Space Refer to Table 1 for Roof Opening Size FS Firestop Spacer 14Z x x 14Z x Framed Opening 1Z x Clearance to Com bustibles with Firestop SK8 Seri...

Страница 11: ...tional for cold climate not a requirement for unit op eration Termination Cap Storm Collar Pan Flashing Draftstop Top Spacer Surround Screen Firebox Metal Safety Strips 1 2 or 3 pieces Nailing Flange...

Страница 12: ...oist 1Z x Clear ance to Combus tibles When Using Firestop Max Installation Height 86 14Z x Square Hole in Joist 1Z x Min Air Space Clear ance Between Chimney and combustibles Firestop Spacer Firestop...

Страница 13: ...arances as specified by this in struction manual 3 Set the fireplace in the desired location and be sure it is securely supported and leveled Install metal safety strip for hearth extension as shown b...

Страница 14: ...eplace Model C36RMA B36RA8 with RLK Louver kit WB36LR Glass Door and OAC6 Combustion Air Model C36LMA not shown same as above except uses LLK Louver Kit on the B36LA8 fireplace Cool Air Inlet WB36LR G...

Страница 15: ...ge to the chimney 4 Install firestop spacers at each ceiling level 5 Install the proper chimney cap or chimney housing on the chimney to prevent the entry of rain and debris into the chimney and to as...

Страница 16: ...to the chimney exit B36LA8 B36RA8 Maximum 90 0 Minimum Without Elbows 15 6 With 2 Elbows 17 6 With 4 Elbows 21 0 B Do not use more than 4 elbows per chimney Attach the straps of the return top elbow t...

Страница 17: ...lace may be used 6 A guy wire stabilizer is required for chimneys extend ing more than 6 1 8 m above a roof line The Ten Foot Rule Major U S building codes specify a minimum chimney height above the r...

Страница 18: ...hase it is also a good idea to install a firestop at the first ceiling level above the fireplace and enclose the chase with sheeting material Insulation may then be installed above sheet ing material...

Страница 19: ...size of the hole in ceiling will vary with the angle at which the chimney passes through ceiling Drive a nail up through ceiling at marked chimney center point Go to floor above and see where hole wil...

Страница 20: ...is used to keep pipe spaced properly and required for safety Nail the firestop spacer at each corner to the framing members of the ceiling hole Note A firestop spacer is not required at the roof Hole...

Страница 21: ...chimney termina tion installed Refer to installation instructions provided with the chimney termination to find correct size of roof hole There must be an air space 1 38 mm with SK8 between outermost...

Страница 22: ...E Firestop Spacer 14Z x x 14Z x Maximum four 4 elbows Per Fire place Offset Max 10 Support Straps Diagonal Chimney Enclosure Vertical Chimney Enclosure Recommended Diagonal Chimney Enclosure Acceptabl...

Страница 23: ...an exterior location which is not likely to be accidentally blocked in any manner The assembly should be located above the snow line to prevent blockage by snow accumulation 3 The combustion air inlet...

Страница 24: ...e fireplace with the four 4 sheet metal screws provided Figure 24 3 Cut a 6 diameter opening for model OAC4 in the out side wall covering where the model OAC4 outside grille is to be located Figure 26...

Страница 25: ...sions on the fireplace The following instructions only apply to passing the gas line through the fireplace wall Follow the instructions provided by the appliance for the gas line testing and ad justin...

Страница 26: ...is manual Page 13 Figure 10 Combustible mantels and trim must be installed in accordance with the National Fire Protection Association ANSI NFPA 211 Standard Section 7 2 3 3 Glass Door Installation Th...

Страница 27: ...rer Recommendation Top Edge of Fireplace Opening Mantel Installation Do Not Install Combustible Facing Material Below Top Edge of Fireplace Air Inlet Opening CAUTION Never block bottom air inlet openi...

Страница 28: ...blems If your fireplace is equipped with an outside combustion air assembly open the combustion air inlet by pushing upward on the lever located above the firebrick on the left side of the firebox NEV...

Страница 29: ...ced on a noncombustible floor or on the ground well away from all combustible materials pending final disposal If the ashes are disposed of by burial in soil or otherwise locally dispersed they should...

Страница 30: ...the chimney 9 Do install firestop spacers at each ceiling level when the chimney is installed in a multistory building 10 Do install the proper chimney cap or chimney housing on the chimney to preven...

Страница 31: ...larly 21 Don t operate the fireplace with the glass fire screen doors partially open The doors should always be fully open or fully closed 22 Don t use gasoline kerosene engine oil or charcoal lighte...

Страница 32: ...Y 40361 www mhsc com Item Description Qty B36RA8 B36LA8 1 Retainer Side Brick 1 020270 020270 2 Retainer 2 Z19901 Z19901 3a Firebrick Side Assy Right 1 014012 3b Firebrick Side Assy Left 1 021663 4 Ro...

Страница 33: ...87D0176 33 B36LA8 B36RA8 Woodburning Fireplaces...

Страница 34: ...34 87D0176 B36LA8 B36RA8 Woodburning Fireplaces...

Страница 35: ...your local building code contains restrictions on the use of this fireplace before you purchase it Blowers or fans which are warranted separately Heat loss due to the passage of heat or air through o...

Страница 36: ...MHSC 149 Cleveland Drive Paris Kentucky 40361 www mhsc com...

Отзывы: