It is important to ensure that an adequate supply of fresh air for combustion and general plant room
ventilation is provided.
The following requirements for ventilation must be met:
Or alternatively, the ventilation requirement may be met by the provision of mechanically supplied and
mechanically extracted air (interlocked to the appliance to prevent appliance operation in the event of
mechanical system failure) or mechanically supplied air (interlocked) and natural extract at the rate of:
Supply air at 1.1m
3
/
S
per 1000 kW of gross appliance input and extract air at 0.45m
3
/
S
per 1000 kW of
gross heat input.
Model
NHRE 18
NHRE 26
NHRE 36
NHRE 60
NHRE 90
High Level Free Area cm
2
N/A
N/A
N/A
N/A
388
Low Level Free Area cm
2
75
135
185
300
775
Natural Ventilation Direct to Outside Air
13.0 ventilation
requirements
14.0 appliance
location
The location chosen for the appliance must permit adequate space for maintenance and inspection and
must be capable of supporting the weight of the appliance when full of water.
Some chemicals produce vapours which can cause rapid failure of thermocouples, burners and the
water heater tank walls, if they are drawn into the combustion air supply. Therefore if this water heater
will be used to supply hot water to:
●
Hairdressers
●
Dry cleaners
●
Industrial degreasing processes
●
Or any other area where halogens or oxidising agents (such as swimming pools) are used or stored
then care should be taken to ensure that the combustion and ventilation air supply to the space where
the water heater is installed is communicated directly to outside air and free of any chemical vapour
contaminants.
15.0 Gas
connection
The gas supply to this appliance must be installed in accordance with either: BS 6891, BS5482 or
IGE/UP/2, as appropriate and the pipe used to supply the appliance must not permit a pressure drop of
more than 1 mbar from the meter to the appliance inlet connection.
Nominal inlet pressures (working) required are as follows:
Natural Gas G20
- 20 mbar
LPG G31
- 37 mbar.
The supplied gas isolation valve must be installed into the gas supply pipework adjacent to the appliance and