![MHS Boilers TUDOR NHRE 18 Скачать руководство пользователя страница 20](http://html1.mh-extra.com/html/mhs-boilers/tudor-nhre-18/tudor-nhre-18_instructions-for-installation-servicing-and-operation_1783544020.webp)
19
TUDOR NHRE
19.1
burners, injectors, burner pressure &
gas consumption data
18
26
36
60
90
Listing
C - D
C - D - E
C - D - E
C - D - E
B - F
C - D - E
A -B - F -G
Number
2
3
3
3
2
3
4
Diameter
300
300
325
325
300
365
300
Pressure
mbar
9
8.8
11.4
10.3
9.3
Diameter
175
170
190
190
175
210
170
Pressure
mbar
28
35.5
32.9
35.6
35.2
CATEGORIE: II 2H + 3P ENGLAND
Main Injector
Diameter and listing
in 1/100 of mm
Assembly arrangement
according to page 13
burner drawings
Injectors
Nat Gas
group H - G20
34.02 MJ/m
3
20
Propane
G31
46.34 MJ/m
3
37
Current Designation
Reference
Net calorific value (15ºC/1013 mbar)
Nominal Supply Pressure (mbar)
Equipment Type:
NHRE
Pilot Flame Injector (diameter 1/100 of mm)
Gas Type
27
22
18
26
36
60
90
Nat Gas
4 x 2,5
6.00
7.50
8.85
10.3
LPG
without
without
7.50
without
without
Nat Gas
2 x 2,8
26
without
28
32
LPG
without
without
without
without
without
in m
3
/h
2.33
3.60
4.65
7.08
10.47
in kg/h
1.71
2.64
3.42
5.20
7.68
Gas Valve Restrictor *
Diameter in mm
Draft Limiter
Diameter in mm
Gas Flow Rates at 15ºC & 1013,25 mbar
*The restrictor is always at the outlet of the Gas Valve block.
Содержание TUDOR NHRE 18
Страница 27: ...26 TUDOR NHRE 28 0 parts list...