5
different types of Galaxy
PW™ systems
single-UPS unit
Fig. 2
parallel UPS system
See figure 3 showing two parallel-connect-
ed (redundant) UPS units.
Fig. 3
When increased power is required (two to
four parallel units), an external bypass
must be added (see figure 4).
Fig. 4
isolation and protection
devices
(See figure 1 on previous page):
■
Q1 (Molded circuit breaker NA):
❏
isolation of the rectifier/charger (A) from
the normal AC source (1);
❏
rectifier/charger (A) start-up;
■
QF1 (circuit breaker):
❏
battery (D) protection and isolation;
■
Q5N (switch):
❏
isolation of the UPS (B) from the load;
■
Q4S (switch):
❏
isolation of the static bypass (C) from
the bypass AC source (2);
■
Q3BP (switch):
❏
bypass switch for maintenance;
■
FUE (fuses):
❏
protection of the rectifier/charger (A)
from the normal AC source;
■
FUS (fuses):
❏
protection of the inverter (B) from the
load.
Note:
■
switch Q3BP is lock on open position on
parallel UPS systems constituted to
increase available power.
external bypass for parallel
UPSs and the hot-swap
option
See figure 4.
■
Q5N: isolation of the inverters of all the
parallel UPS systems from the load;
■
Q3BP: bypass for maintenance.
2
1
Q3BP
Galaxy 1
Galaxy 2
2
1
Galaxy 3
2
1
Galaxy 4
2
2
Q5N
1
2
1
Q3BP
S
Galaxy 1
Galaxy 2
2
2
Q5N
1
1
2
A
B
C
D
User’s Manual
Introduction
Содержание Galaxy PW
Страница 1: ...Galaxy PW 100 to 225 kVA User s Manual w w w m g e u p s c o m ...
Страница 2: ......
Страница 4: ...ii Chapter name Galaxy PW 100 to 225 kVA User s Manual This page intentionally left blank ...
Страница 6: ...This page intentionally left blank iv ...
Страница 8: ...This page intentionally left blank vi ...
Страница 40: ...This page intentionally left blank 32 ...
Страница 42: ...34 ...
Страница 43: ...35 ...
Страница 44: ...1660 Scenic Avenue Costa Mesa California 92626 714 557 1636 w w w m g e u p s c o m ...