Electrical parameters for determining cable cross-sections

Characteristics

 (cont.)

this table has been drawn up for

rated phase-to-phase AC source and
load voltages of 400 V. For voltages of
380 V or 415 V, multiply the currents for
the bypass AC source and the load by
1.05 and 0.96 respectively;

the current values and cable cross-

sections for the normal AC source are
given for full rated load with a power
factor of 0.8 and a battery consuming
its minimum float charging voltage.

the battery current values and cable

cross-sections have been determined
for a battery at the end of discharging;

the current values and cable sections

for the bypass AC source and load are
given for full rated load with a power
factor of 0.8.
For frequency converters, the
parameters concerning the bypass AC
source are not applicable.

Parameters for cables for a single-UPS unit

Rated UPS

Line currents absorbed in Amps

Cross-sectional area of Cu cables in mm

2

 (2)

output

Normal AC source

400 V

Battery

Normal AC source

400 V

Battery

in kVA

with or

bypass AC

with or without battery

bypass AC

without battery (1)

source and load

source and load

20

33

29

52

16

16

16

30

49

43

72

25

25

25

40

66

58

103

35

35

35

50

83

72

128

50

35

50

60

100

87

154

50

50

70

80

133

116

205

95 or 2x50

70

95 or 2x50

100

166

144

256

95 or 2x50

70

2x70

120

199

174

308

95 or 2x50

70

2x70

160

262

231

410

95

95

2x95

200

329

289

512

120

120

2x95

(1) The rated normal AC source currents (In) have
been determined for a minimum float charging
voltage of 423 V and full rated load with a power
factor of 0.8.

(2) the cable cross-sections are given for copper
conductors (increase by 30% for aluminium
conductors). They are calculated according to
permissible temperature rise and allow for line
voltage drops over a maximum length of 100 m
(AC circuits) or 25 m (DC circuits if cables not

Recommended protection

provided). For greater lengths, the cross-sections
should be chosen to limit voltage drops to 3% (AC)
or 1% (DC).

protection upstream of
Galaxy PW

The information provided here is purely
indicative, for a single-UPS unit
supplied by a 380 to 415 V, 50 to 60 Hz
distribution system. Check that all the
criteria mentioned in the previous
section are taken into account (short-
circuit current and protection of the
static-switch semiconductors on the
bypass AC input).

Ratings of recommended protection devices upstream of a single-UPS unit
(Merlin Gerin circuit breakers)

Rated UPS

Circuit breaker on normal

Circuit breaker on bypass

output

AC input

AC input

in kVA

Circuit breaker

Control unit

Circuit breaker

Control unit

20

NS 100N 3P

TM 63D

NS 100N 4P

TM 63D

30

NS 100N 3P

TM 63D

NS 100N 4P

TM 63D

40

NS 100N 3P

TM 80D

NS 100N 4P

TM 80D

50

NS 100N 3P

TM 100D

NS 100N 4P

TM 100D

60

NS 125E 3P

TM 125D

NS 125E 4P

TM 125D

80

NS 160N 3P

TM 160D

NS 160N 4P

TM 160D

100

NS 250N 3P

TM 200D

NS 250N 4P

TM 200D

120

NS 250N 3P

TM 250D

NS 250N 4P

TM 250D

160

NS 400N 3P

STR 23 SE

NS 400N 4P

STR 23 SE

200

NS 400N 3P

STR 23 SE

NS 400N 4P

STR 23 SE

Protection downstream of
Galaxy PW

These protection devices ensure
discrimination for each of the Galaxy
PW
 output circuits. If the recommended
downstream protection is not installed
and a short-circuit occurs, the result
may be a break longer than 20 ms on
all the other output circuits.

Ratings of recommended protection devices downstream of a single-UPS unit
(Merlin Gerin circuit breakers)

Rated UPS

Downstream circuit

output

breaker(s)

in kVA

Circuit breaker Control unit

20 to 40 kVA

C60N

C 10A
B 20A

50 to 60 kVA

C60N

C 20A
B 32A

80 to 120 kVA

C60N

C 50A

NC100

B 63A

160 to 200 kVA

NC100

C 63A
B 100A

Содержание GALAXY PW 100 kVA

Страница 1: ...E 51028231XU BH 1 Installation manual www mgeups com MGE UPS SYSTEMS Galaxy PW 20 200 kVA T H E U N I N T E R R U P T I B L E P O W E R P R O V I D E R...

Страница 2: ...2 E 51028231XU BH...

Страница 3: ...Connection of power circuits 12 UPS cubicle 12 Battery cubicle 15 Connection through the top 16 External bypass cubicle 150 kVA 17 External bypass cubicle 360 kVA 18 External bypass cubicle 600 kVA 1...

Страница 4: ...for non linear load 2 Ph Ph 3 Ph N at 80 of Pn 1 Battery standard battery type gas recombination sealed lead acid battery UPS characteristics active power kW 16 24 32 40 48 64 80 96 128 160 efficiency...

Страница 5: ...tioned against the back wall connections are made through the bottom Connections through the top are available on option for all 1900 mm high cubicles except the 160 and 200 kVA units the connection c...

Страница 6: ...the bypass AC input allow for the inrush current caused by magnetisation of the transformer windings UPS output Maximum permissible current in kVA 20 43 In for 20 ms 30 29 In for 20 ms 40 21 In for 20...

Страница 7: ...ng to permissible temperature rise and allow for line voltage drops over a maximum length of 100 m AC circuits or 25 m DC circuits if cables not Recommended protection provided For greater lengths the...

Страница 8: ...and allow for line voltage drops over a The table opposite serves as an example for a parallel connected installation comprising up to four UPS units for installations with redundant units take into...

Страница 9: ...loor see figure 5 for a single UPS Galaxy PW unit with a single battery cubicle see figure 6 for a single UPS Galaxy PW unit with several battery cubicles see figure 7 for two parallel connected Galax...

Страница 10: ...llel Galaxy PW units combined for higher output see figure 11 for a Galaxy PW frequency converter without a battery Key for figures 8 and 9 1 normal AC source 2 bypass AC source A the rectifier charge...

Страница 11: ...any additional battery cubicles F the equipotential bonding connection between cubicles G K3N contactor or output static switch module Fig 11 Fig 10 2 1 C B A Q4S D E F QF1 Q1 Q5N Galaxy PW F G 2 1 C...

Страница 12: ...ternal bypass unit must imperatively be of the same length Outside the cubicles separate the auxiliary wiring from the power cables UPS cubicle See figure 12 for 20 to 60 kVA units and figure 13 for 8...

Страница 13: ...S or RELI board 80 to 200 kVA UPS T APOZ board U MISI board V modem socket switch W trough 20 to 60 kVA or binding bar 80 to 200 kVA for fine wiring X fuses for overvoltage protection RC circuit on by...

Страница 14: ...M static bypass module N rack containing electronic boards O Media Contacts 11 board Fig 14 P slot for communications boards Q FUE input fuses R FUS output fuses S ETOI board 20 to 60 kVA UPS or RELI...

Страница 15: ...move this fixture before commissioning Accidental closing of QF1 will power up the downstream circuits which could be hazardous for personnel and permanently damage the battery by deep discharge conne...

Страница 16: ...opening 460 x 197 mm with cable gland plate K top view of the cubicle Note For 160 to 200 kVA units this option is not available because air is discharged through the top However it is possible to run...

Страница 17: ...Q4S Q3BP Q5N C 317 5 6 Q5N Fig 17 External bypass cubicle 150 kVA See figure 17 Key to figure 17 A bottom view of the unit B front view of the unit C passageway for cables 317 x 120 mm D bypass AC inp...

Страница 18: ...G bypass AC input connection H connection of load I air outlet grid J opening of 460 x 197 mm for cable insertion K fuses for overvoltage protection RC circuit on bypass to be replaced when the indica...

Страница 19: ...ary position wires of switches Q4S and Q3BP C D E AA A A H G B D E Q4S Q3BP Q5N G H F I J XM8 MISI 1 1 2 Q3BP Q3BP XM9 1 2 Q4S Q4S XM8 MISI 2 1 2 Q3BP Q3BP XM9 1 2 Q4S Q4S MISI 3 MISI 4 E Q4S Q3BP 1 2...

Страница 20: ...s of redundant parallel UPSs Power cables for UPS to bypass connections are not supplied Galaxy PW cubicle with built in bypass AC input isolation transformer 20 to 60 kVA UPSs For this option the cub...

Страница 21: ...AC input connection to UPS s terminals n a b c G air inlets H air outlets I cable exit through the bottom J trough if applicable K bypass AC input isolation transformer L passage of cables through th...

Страница 22: ...00 mm high 20 to 120 kVA units width of auxiliary cubicle 715 mm 160 to 200 kVA units width of auxiliary cubicle 1015 mm For THM filter installation and connections see manual No 51024338 Key to figur...

Страница 23: ...ton This pushbutton must therefore have as many contacts as there are units in the installation as well as the contact or contacts required to open the upstream protective circuit breakers on the norm...

Страница 24: ...g the special cables A supplied connectors XM5 XM6 and XM7 on the MISI board are used to transmit signals connectors XM10 XM11 and XM12 on the MISI board are used to receive signals connector XM5 is a...

Страница 25: ...options Three slots are available on the Media Contacts 11 board for communications options See the position of these slots marked P in figures 12 to 14 Installation of boards boards may be installed...

Страница 26: ...ese cubicles are located in the same room at the same ambient temperature Connection of the battery Temperature Monitor single UPS unit Fig 31 Fig 32 Connection of the battery Temperature Monitor n pa...

Страница 27: ...necting cable to the cubicle upright so that it does not pull on the unit Installing the Temperature Monitor in a battery cubicle Fig 33 Temperature Monitor installation in a battery room The Temperat...

Страница 28: ...n SUB D connector depending on the type of AS 400 Configuration of the AS 400 Certain values on the AS 400 must be configured to enable operation of the Galaxy PW AS 400 link The values requiring modi...

Страница 29: ...ches and circuit breakers Connection of the LED indications unit optional This unit connects to the XR4 and XR5 connectors see the position of the board in the figures in the connection of Media Conta...

Страница 30: ...30 E 51028231XU BH...

Отзывы: