E-51028231XU/BH
- 7
Electrical parameters for determining cable cross-sections
Characteristics
(cont.)
◗
this table has been drawn up for
rated phase-to-phase AC source and
load voltages of 400 V. For voltages of
380 V or 415 V, multiply the currents for
the bypass AC source and the load by
1.05 and 0.96 respectively;
◗
the current values and cable cross-
sections for the normal AC source are
given for full rated load with a power
factor of 0.8 and a battery consuming
its minimum float charging voltage.
◗
the battery current values and cable
cross-sections have been determined
for a battery at the end of discharging;
◗
the current values and cable sections
for the bypass AC source and load are
given for full rated load with a power
factor of 0.8.
For frequency converters, the
parameters concerning the bypass AC
source are not applicable.
Parameters for cables for a single-UPS unit
Rated UPS
Line currents absorbed in Amps
Cross-sectional area of Cu cables in mm
2
(2)
output
Normal AC source
400 V
Battery
Normal AC source
400 V
Battery
in kVA
with or
bypass AC
with or without battery
bypass AC
without battery (1)
source and load
source and load
20
33
29
52
16
16
16
30
49
43
72
25
25
25
40
66
58
103
35
35
35
50
83
72
128
50
35
50
60
100
87
154
50
50
70
80
133
116
205
95 or 2x50
70
95 or 2x50
100
166
144
256
95 or 2x50
70
2x70
120
199
174
308
95 or 2x50
70
2x70
160
262
231
410
95
95
2x95
200
329
289
512
120
120
2x95
(1) The rated normal AC source currents (In) have
been determined for a minimum float charging
voltage of 423 V and full rated load with a power
factor of 0.8.
(2) the cable cross-sections are given for copper
conductors (increase by 30% for aluminium
conductors). They are calculated according to
permissible temperature rise and allow for line
voltage drops over a maximum length of 100 m
(AC circuits) or 25 m (DC circuits if cables not
Recommended protection
provided). For greater lengths, the cross-sections
should be chosen to limit voltage drops to 3% (AC)
or 1% (DC).
protection upstream of
Galaxy PW
The information provided here is purely
indicative, for a single-UPS unit
supplied by a 380 to 415 V, 50 to 60 Hz
distribution system. Check that all the
criteria mentioned in the previous
section are taken into account (short-
circuit current and protection of the
static-switch semiconductors on the
bypass AC input).
Ratings of recommended protection devices upstream of a single-UPS unit
(Merlin Gerin circuit breakers)
Rated UPS
Circuit breaker on normal
Circuit breaker on bypass
output
AC input
AC input
in kVA
Circuit breaker
Control unit
Circuit breaker
Control unit
20
NS 100N 3P
TM 63D
NS 100N 4P
TM 63D
30
NS 100N 3P
TM 63D
NS 100N 4P
TM 63D
40
NS 100N 3P
TM 80D
NS 100N 4P
TM 80D
50
NS 100N 3P
TM 100D
NS 100N 4P
TM 100D
60
NS 125E 3P
TM 125D
NS 125E 4P
TM 125D
80
NS 160N 3P
TM 160D
NS 160N 4P
TM 160D
100
NS 250N 3P
TM 200D
NS 250N 4P
TM 200D
120
NS 250N 3P
TM 250D
NS 250N 4P
TM 250D
160
NS 400N 3P
STR 23 SE
NS 400N 4P
STR 23 SE
200
NS 400N 3P
STR 23 SE
NS 400N 4P
STR 23 SE
Protection downstream of
Galaxy PW
These protection devices ensure
discrimination for each of the Galaxy
PW output circuits. If the recommended
downstream protection is not installed
and a short-circuit occurs, the result
may be a break longer than 20 ms on
all the other output circuits.
Ratings of recommended protection devices downstream of a single-UPS unit
(Merlin Gerin circuit breakers)
Rated UPS
Downstream circuit
output
breaker(s)
in kVA
Circuit breaker Control unit
20 to 40 kVA
C60N
C 10A
B 20A
50 to 60 kVA
C60N
C 20A
B 32A
80 to 120 kVA
C60N
C 50A
NC100
B 63A
160 to 200 kVA
NC100
C 63A
B 100A