Empty battery cubicles

Characteristics of empty battery cubicles

Cubicle width

Cubicle height

Cubicle depth

Maximum weight  (1)

in mm

in mm

in mm

in kg

715

1400 

±

 10

825

145

1900 

±

 10

825

180

1015

1400 

±

 10

825

185

1900 

±

 10

825

230

Electrical parameters for selecting protective devices

Normal AC source

The parameters given in the table
opposite can be used to determine the
required rating of the upstream
protective circuit breaker on the normal
AC input for one single-UPS or parallel-
UPS unit, a unit in economy mode or a
frequency converter.

Important:
It is essential to choose the type of
circuit breaker according to its breaking
capacity and the prospective short-
circuit current at its place of installation
(see Schneider Electric LV
documentation).

Note:
For normal AC source power supply
voltages of 380, 400 and 415 V, the
normal AC source current is the same
because it is a function of the DC
voltage.

Electrical parameters for the normal AC source

Rated

Current normal AC source

UPS

Rated current In for unit:

for 25%

for 50%

output

with battery at start without battery (2)

overload (3)

overload (3)

in kVA

of charge cycle (1)

20

36

33

41

50

30

53

49

62

74

40

71

66

83

100

50

88

83

103

124

60

107

100

125

150

80

142

133

166

200

100

179

166

208

249

120

214

199

249

299

160

282

262

329

397

200

358

329

414

501

UPS cubicles

Characteristics

 (cont.)

the cubicles are cooled by forced

ventilation. The air enters via the doors
and grids at the bottom and is
discharged through the back, or
through the roof for the 1900 mm high
cubicles (except the 160 and 200 kVA
units from which the air is discharged
through the roof only, which means the
cubicles can be positioned against the
back wall).

connections are made through the

bottom. Connections through the top
are available on option for all 1900 mm
high cubicles (except the 160 and
200 kVA units).

the connection cables may be run in

three ways:

in a trench running under the

cubicles,

under a false floor,

on the floor under the cubicles, in the

free space equal to the height of the
feet; in this case the cables should be
run side by side to avoid blocking the
flow of air for ventilation;

 the cables for connections between:

the battery and UPS cubicles (power

and control cables);

the bypass AC-source transformer in

an auxiliary cubicle and the UPS
cubicle can be supplied on option.
Layout must comply with figures 5, 6
and 7. The other power cables for
connections between cubicles are not
supplied.

only the wires for the intercubicle

control connections between parallel-
connected UPS units are supplied;

the cubicle doors are secured by

SOUTHCO locks (key CH751).

(1) the indicated weights are for the empty
cubicles, without the batteries because the total
battery weight may vary widely.

(1) the rated normal AC source currents (In) have
been determined for a rated phase-to-phase
voltage of 400 V, a battery with a 10 minute
backup time at the beginning of its charge with 206
cells at 2 Volts per cell (412 Volts) and full rated
load with a power factor of 0.8.
(2) The rated normal AC source currents (In) have
been determined for a minimum float charging
voltage of 423 V and full rated load with a power
factor of 0.8.

(3) the normal AC source currents given for an
overload of 25% or 50% are maximum values.
They have been determined for a battery with
minimum float charging voltage and a load power
factor of 0.8. When choosing the circuit breaker
rating, use the "rated current" column and check
that the circuit breaker tripping curves are
compatible with the values in the overload
columns.

Содержание GALAXY PW 100 kVA

Страница 1: ...E 51028231XU BH 1 Installation manual www mgeups com MGE UPS SYSTEMS Galaxy PW 20 200 kVA T H E U N I N T E R R U P T I B L E P O W E R P R O V I D E R...

Страница 2: ...2 E 51028231XU BH...

Страница 3: ...Connection of power circuits 12 UPS cubicle 12 Battery cubicle 15 Connection through the top 16 External bypass cubicle 150 kVA 17 External bypass cubicle 360 kVA 18 External bypass cubicle 600 kVA 1...

Страница 4: ...for non linear load 2 Ph Ph 3 Ph N at 80 of Pn 1 Battery standard battery type gas recombination sealed lead acid battery UPS characteristics active power kW 16 24 32 40 48 64 80 96 128 160 efficiency...

Страница 5: ...tioned against the back wall connections are made through the bottom Connections through the top are available on option for all 1900 mm high cubicles except the 160 and 200 kVA units the connection c...

Страница 6: ...the bypass AC input allow for the inrush current caused by magnetisation of the transformer windings UPS output Maximum permissible current in kVA 20 43 In for 20 ms 30 29 In for 20 ms 40 21 In for 20...

Страница 7: ...ng to permissible temperature rise and allow for line voltage drops over a maximum length of 100 m AC circuits or 25 m DC circuits if cables not Recommended protection provided For greater lengths the...

Страница 8: ...and allow for line voltage drops over a The table opposite serves as an example for a parallel connected installation comprising up to four UPS units for installations with redundant units take into...

Страница 9: ...loor see figure 5 for a single UPS Galaxy PW unit with a single battery cubicle see figure 6 for a single UPS Galaxy PW unit with several battery cubicles see figure 7 for two parallel connected Galax...

Страница 10: ...llel Galaxy PW units combined for higher output see figure 11 for a Galaxy PW frequency converter without a battery Key for figures 8 and 9 1 normal AC source 2 bypass AC source A the rectifier charge...

Страница 11: ...any additional battery cubicles F the equipotential bonding connection between cubicles G K3N contactor or output static switch module Fig 11 Fig 10 2 1 C B A Q4S D E F QF1 Q1 Q5N Galaxy PW F G 2 1 C...

Страница 12: ...ternal bypass unit must imperatively be of the same length Outside the cubicles separate the auxiliary wiring from the power cables UPS cubicle See figure 12 for 20 to 60 kVA units and figure 13 for 8...

Страница 13: ...S or RELI board 80 to 200 kVA UPS T APOZ board U MISI board V modem socket switch W trough 20 to 60 kVA or binding bar 80 to 200 kVA for fine wiring X fuses for overvoltage protection RC circuit on by...

Страница 14: ...M static bypass module N rack containing electronic boards O Media Contacts 11 board Fig 14 P slot for communications boards Q FUE input fuses R FUS output fuses S ETOI board 20 to 60 kVA UPS or RELI...

Страница 15: ...move this fixture before commissioning Accidental closing of QF1 will power up the downstream circuits which could be hazardous for personnel and permanently damage the battery by deep discharge conne...

Страница 16: ...opening 460 x 197 mm with cable gland plate K top view of the cubicle Note For 160 to 200 kVA units this option is not available because air is discharged through the top However it is possible to run...

Страница 17: ...Q4S Q3BP Q5N C 317 5 6 Q5N Fig 17 External bypass cubicle 150 kVA See figure 17 Key to figure 17 A bottom view of the unit B front view of the unit C passageway for cables 317 x 120 mm D bypass AC inp...

Страница 18: ...G bypass AC input connection H connection of load I air outlet grid J opening of 460 x 197 mm for cable insertion K fuses for overvoltage protection RC circuit on bypass to be replaced when the indica...

Страница 19: ...ary position wires of switches Q4S and Q3BP C D E AA A A H G B D E Q4S Q3BP Q5N G H F I J XM8 MISI 1 1 2 Q3BP Q3BP XM9 1 2 Q4S Q4S XM8 MISI 2 1 2 Q3BP Q3BP XM9 1 2 Q4S Q4S MISI 3 MISI 4 E Q4S Q3BP 1 2...

Страница 20: ...s of redundant parallel UPSs Power cables for UPS to bypass connections are not supplied Galaxy PW cubicle with built in bypass AC input isolation transformer 20 to 60 kVA UPSs For this option the cub...

Страница 21: ...AC input connection to UPS s terminals n a b c G air inlets H air outlets I cable exit through the bottom J trough if applicable K bypass AC input isolation transformer L passage of cables through th...

Страница 22: ...00 mm high 20 to 120 kVA units width of auxiliary cubicle 715 mm 160 to 200 kVA units width of auxiliary cubicle 1015 mm For THM filter installation and connections see manual No 51024338 Key to figur...

Страница 23: ...ton This pushbutton must therefore have as many contacts as there are units in the installation as well as the contact or contacts required to open the upstream protective circuit breakers on the norm...

Страница 24: ...g the special cables A supplied connectors XM5 XM6 and XM7 on the MISI board are used to transmit signals connectors XM10 XM11 and XM12 on the MISI board are used to receive signals connector XM5 is a...

Страница 25: ...options Three slots are available on the Media Contacts 11 board for communications options See the position of these slots marked P in figures 12 to 14 Installation of boards boards may be installed...

Страница 26: ...ese cubicles are located in the same room at the same ambient temperature Connection of the battery Temperature Monitor single UPS unit Fig 31 Fig 32 Connection of the battery Temperature Monitor n pa...

Страница 27: ...necting cable to the cubicle upright so that it does not pull on the unit Installing the Temperature Monitor in a battery cubicle Fig 33 Temperature Monitor installation in a battery room The Temperat...

Страница 28: ...n SUB D connector depending on the type of AS 400 Configuration of the AS 400 Certain values on the AS 400 must be configured to enable operation of the Galaxy PW AS 400 link The values requiring modi...

Страница 29: ...ches and circuit breakers Connection of the LED indications unit optional This unit connects to the XR4 and XR5 connectors see the position of the board in the figures in the connection of Media Conta...

Страница 30: ...30 E 51028231XU BH...

Отзывы: