4. Advanced Operations 

 

Environmental Monitor Status traps 

Status Error Description 

Normal 

 

The Environmental Monitor is working correctly 

NoComm 

Communication to the Environmental Monitor has been lost 

Temperature/Humidity Sensor Status traps 

Status Error Description 

Found 

 

The sensor has been detected 

NotFound 

 

No sensor has been detected 

 

Lost 

Sensor initially detected but communication to the sensor has been lost 

NoComm 

Communication to the sensor has been lost 

 

NOTE:  Traps are generated according to a hierarchical architecture; i.e. if a Tower Status enters a trap 
condition, only the Tower Status trap is generated.  Infeed and Outlet Status traps are suppressed until the 
Tower Status returns to Normal. 

Change trap 

The Change trap is generated for all outlet status changes between any on/off conditions.  Change traps 
include the outlet status, Location of the AmpMeter PDU, and identifier and name of the affected outlet.  For 
descriptions of the outlet status types, please refer to the prior table. 

Load Trap 

The Load trap is generated whenever the total input load on an infeed exceeds a preset threshold.  Load traps 
include the reported input load, load status, Location of the AmpMeter PDU, and identifier and name of the 
affected infeed. 

Any error state generates a Load trap and triggers the trap timer.  A new trap is generated at the end of every 
timer period until the Load returns to a non-error status. 

Load traps 

Status Error Description 

Normal 

 

Infeed is on and within preset thresholds 

NotOn 

 

Infeed is off 

Reading 

 

Non-error state – Load status currently being read 

LoadHigh 

Infeed current load exceeds preset threshold 

OverLoad 

Infeed current load exceeds the measurable range for the infeed 

ReadError 

Unable to read Load status 

NoComm 

x  

Communication to the infeed has been lost 

301-0399-3 Rev A. - Page 39 

Содержание AmpMeter PDU

Страница 1: ...www mgeups com AmpMeter PDU T H E U N I N T E R R U P T I B L E P O W E R P R O V I D E R Installation and user manual...

Страница 2: ...stems peritoneal dialysis systems neonatal ventilator incubators ventilators for adults or infants anesthesia ventilators infusion pumps and any other devices designated as critical by the U S FDA Com...

Страница 3: ...t Retention Bracket 6 Mounting 7 Connecting to the Power Source 7 Connecting Devices 8 Connecting the Sensors 8 Connecting to the Unit Remote Monitoring Units Only 8 OPERATIONS 10 Interfaces 10 HTML I...

Страница 4: ...the predefined user account prior to attachment to your network 1 Mount the AmpMeter PDU 6 2 Connect to the power source 3 3 Connect the devices to the AmpMeter PDU 7 4 Connect to the AmpMeter PDU 8...

Страница 5: ...nects the PDU to the electrical power source Two RJ45 connectors for Serial RS 232 and Ethernet connection remote monitoring units only F 2 L E D 1 F 1 L E D 2 Im mer Ne tzleitung au skup pe ln vor de...

Страница 6: ...tat et f d rales Der als Standleitung verwendete Zweigstromkreis muss mit einem berlastschalter bzw einer Sicherung ausgestattet sein bei Standleitungs Zweigstromkreisen mit 3 Phasen mehreren Polen m...

Страница 7: ...h the removable flanges to the mount points on the rear of the enclosure using M4 screws 2 Attach the mounting L brackets to the flanges with the supplied screws washers and nut plates The slots allow...

Страница 8: ...with two mini RJ11 T H ports for attachment of the included Temperature Humidity sensor Attach the mini RJ11 plug of the sensor s to the appropriate T H port if applicable Connecting to the Unit Remo...

Страница 9: ...HTTP SSL 13 Serial Ports 14 Users 14 FTP 15 SNTP 16 SNMP 16 Tools 17 Restart 17 COMMAND LINE INTERFACE 18 Logging In 18 Operations Commands 20 Administration Commands 22 User Administration 22 Serial...

Страница 10: ...f the predefined administrative user account after a new account with administrative rights has been created Only an administrative level user may perform operations such as creating removing user acc...

Страница 11: ...t data and allow changes to outlet states or system configuration The following sections describe each interface section page and their use Log Figure 4 Example HTML page ging In Logging in through HT...

Страница 12: ...as assignment and maintenance of the system location and tower descriptive names For description names up to 24 alphanumeric and other typeable characters ASCII 33 to 126 decimal spaces and colon cha...

Страница 13: ...IP address subnet mask or gateway In the appropriate field enter the IP address subnet mask or gateway address and press Apply Telnet SSH The Telnet SSH configuration page used to enable or disable Te...

Страница 14: ...re HTTP and SSL encrypted connections HTTPS are allowed access Required ONLY SSL encrypted connections HTTPS are allowed access Select Optional or Required from the Secure Access drop down menu and pr...

Страница 15: ...associated user On the subsequent User Edit page select Admin User On only or View only from the Access Level drop down menu and press Apply Granting or removing Environmental Monitoring viewing privi...

Страница 16: ...atus traps are suppressed until the Tower Status returns to Normal Enabling or disabling SNMP support Select Enabled or Disabled from the drop down menu and press Apply Setting the community strings E...

Страница 17: ...op down menu and press Apply Note System user outlet group configuration or outlet states are NOT changed or reset with this command Resetting to factory defaults See To reset to factory defaults from...

Страница 18: ...age 26 for more information You may enter commands in any combination of uppercase and lowercase You must enter all command characters correctly there are no command abbreviations There are two types...

Страница 19: ...PDU Set User Access Sets the access level for a user Set User Envmon Grants or removes privileges to view input and environmental monitoring status Set User Password Changes the password for a user S...

Страница 20: ...status of one or more infeed This display includes the infeed absolute and descriptive names and the Input Status and current Load reported to the AmpMeter PDU by the infeed To display status of one...

Страница 21: ...mental Monitor A Name Florida_HQ_1 Status Normal Temperature Humidity Sensors ID Name Temperature Humidity A1 Temp_Humid_Sensor_A1 Not Found Not Found A2 T H2_Florida_HQ_1 23 5 Deg C 22 RH Starting a...

Страница 22: ...type a password of up to 16 alphanumeric and other typeable characters ASCII 32 to 126 decimal Passwords are case sensitive Press Enter To specify no password press Enter at the prompt At the Verify...

Страница 23: ...ername janedoe Enter Password Enter Verify Password Enter Setting user access level privileges The Set User Access command sets the access level privileges for a user The AmpMeter PDU has two defined...

Страница 24: ...levels The List Users command displays all defined users with their access privilege level To display user access privilege levels At the AmpMeter PDU prompt type list users and press Enter Example Th...

Страница 25: ...typeable characters ASCII 33 to 126 decimal spaces are not allowed Port names are not case sensitive Press Enter Example The following command adds the descriptive name Rack1 to Console port AmpMeter...

Страница 26: ...ly or through a Telnet session If you do not issue this command or if you issue this command without specifying any text the control screen s Location field will be blank and no Welcome to banner will...

Страница 27: ...ns a descriptive name to a tower This descriptive name is displayed when the Show Traps command is issued See on page 28 for more information on the Show Traps command To create a tower name At the Am...

Страница 28: ...Enter Input Input Feed ID Feed Name AA HQ_1_Infeed_A AB HQ_1_Infeed_B BA HQ_2_Infeed_A BB HQ_2_Infeed_B Displaying the firmware version The Version command displays the firmware version To display the...

Страница 29: ...r Displaying network configuration information The Show Network command displays TCP IP Telnet SSH Web SSL and SNMP configuration information IP address subnet mask and gateway Enabled disabled status...

Страница 30: ...methods for security and validation of the username password Basic and MD5 digest For more information on authentication methods see Setting the HTTP authentication method on page 14 To set the HTTP...

Страница 31: ...mple The following command sets the FTP username to Guest AmpMeter PDU set ftp username guest Enter Setting the FTP Password The FTP Password command sets the password as required by the FTP Host To s...

Страница 32: ...Setting the SNTP server address The Set SNTP command is used to set the primary and secondary SNTP server addresses To set the SNTP server address At the AmpMeter PDU prompt type set sntp followed by...

Страница 33: ...etting up SSL Support 34 SSL Technical Specifications 34 SSH 35 Enabling and Setting up SSH Support 35 SSH Technical Specifications 35 SNMP 36 Enabling and Setting up SNMP Support 36 SNMP Traps 38 Con...

Страница 34: ...g SSL Command Summary Command Description Set SSL Enables disables SSL support Set SSL access Sets SSL access as optional or required Enabling and Setting up SSL Support NOTE A restart of the AmpMeter...

Страница 35: ...SSH Support NOTE A restart of the AmpMeter PDU is required after setting or changing ANY SSH configurations See Performing a warm boot on page 28 for more information Enabling or disabling SSH suppor...

Страница 36: ...nfigured for access to AmpMeter PDU3 MIB objects and generation of all AmpMeter PDU3 traps Enabling disabling SNMP support The AmpMeter PDU SNMP command is used to enable or disable SNMP support To en...

Страница 37: ...rovides read write access to AmpMeter PDU3 MIB objects The default Setcomm string is private To set the Setcomm community string At the AmpMeter PDU prompt type set snmp setcomm followed by the string...

Страница 38: ...I O Operational status change Change O Control status change Load I Input load out of limit All traps include the Location of the AmpMeter PDU as defined with the Set Location command See Creating a l...

Страница 39: ...ns Change traps include the outlet status Location of the AmpMeter PDU and identifier and name of the affected outlet For descriptions of the outlet status types please refer to the prior table Load T...

Страница 40: ...nsor has been lost NoComm x Communication to the sensor has been lost Humidity Trap The Humidity trap is generated whenever the umidity on a temperature humidity sensor is beyond preset thresholds Hum...

Страница 41: ...bles or disables the Outlet Status trap Show Traps Displays trap configurations Enabling or Disabling a Status trap The Set Trap Status command is used to enable or disable Status traps for a Tower In...

Страница 42: ...loadhigh followed by the infeed name and a value from 0 to 255 in amperes Press Enter Example The following command sets the infeed load limit for the second infeed on the first tower to 25 amperes us...

Страница 43: ...Humid trap To Enable or Disable the Humid trap At the AmpMeter PDU prompt type set trap ths humid followed by the sensor name and on or off Press Enter Example The following command enables the Humid...

Страница 44: ...lorida_HQ_2 ON More Y es N o y Input feed trap configuration Input Input Status Load High Feed ID Feed Name Trap Trap Thresh AA HQ_1_Infeed_A ON ON 255 A BA HQ_2_Infeed_A ON ON 255 A More Y es N o y E...

Страница 45: ...6 To reset to factory defaults using the reset button 46 UPLOADING FIRMWARE 46 To initiate an FTP upload session from the HTML interface 46 To initiate an FTP upload session from the command line 46 T...

Страница 46: ...ast ten seconds NOTE If the reset button is depressed and held for more than 15 seconds the reset will abort Uploading Firmware You may upload new versions of firmware using File Transfer Protocol FTP...

Страница 47: ...el V o ltage C urrent Vo ltage O utlet B ranch C ircuit P hase 2 T o tal M odele Tension Courrant Tension Prise Circuit de la Branche Total M odell Spannung Strom Spannung Anschlussstelle Zweigstromkr...

Страница 48: ...sse Input Entr e Eingang A B 1 2 3 4 5 6 VDx One 6 outlet module 6 outlets 1 s rie de 6 prises de courants soit au total 6 prises Dx Two 6 outlet module 12 outlets 2 s rie de 6 prises de courants soit...

Страница 49: ...a PC DB9M DCE serial port The adapter pinouts below reflect use of the adapter with the provided RJ45 crossover cable Pin DCE Signal Name Input Output 1 2 Receive Data RD Output 1 2 3 4 5 6 7 8 9 3 T...

Страница 50: ......

Страница 51: ......

Страница 52: ......

Отзывы: