Operation
3.0
Scope
Important information on the Comet 40-150kVA systems’ operation procedure sequences; for normal, on battery,
and bypass operation, with descriptions of the control and display indicators.
3.1
Power Flow
3.1.1
Power Flow, For Normal Operation
During normal operation the AC input source supplies the Rectifier, which converts the incoming AC power to
DC. The rectifier in turn supplies the Inverter, which converts DC power to AC to supply the attached load (see
Figure 3-1).
Figure 3-1: Power Flow, For Normal Operation.
3.1.2
Power Flow, For On Battery Operation
When AC input power fails, the UPS goes to on-battery operation. DC power is supplied from the UPS battery
system to the inverter, which converts battery power (DC) to AC power to supply the attached load (see Figure
3-2).
Figure 3-2: Power Flow, For On Battery Operation.
3 —1
86-160310-00 E00
Operation
INVERTER
BYPASS
INPUT
(OPTIONAL)
MAIN
INPUT
BATTERY
RECTIFIER
TO LOAD
STATIC SWITCH
INVERTER
BYPASS
INPUT
(OPTIONAL)
MAIN
INPUT
BATTERY
RECTIFIER
TO LOAD
STATIC SWITCH
Содержание 40-150kVA
Страница 2: ......
Страница 6: ...This page left blank intentionally Comet 40 150kVA iv 86 160310 00 E00...
Страница 11: ...This page left blank intentionally c v 86 160310 00 E00 Installation and User Manual...
Страница 24: ...COMET 40 150kVA Chaptername 1 12 86 160310 00 E00...
Страница 25: ...This page left blank intentionally Comet 40 150kVA 1 13 86 160310 00 E00...
Страница 31: ...COMET 40 150kVA Chaptername 2 6 86 160310 00 E00...
Страница 32: ...This page left blank intentionally Comet 40 150kVA 2 7 86 160310 00 E00...
Страница 48: ...This page left blank intentionally Comet 40 150kVA W 4 86 160310 00 E00...
Страница 52: ...Comet 40 150kVA G 4 86 160310 00 E00 This page left blank intentionally...
Страница 54: ......
Страница 55: ......