Figure 1-5:  Front View of the Comet 40-80kVA.

Comet 40-150kVA

System Description and Specifications

1 — 4

86-160310-00 E00

A

05

01

02

04

DETAIL BEHIND ITEM 

25 

(KA1) Input Contactor

(K3N) Output Contactor

(KA2) Bypass Input Contactor (Optional)

(F1, F2, F3) Input Fuses

(F4, F5, F6) Output Fuses

(SR1) Rotary Switch

Rectifier/Static Switch Assembly

Inverter Assembly

Feedback PCA

DC Power Supply PCA

Interconnect PCA

High-Frequency Power Supply PCA

(FU1-FU6) Power Supply Fuses

Teleservice Receptacles (J1-J2) & Fuse (FU13)

Heatsink Cooling Fans

(TB3) Separate Bypass Input Terminal Block

Battery Connections

(TB1) Main Input Terminal Block

(TB2) Output Terminal Block

(SR2)  Fan Control Switch

(FU7-FU12) Fan and Teleservice Fuses

Ground Busbar

Neutral Busbar

Bottom of Top-Entry Channel

Battery Charger

25

24

23

22

21

20

19

18

17

16

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

Содержание 40-150kVA

Страница 1: ...ptible Power Supply Installation and User Manual fault EMERGENCY POWER OFF U P S S Y S T E M S M G E COMET Load Protected KVA Load 0 Setup Alarms Inputs Load Battery Main UPS Input KA2 KA1 K3N QF1 loa...

Страница 2: ......

Страница 3: ...User Manual 86 160310 00 Revision A00 Initial Release 03 1997 B00 ECN 289 91 01 1998 C00 ECN 290 30 07 1998 D00 ECN 002456 02 2002 E00 ECN 004466 08 2005 Copyright 2005 MGE UPS SYSTEMS INC All rights...

Страница 4: ...part 15 of the FCC rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates us...

Страница 5: ...nd skin Comply with all applicable regulations for the disposal of the battery Batteries constitute a danger electrical shock burns The short circuit current may be very high Precautions must be taken...

Страница 6: ...This page left blank intentionally Comet 40 150kVA iv 86 160310 00 E00...

Страница 7: ...r Components 1 3 1 3 Specifications 1 8 1 3 1 AC Input Ratings 1 9 1 3 2 AC Output Ratings 1 9 1 3 3 DC Ratings 1 9 1 3 4 Mechanical Specifications UPS Cabinet Only 1 10 1 3 5 Environmental Specificat...

Страница 8: ...3 2 3 3 Startup Procedures 3 5 3 3 1 Preliminary Checks 3 5 3 3 2 Powering Up the Comet 3 5 3 4 Inverter Manual Startup 3 5 3 5 Operating Procedures 3 6 3 5 1 Normal Operation 3 6 3 5 2 Operation on...

Страница 9: ...For Bypass Operation 3 2 3 4 Comet Front Panel GUI Controls and Indicators 3 3 3 5 Output Current Overload Curve 3 7 3 6 Output Power Overload Curve 3 7 Tables table description page 1 1 Comet 40 150k...

Страница 10: ...NUMBER _______________________________________________________ BATTERY SERIAL NUMBER ___________________________________________________ ADDITIONAL MODULES SERIAL NUMBERS ____________________________...

Страница 11: ...This page left blank intentionally c v 86 160310 00 E00 Installation and User Manual...

Страница 12: ...system specifications 2 Installation Installation of the Comet 40 150kVA UPS which include receiving handling and storage procedures prerequisites to installation installation procedures and startup...

Страница 13: ...ation of UPS performance signals and communication capabilities allow total control of the UPS by its user See Figures 1 1 and 1 2 The Comet UPS and its auxiliary equipment are designed for installati...

Страница 14: ...energy in the batteries and the load is powered continuously with no disruption Figure 1 3 Single Line Diagram for the Comet 40 80kVA Figure 1 4 Single Line Diagram for the Comet 100 150kVA Comet 40 1...

Страница 15: ...right side of the UPS using c brackets provided with the cabinet Stand alone battery cabinets are remote from the UPS Refer to the battery cabinet installation drawing for more details An external ba...

Страница 16: ...ch Assembly Inverter Assembly Feedback PCA DC Power Supply PCA Interconnect PCA High Frequency Power Supply PCA FU1 FU6 Power Supply Fuses Teleservice Receptacles J1 J2 Fuse FU13 Heatsink Cooling Fans...

Страница 17: ...ser Manual Figure 1 6 Rear View of the Comet 40 80kVA System Description and Specifications 1 5 86 160310 00 E00 T1 INPUT TRANSFORMER OPTIONAL T2 OUTPUT TRANSFORMER OPTIONAL TOP ENTRY CONDUIT LANDING...

Страница 18: ...KA2 Bypass Input F1 F2 F3 Input Fuses F4 F5 F6 Output Fuses SR1 Rotary Switch Rectifier Static Switch Inverter Assembly Chopper Assembly Interconnect PCA Ground Busbar Neutral Busbar option Charger P...

Страница 19: ...al Figure 1 8 Front View of Communications Components for the Comet 100 150kVA System Description and Specifications 1 7 86 160310 00 E00 COMMUNICATION PCAs TOP CONDUIT LANDING FOR CABLE ACCESS TO PCA...

Страница 20: ...0 440 11328 600 208 180 57 180 60 00 1524 2910 1320 17552 80kVA 64 kW 208 208 222 200 222 32 75 832 2115 960 21603 220 220 210 190 210 32 75 832 2115 960 21603 480 208 222 86 222 32 75 832 1590 721 21...

Страница 21: ...itions from 0 to 100 or 100 to 0 Frequency 60 Hz 0 1 free running Phases 3 phase sequence must be A B C clockwise Wires 3 wires plus ground 480 480 VAC only Power factor 0 8 Current 480 VAC 40kVA 50kV...

Страница 22: ...nager UM1 software Table 1 2 UPS Manager Dry Contact Interface UPS Manager Dry Contact Interface DB15 Softunor DB9 Operation on Inverter Diagnostics for MGE Customer Care Center use only Operation on...

Страница 23: ...for the connection of a customer supplied battery system to Battery Subsystem the UPS External Batteries Communication Options Communication options may be used simultaneously on the Comet thus enabl...

Страница 24: ...COMET 40 150kVA Chaptername 1 12 86 160310 00 E00...

Страница 25: ...This page left blank intentionally Comet 40 150kVA 1 13 86 160310 00 E00...

Страница 26: ...by calling 1 800 438 7373 2 2 Handling Any equipment shipped on a shipping pallet is intended for handling by a pallet jack or a fork lift truck Move the equipment to its intended location while still...

Страница 27: ...fe 2 4 Prerequisite to Installation This section provides more information for a successful and efficient installation of the Comet 40 150kVA Installation of equipment must be handled by skilled techn...

Страница 28: ...ution requirements Cable sizing data is provided on the installation drawings supplied with the equipment The Comet 480 480V UPS is not a separately derived source The Comet 208 208V UPS is a separate...

Страница 29: ...supplied with your equipment CAUTION Before making any electrical connections verify that all battery disconnect circuit breaker QF1 are in the off position Customer supplied upstream protective devic...

Страница 30: ...tive and ground cables from the battery cabinet to the UPS These are terminated at the appropriate connections in the UPS cabinet see Figures 2 3 and 2 4 Additionally control wires and temperature sen...

Страница 31: ...COMET 40 150kVA Chaptername 2 6 86 160310 00 E00...

Страница 32: ...This page left blank intentionally Comet 40 150kVA 2 7 86 160310 00 E00...

Страница 33: ...ch converts DC power to AC to supply the attached load see Figure 3 1 Figure 3 1 Power Flow For Normal Operation 3 1 2 Power Flow For On Battery Operation When AC input power fails the UPS goes to on...

Страница 34: ...l operation load protected Battery power is not available load not protected Downgraded operation fault Danger of a break in the supply of power to the load load not protected Operation on battery pow...

Страница 35: ...NCY POWER OFF 1 2 3 4 5 6 7 8 9 10 10 11 11 Load Protected KVA Load 0 Setup Alarms Inputs Load Battery Main UPS Input KA2 KA1 K3N QF1 load Graphical User Interface GUI Display Emergency Power Off Swit...

Страница 36: ...t failure or detection of an AC input voltage outside of tolerances It flashes to indicate that the low battery shutdown warning level has been reached If the LED flashes when the system is not on bat...

Страница 37: ...the Static Switch The Graphical User Interface GUI display will begin to startup Apply AC input power to the unit by closing the upstream circuit breaker Put the battery circuit breaker s in the ON p...

Страница 38: ...is possible during operation on battery power to increase the battery backup time by reducing the power drawn by the load shedding of non priority load A low battery shutdown warning signal is availa...

Страница 39: ...pplied by AC input power via the Static Switch The green Load Protected LED goes off The red Load Not Protected LED goes on The operating status of the UPS is provided by the GUI display If the overlo...

Страница 40: ...ance The load can be transferred from the Inverter output to the bypass input source or back with a power interruption of 500 milliseconds Transferring the Load to Bypass Input From Inverter On the fr...

Страница 41: ...r to the load 1 Move the fan control switch SR2 to the ON position if the cooling fans were de energized during maintenance 2 Turn the manual bypass switch SR1 to the TRANSFER position 3 Wait for the...

Страница 42: ...gnostics system Before undertaking any servicing or other action note the status of the different LED s and the GUI messages displayed on the panel If an alarm is present and the load still functions...

Страница 43: ...rt of a grounded battery can result in electrical shock The likelihood of such shock will be reduced if such grounds are removed during installation and maintenance 4 2 Preventive Maintenance The foll...

Страница 44: ...d below Level Description A This level of replacement parts consists of consumable items specifically power and control fuses It is recommended to have these items on hand during installation of the U...

Страница 45: ...bject product The warranty stated herein includes parts and labor however MGE will not be liable for any labor subcontracted or performed by Purchaser for preparation of the warranted item for return...

Страница 46: ...with the product User Information Last name ________________________________________ First name ________________________________________ Company name ________________________________________ Address _...

Страница 47: ...MGE UPS SYSTEMS INC is committed to providing easy to access factory trained experts that will provide responses to any questions that you might have Scheduling Field Service Engineer Support Schedul...

Страница 48: ...This page left blank intentionally Comet 40 150kVA W 4 86 160310 00 E00...

Страница 49: ...l Standard Institute AWG American Wire Gauge Breaker Electrical circuit interrupter BTU or Btu British thermal unit Defined as the amount of heat required to raise the tempera ture of one pound of wat...

Страница 50: ...transistor Freq Frequency Frequency slew rate The change in frequency per unit of time Given in term of Hz per second Hz sec GND Ground safety Hz Hertz frequency measurement unit 1Hz is one cycle per...

Страница 51: ...fier Shipping damage Any damage done to an article while it is in transit SPDT Single Pole Double Throw Static Transfer An solid state switching mechanism electronically controlled to pass AC power di...