42

10.0

Compatible Fire Alarm Control 
Panels

UDACT-300A: 

Compatible with 

FA-1000 Series

FX-2000 Series

FleX-Net 

TM

 and 

MMX

TM

 

Fire Alarm Control Panels

Содержание UDACT-300A

Страница 1: ...Alarm Communicator Transmitter LT 888 Rev6 June 2017 Installation and Operation Manual 1 5 8 0 ENTER MENU CANCEL INFO 6 2 ABC 3 DEF 4 GHI JKL MNO 7 PRS TUV 9 WXY QZ RS 485 COMMON TROUBLE CPU FAIL LINE...

Страница 2: ......

Страница 3: ...al Connections 11 6 0 Power Up Procedures 12 7 0 Basic Operation and Supervision 13 8 0 Configuration Setup 14 8 1 Configuration with the On board Keypad 14 8 2 Configuration with UIMA and a Computer...

Страница 4: ...Alarm Control Panels 42 11 0 Connecting to a 3G4010 CF Interface Device 43 11 1 Connecting to a 3G4010 Interface Device for Canada 43 11 2 Connecting to a 3G4010CF Interface Device outside Canada 44 1...

Страница 5: ...m s UDACT 300A Digital Communicator described in this manual is listed by Underwriters Laboratories Inc ULI under Standard 864 Control Units for Fire Protective Signaling Systems These Communicators c...

Страница 6: ...ration of your equipment the telephone company will give you notice in writing to allow you to make any changes necessary to maintain uninterrupted service In certain circumstances it may be necessary...

Страница 7: ...R using Ademco Contact ID or SIA DCS reporting protocols 300 baud or 110 baud rate The UDACT 300A has the ability of disconnecting the incoming and outgoing calls and capturing the line for transmissi...

Страница 8: ...ure 1 below shows the mechanical installation for an FA 1000 FX 2000 FleX NetTM or MMXTM FACP Figure 1 UDACT 300A Mechanical Installation Note 1 Front plate is not shown 2 Reserved for PR 300 and UDAC...

Страница 9: ...reset the default passcode Jumper JW2 is required for configuring the UDACT 300A Refer to the Figure 2 for location of jumpers cable connections pushbutton and LEDs Table 1 following provides a descr...

Страница 10: ...unication is active Common Trouble Steady amber for any troubles on the Fire Alarm panel or UDACT 300A CPU Fail Steady amber for any on board CPU trouble Telephone Line 1 Telephone status indicator LE...

Страница 11: ...ction only Dialer will try to report using Line 2 first Figure 3 Telephone Line Wiring Diagram Note Most Authorities Having Jurisdiction AHJ do not allow the connection of premise telephones see speci...

Страница 12: ...Connects to P2 for Mircom FA 1000 and P4 for the Mircom FX 2000 and FleX NetTM and MMXTM Fire Alarm Control Panels 5 Connect the CFG 300 Configuration Tool to the U18 connector and place over the moun...

Страница 13: ...multiple events to a single account number within a single call session For a single event not yet reported up to 4 retries will be made within a single call attempt A failure to report to either or...

Страница 14: ...e 8 1 Configuration with the On board Keypad 1 Place jumper on JW2 located in the bottom right hand corner of the UDACT 300A board this will generate a trouble on the UDACT 300A and report this to the...

Страница 15: ...UIMA cable 3 Connect the 10 pin cable connector of the UIMA to P2 on the UDACT 300A board 4 Connect the other end of the serial or USB cable to the computer 5 Place a jumper at JW2 on the UDACT 300A b...

Страница 16: ...jumper at JW2 on the UDACT 300A board to allow the configuration a trouble is generated and reported to the receiver DACR 4 Start the Dialer Configuration Utility 5 Click the Tools menu and then click...

Страница 17: ...n mode press the Menu button on the front panel display The CFG 300 LCD will display the Main Menu The keypad on the UDACT 300A board and the CFG 300 is shown together in Figure 6 below Figure 6 UDACT...

Страница 18: ...on To exit from the main command menu press CANCEL or select the Exit menu option and then press the ENTER key Figure 8 Command Menu After you select a feature item by pressing the ENTER key use the U...

Страница 19: ...If the number of events goes beyond 500 all new incoming events will be ignored Select the type of log to view Press the ENTER key The system will then show the log chosen Use this function to select...

Страница 20: ...o 500 events Press Enter to test Line 1 Press Cancel to exit this menu For a description of test messages see Dialer Test Messages on the following page Press Enter to test Line 2 Press Cancel to exit...

Страница 21: ...l tone was detected and telephone number dialing is in process This message indicates that the dialer failed to send a DTMF tone Waiting for availability of the receiver The receiver confirms the avai...

Страница 22: ...ompleted remotely through a modem If you upload a job configuration to the panel using the PC configuration utility the job name will appear on this screen The job name can be up to a maximum of 20 ch...

Страница 23: ...changes Note time is in 24hr format The UDACT will update time and date automatically in conjunction with the FX 2000 FleX NetTM and MMXTM Command Menu Time Clock 3 Compensation Once the compensation...

Страница 24: ...ode The minimum number of digits is 4 and the maximum number is 10 ONLY numeric digits are allowed Command Menu Default Config Press UP and DOWN to select between Y N if ENTER is pressed the default c...

Страница 25: ...ring station to which the dialer reports events The maximum number of digits allowed is six For contact ID only the first four digits are used the last two are truncated If you are using the Contact I...

Страница 26: ...out where required Command Menu Dialer Config Account Info 3 Account 1 Reporting Format X CONTACT ID Default SIA 300 Baud SIA 110 Baud Set the reporting format that is recognized or preferred by the...

Страница 27: ...terface only The dial tone detection should be disabled Command Menu Dialer Config Telephone Line 5 Number of retries 06 Default Set the number of retries for both line 1 and line 2 This function lets...

Страница 28: ...ocol type Level 0 X Level 1 Default Level 2 Level 1 G Change this function as required for appropriate fire alarm panel Level 1 is the FA 1000 Level 2 is the FX 2000 FleX NetTM and MMXTM and Level 0 a...

Страница 29: ...roup number will be reported by the dialer regardless of Event Number Format selection Command Menu Dialer Config Report Options 9 Output Offset 0 Default Can be set from 1 to 9999 Used to offset the...

Страница 30: ...the FX 2000 only can be grouped so that the UDACT will report any individual input event as a group event If a device is not in the group the dialer will report the event directly Use the File menu to...

Страница 31: ...from the left side of the screen and the Dialer Configuration information will appear on the right hand as shown below 9 9 5 Select the Dialer Mode Double click on the Dialer Configuration informatio...

Страница 32: ...ort the group active event when the first circuit inside becomes active After all the active circuits are cleared the dialer will report the group restore event The Description section is used to type...

Страница 33: ...also as Fire Supv from the list of Override Selection items The Offset last column on the right is default 0 which means that Group 1 will be transmitted by the dialer to the Receiving Station as Gro...

Страница 34: ...34 Configuration and LCD Operation Once you have entered all the groups select OK and the following screen with display all the groups and their associated input circuit numbers...

Страница 35: ...ter 3 Auto test time 00 30 Default Use this function to set the time for auto test When this test is performed the test report is sent to the monitoring station The time is in 24hr format using the CF...

Страница 36: ...wing Test Times 00 00 12 a m 01 55 1 55 a m 02 00 2 00 a m and 03 00 3 00 a m Command Menu Dialer Config Enable Disable X ENABLE Default DISABLE The dialer is enabled by default When the dialer is ena...

Страница 37: ...est Event NORMAL Test New event 1 602 00 000 Periodic 24 hr Test Event OFF NORMAL Test New event 1 608 00 000 Manually initiated dialer test Test New event 1 601 00 000 Contact ID Event Description Ev...

Страница 38: ...larm New event 1 144 00 NNN Sensor Tamper Alarm restore Alarm Restore 3 144 00 NNN Hazard Alert Alarm Alarm New event 1 150 00 NNN Hazard Alert Alarm restore Alarm Restore 3 150 00 NNN Indicating Zone...

Страница 39: ...00 NNN System Reset Trouble New event 1 305 00 000 Program Change Trouble New event 1 306 00 000 Time Change Trouble New event 1 625 00 000 RAM Checksum Trouble New event 1 303 00 000 ROM Checksum Tr...

Страница 40: ...ed dialer test Test New event RX 000 Event Description Event Family Qualifier SIA Event Code Parameter Zone Fire Alarm Alarm New event FA NNN Zone Fire Alarm restored Alarm Restore FH NNN Zone Sensor...

Страница 41: ...eset Trouble New event YW 000 Program Change Trouble New event YG 000 Time Change Trouble New event JT 000 RAM ROM Checksum Trouble New event YF 000 Peripheral Trouble Trouble New event ET 000 Periphe...

Страница 42: ...42 10 0 Compatible Fire Alarm Control Panels UDACT 300A Compatible with FA 1000 Series FX 2000 Series FleX Net TM and MMXTM Fire Alarm Control Panels...

Страница 43: ...S Typical Installation in Canada Line 2 Line 1 PCS 100 POWER 24V GND PGM4 GND 14V NC COM NO TBL RELAY JW1 PGM4 AUX SUPPLY Internet Computer Printer SUR GARD SYSTEM IV Internal IP X X X X External IP X...

Страница 44: ...X X X X Port YYYY UDP Router Conventional input configured as 3G4010CF radio trouble FACP UDACT 300A 3G4010CF TRBL Option 1 dashed line Conventional input Legend ALARM RELAY SPV RELAY TRBL RELAY NO C...

Страница 45: ...ved SIA DCS and Ademco Contact ID Osborne Hoffman OH 2000 Receiver ULI Approved SIA DCS and Ademco Contact ID Silent Knight Model 9500 Receiver ULI Approved SIA DCS and Ademco Contact ID Radionics Mod...

Страница 46: ...he Communicator and the FACP Transmits Zoned Alarm Supervisory and Trouble status to a Central Monitoring Station using either Ademco Contact ID or SIA DCS Protocols User configurable locally or remot...

Страница 47: ...is the system a substitute for property owners renters or other occupants to act prudently to prevent or minimize the harmful effects of an emergency situation Building automation systems produced by...

Страница 48: ...may not provide timely warning of fires caused by carelessness or safety hazards such as smoking in bed violent explosions escaping gas improper storage of flammable materials overloaded electrical c...

Страница 49: ...Alarm notification appliances such as sirens bells horns or strobes may not warn or waken a sleeping occupant if there is an intervening wall or door It is less likely that the occupants will be alert...

Страница 50: ...of receiving station including area code ____________________ Reporting Format Contact ID SIA __________________________________________________________________________ Account 2 Identification max 6...

Страница 51: ......

Страница 52: ...660 4113 MGC 2017 Printed in Canada Subject to change without prior notice www mircomgroup com U S A 4575 Witmer Industrial Estates Niagara Falls NY 14305 Tel 888 660 4655 905 660 4655 Fax 905 660 41...

Отзывы: