5.0
Field Wiring
5.1
UDACT-300A Main Board Terminal Connections
Wire the two telephone lines to RJ31X Connector terminals as shown in Figure 3 below. The
UDACT-300A terminals are located on the top left hand corner of the board. If using a cellular
or wireless service, use the Line 2 interface connection only. Dialer will try to report using Line
2 first.
Figure 3
Telephone Line Wiring Diagram
Note:
Most Authorities Having Jurisdiction (AHJ) do not allow the connection of
premise telephones. see specifications for more information.
i
T
T
R
R
premise telephone
IF permitted
T
T
R
R
LINE-1
LINE-2
1
2
3
4
8
5
7
6
Public switch
Telephone company
wiring
TIP
RING
TIP
RING
RJ31X
RE
D
GR
EEN
GR
EY
BR
O
W
N
RES
RES
C.O.
C.O.
Line 2 is Wired as shown for Line 1
UDACT-300A
For cellular or wireless service use
Line 2