37
Configuration and LCD Operation
9.13 Exit (Command-Menu)
Pressing “ENTER” after selecting “Exit from the main menu will return the UDACT-300A to
normal.
ADEMCO
CONTACT-ID
UDACT-300A Internal Events:
UDACT-300A External Events:
Contact-ID Event Description
Event Family
Qualifier
Code
Group #
Contact #
Phone Line #1 trouble detected
Trouble
New event
1 351
00
000
Phone Line #2 trouble detected
Trouble
New event
1 352
00
000
Phone Line #1 trouble restored
Trouble
Restore
3 351
00
000
Phone Line #2 trouble restored
Trouble
Restore
3 352
00
000
Failure to report to an Account
Trouble
New event
1 354
Acct #
Acct #
Report to an Account successful
Trouble
Restore
3 354
Acct #
Acct #
RS-485 Communication Trouble
Trouble
New event
1 350
00
485
Periodic (24 hr) Test Event (NORMAL)
Test
New event
1 602
00
000
Periodic (24 hr) Test Event (OFF
NORMAL)
Test
New event
1 608
00
000
Manually initiated dialer test
Test
New event
1 601
00
000
Contact-ID Event Description
Event Family
Qualifier
Code
Group #
Contact #
Zone Fire Alarm
Alarm
New event
1 110
00
NNN
Zone Fire Alarm restored
Alarm
Restore
3 110
00
NNN
Smoke Alarm
Alarm
New event
1 111
00
NNN
Smoke Alarm restored
Alarm
Restore
3 111
00
NNN
Combustible Alarm
Alarm
New event
1 112
00
NNN
Combustible Alarm restored
Alarm
Restore
3 112
00
NNN
Fire Drill
Trouble
New event
1 604
00
NNN
Fire Drill restore
Trouble
Restore
3 604
00
NNN
Zone Trouble detected
Trouble
New event
1 300
00
NNN
Zone Trouble restored
Trouble
Restore
3 300
00
NNN
Zone Supervisory condition
Supervisory
New event
1 200
00
NNN
Zone Supervisory restored
Supervisory
Restore
3 200
00
NNN
System Trouble
Trouble
New event
1 300
00
NNN
System Trouble restore
Trouble
Restore
3 300
00
NNN