Control
Unit
E6L
/
Rev
6.11
‐
47
Standard
for
production
and
installation
EN
60439
‐
1:2005
Type
of
current
AC
50Hz
Number
of
poles
5
Rated
voltage
Un
400V/230V
+6%...
‐
10%
Rated
insulation
voltage
Ui
400V
Control
Voltage
24VDC
Rated
current
In
6A
Input
fuse
max.
3x10A
in
a
circuit
board
version
Short
‐
circuit
protection
for
transformer
2x315
mA
rapid
glass
tube
fuse
5x20mm
Overload
protection/
control
fuse
for
transformer
1
A
rapid
glass
tube
fuse
5x20mm
Resistance
against
short
circuit
ICW
<
10kA
Encapsulation
class
IP54
normal
version
Protection
against
electric
shock:
Control
Unit
Protection
class
II,
normal
version
System
Protection
class
I,
normal
version
EMC
operation
environment
A
and
B
Distribution
system
TN
‐
S
normal
version
Dimensions
(hxwxd)
290x280x170
mm,
included
in
the
length
is
the
cable
gland
flange
and
in
the
height
the
mains
switch,
normal
version
Weight
3,4
kg
normal
version
12.
TECHNICAL
DATA
Waste
electrical
products
and
batteries
should
not
be
disposed
of
with
household
waste!
Disposal
should
be
carried
out
according
to
DIRECTIVE
2002/96/EC
OF
THE
EUROPEAN
PARLIAMENT
AND
OF
THE
COUNCIL
of
27
January
2003
on
waste
electrical
and
elec
‐
tronic
equipment
and
DIRECTIVE
2006/66/EC
OF
THE
EUROPEAN
PARLIAMENT
AND
OF
THE
COUNCIL
of
6
Sep
‐
tember
2006
on
batteries
and
accumulators.
Disposal