METZ CONNECT
| Im Tal 2 | 78176 Blumberg | Deutschland | Tel. +49 7702 533-0 | Fax +49 7702 533-433
Vertrieb durch
RIA CONNECT GmbH
und
BTR NETCOM GmbH
Montageanleitung siehe www.metz-connect.com
Binary Input Objects 1 ... 10
Property
Remark / Value
RW
Object_Identifier
binary-input, instance 1 … 10
R
Object_Name
“Input 1” … “Input 10”
R
Object_Type
BINARY_INPUT (3)
R
Present_Value
INACTIVE (0) / ACTIVE (1)
RW
Status_Flags
IN_ALARM: 0
FAULT: 0
OVERRIDDEN: 0
OUT_OF_SERVICE: 0 / 1
R
Event_State
NORMAL (0)
R
Out_Of_Service
FALSE (0) / TRUE (1)
RW
Polarity
NORMAL (0) / REVERSE (1)
RW-E
Inactive_Text
“Off”
R
Active_Text
“On”
R
Notification_Class
Unsubscribed UnconfirmedCOVNotification
0: no COV notification,
1: local broadcast,
2: global broadcast
RW-E
R: Read Property, W: Write Property, -E: Storage in EEPROM
Function Table for Binary Input
Out_Of_Service
Polarity
Binary Input
Present_Value
OUT_OF_SERVICE
0
0
0
1
0
1
0
0
1
0
1
1
0
0
1
0
0
1
x
1
1
1
0
1
x
1
x: Present_Value is writeable and not affected by inputs
Group Object 1 ... 11
Property
Remark / Value
RW
Object_Identifier
group, instance 1 … 11
R
Object_Name
“Group 1” … “Group 11”
R
Object_Type
GROUP (11)
R
Present_Value
Present_Value of Binary Inputs,
see next Table
R
List_Of_Group_Members
see next Table
R
R: Read Property, W: Write Property, -E: Storage in EEPROM
Members of Groups
Group
Binary Input
1
2
3
4
5
6
7
8
9
10
1
x
x
x
x
x
x
x
x
x
x
2
x
x
x
x
x
x
x
3
x
x
x
x
x
x
x
4
x
x
x
x
x
x
5
x
x
x
x
x
6
x
x
x
x
x
7
x
x
x
x
8
x
x
x
9
x
x
x
10
x
x
11
x
x