1. Description

The BACnet MS/TP module with 10 digital inputs is designed for 

local switching operations. It is suitable to record potential-free 

switching states as for example electrical limit switches of venti-

lation valves or auxiliary contacts of power contactors. The inputs 

can be operated as contact and voltage inputs (A1, 24 VAC/DC, 

jumper J - A2) or with actuation to GND (A2, jumper J - A1), de-

pending on the setting of the jumper J. The inputs can be scanned 

by standard objects via a BACnet-Client. Addressing of the module 

and baud rate setting are done with the two address switches (x1 

/ x10) on the front. Possible settings are addresses 00 to F9 and 

baud rates 9600 Bd, 19200 Bd, 38400 Bd, 57600 Bd, 76800 Bd 

and 115200 Bd.

899299-02

Digital Input Module 

BMT-DI10

1108811319

2. Declaration of Conformity 

The device was tested according to the applicable standards. 

Conformity was proofed. The declaration of conformity is 

available at the manufacturer BTR NETCOM GmbH.

Notes Regarding Device Description

These instructions include indications for use and mounting of 

the device. In case of questions that cannot be answered with 

these instructions please consult supplier or manufacturer. 
The indicated installation directions or rules are applicable to 

the Federal Republic of Germany. If the device is used in other 

countries it applies to the equipment installer or the user to 

meet the national directions. 

Safety Instructions

Keep the applicable directions for industrial safety and prevention 

of accidents as well as the VDE rules. 
Technicians and/or installers are informed that they have to  

electrically discharge themselves as prescribed before installation 

or maintenance of the devices.
Only qualified personnel shall do mounting and installation work 

with the devices, see section “qualified personnel”. 
The information of these instructions have to be read and under-

stood by every person using this device. 

Symbols

Warning of dangerous electrical voltage 

Danger

 

means that non-observance may cause risk of life,  

grievous bodily harm or heavy material damage. 

Qualified Personnel

Qualified personnel in the sense of these instructions are persons 

who are well versed in the use and installation of such devices 

and whose professional qualification meets the requirements of  

their work. 
This includes for example:

 

Qualification to connect the device according to the VDE  

specifications and the local regulations and a qualification to 

put this device into operation, to power it down or to activate 

it by respecting the internal directions.

 

Knowledge of safety rules.

 

Knowledge about application and use of the device within the 

equipment system etc. 

3. Technical Data

BACnet Interface

Protocoll 

BACnet MS/TP

Transmission rate 

9600 ... 115200 Bd  

   

(factory setting 9600 Bd)

Cabling 

RS485 two wire bus with voltage  

   

equalizing cable in bus / line topology

Supply

Operating voltage range  20 ... 28 V AC/DC (SELV)
Current consumption 

85 mA (AC) / 75 mA (DC)

Relative duty cycle 

100 %

Input

Input voltage 

30 V DC 

High-signal recognition 

>7 V AC/DC

Housing

Dimensions WxHxD 

1.4 x 2.8 x 2.6 in. (35 x 70 x 65 mm)

Weight 

83 g

Mounting position 

any

Mounting 

standard rail TH35 per IEC 60715

Mounting in series  

the maximum quantity of modules  

without space 

connected in line is limited to 15 or 

   

to a maximum power consumption of  

   

2 Amps (AC or DC) per connection to  

   

the power supply. For any similar 

   

block of additional modules a sepa- 

   

rate connection to the power supply 

   

is mandatory.

Material 

  Housing 

Polyamide 6.6 V0 

  Terminal blocks 

Polyamide 6.6 V0

Cover plate  

Polycarbonate

Type of protection  

(IEC 60529) 

 Housing 

IP40 

  Terminal blocks 

IP20

Terminal blocks

Supply and bus 

  4 pole terminal block 

max. AWG 16 (1,5 mm²) solid wire 

   

max. AWG 18 (1,0 mm²) stranded wire

Wire diameter 

min. 0.3 mm up to max. 1.4 mm 

   

(terminal block and jumper plug are  

   

included to each packing unit)

Module connection 

  Input/Output 

max. AWG 12 (4.0 mm²) solid wire 

   

max. AWG 14 (2.5 mm²) stranded wire

Wire diameter 

min. 0.3 mm up to max 2.7 mm

Protective circuitry 

polarity reversal protection of  

   

operating voltage 

   

polarity reversal protection of supply  

   

and bus

Temperature range

Operation 

-5 °C ... +55 °C

Storage 

-20 °C ... +70 °C

Display

Operating / bus activity 

green LED

Error indication 

red LED

Status of the inputs 

yellow LED

5. Connection Diagram

BUS A-

BUS B+

2

1

3

5

4

9

8

7

6 C1

10

A1
A2

A-

B+

A1
A2

A-

B+

GND

24 V AC/DC

C1

4. Wiring Diagram

BUS A-

BUS B+

C1

1
2
3
4
5
6
7
8
9
10

A2 /GND

A1/+24 V

BACnet MS/TP on RS-485

RISC - CPU

24 V

C1

+24 V

GND

J

Содержание C Logline BMT-DI10

Страница 1: ...n die das Gerät einsetzt muss die Beschreibungen dieser Anleitung gelesen und verstanden haben Warnung vor gefährlicher elektrischer Spannung Gefahr bedeutet dass bei Nicht beachtung Lebensgefahr besteht schwere Körper verletzungen oder erhebliche Sach schäden auftreten können Qualifiziertes Fachpersonal Qualifiziertes Fachpersonal im Sinne dieser Anleitung sind Per sonen die mit den beschriebenen...

Страница 2: ...rehen um die Netzwerkadresse einzustellen Werkseinstellung 9600 Bit s Adressschalter x10 F F F F F F Adressschalter x1 A B C D E F Bitrate Bit s 9600 19200 38400 57600 76800 115200 8 Anschlussbeispiele Anschlussbeispiele 1 2 9 10 8 6 7 C1 ERROR 24V 10 1 9 2 8 3 7 4 6 5 X10 A B GND 24 V A B GND 24 V 24V 2 1 3 5 4 C1 BUSY X1 BMT DI10 BACnet MS TP Jumper unter der Blende Jumper below the faceplate A1...

Страница 3: ...VNotification 0 no COV notification 1 local broadcast 2 global broadcast RW E R Read Property W Write Property E Storage in EEPROM Function Table for Binary Input Out_Of_Service Polarity Binary Input Present_Value OUT_OF_SERVICE 0 0 0 1 0 1 0 0 1 0 1 1 0 0 1 0 0 1 x 1 1 1 0 1 x 1 x Present_Value is writeable and not affected by inputs Group Object 1 11 Property Remark Value RW Object_Identifier gr...

Страница 4: ...y harm or heavy material damage Qualified Personnel Qualified personnel in the sense of these instructions are persons who are well versed in the use and installation of such devices and whose professional qualification meets the requirements of their work This includes for example Qualification to connect the device according to the VDE specifications and the local regulations and a qualification...

Страница 5: ...to select Network Address Factory setting 9600 Bit s Adress switch x10 F F F F F F Adress switch x1 A B C D E F Bitrate Bit s 9600 19200 38400 57600 76800 115200 8 Connection examples Connection examples 1 2 9 10 8 6 7 C1 ERROR 24V 10 1 9 2 8 3 7 4 6 5 X10 A B GND 24 V A B GND 24 V 24V 2 1 3 5 4 C1 BUSY X1 BMT DI10 BACnet MS TP Jumper unter der Blende Jumper below the faceplate A1 24 V AC DC A2 GN...

Страница 6: ...VNotification 0 no COV notification 1 local broadcast 2 global broadcast RW E R Read Property W Write Property E Storage in EEPROM Function Table for Binary Input Out_Of_Service Polarity Binary Input Present_Value OUT_OF_SERVICE 0 0 0 1 0 1 0 0 1 0 1 1 0 0 1 0 0 1 x 1 1 1 0 1 x 1 x Present_Value is writeable and not affected by inputs Group Object 1 11 Property Remark Value RW Object_Identifier gr...

Отзывы: