1. Description
The BACnet MS/TP module with 10 digital inputs is designed for
local switching operations. It is suitable to record potential-free
switching states as for example electrical limit switches of venti-
lation valves or auxiliary contacts of power contactors. The inputs
can be operated as contact and voltage inputs (A1, 24 VAC/DC,
jumper J - A2) or with actuation to GND (A2, jumper J - A1), de-
pending on the setting of the jumper J. The inputs can be scanned
by standard objects via a BACnet-Client. Addressing of the module
and baud rate setting are done with the two address switches (x1
/ x10) on the front. Possible settings are addresses 00 to F9 and
baud rates 9600 Bd, 19200 Bd, 38400 Bd, 57600 Bd, 76800 Bd
and 115200 Bd.
899299-02
Digital Input Module
BMT-DI10
1108811319
2. Declaration of Conformity
The device was tested according to the applicable standards.
Conformity was proofed. The declaration of conformity is
available at the manufacturer BTR NETCOM GmbH.
Notes Regarding Device Description
These instructions include indications for use and mounting of
the device. In case of questions that cannot be answered with
these instructions please consult supplier or manufacturer.
The indicated installation directions or rules are applicable to
the Federal Republic of Germany. If the device is used in other
countries it applies to the equipment installer or the user to
meet the national directions.
Safety Instructions
Keep the applicable directions for industrial safety and prevention
of accidents as well as the VDE rules.
Technicians and/or installers are informed that they have to
electrically discharge themselves as prescribed before installation
or maintenance of the devices.
Only qualified personnel shall do mounting and installation work
with the devices, see section “qualified personnel”.
The information of these instructions have to be read and under-
stood by every person using this device.
Symbols
Warning of dangerous electrical voltage
Danger
means that non-observance may cause risk of life,
grievous bodily harm or heavy material damage.
Qualified Personnel
Qualified personnel in the sense of these instructions are persons
who are well versed in the use and installation of such devices
and whose professional qualification meets the requirements of
their work.
This includes for example:
•
Qualification to connect the device according to the VDE
specifications and the local regulations and a qualification to
put this device into operation, to power it down or to activate
it by respecting the internal directions.
•
Knowledge of safety rules.
•
Knowledge about application and use of the device within the
equipment system etc.
3. Technical Data
BACnet Interface
Protocoll
BACnet MS/TP
Transmission rate
9600 ... 115200 Bd
(factory setting 9600 Bd)
Cabling
RS485 two wire bus with voltage
equalizing cable in bus / line topology
Supply
Operating voltage range 20 ... 28 V AC/DC (SELV)
Current consumption
85 mA (AC) / 75 mA (DC)
Relative duty cycle
100 %
Input
Input voltage
30 V DC
High-signal recognition
>7 V AC/DC
Housing
Dimensions WxHxD
1.4 x 2.8 x 2.6 in. (35 x 70 x 65 mm)
Weight
83 g
Mounting position
any
Mounting
standard rail TH35 per IEC 60715
Mounting in series
the maximum quantity of modules
without space
connected in line is limited to 15 or
to a maximum power consumption of
2 Amps (AC or DC) per connection to
the power supply. For any similar
block of additional modules a sepa-
rate connection to the power supply
is mandatory.
Material
Housing
Polyamide 6.6 V0
Terminal blocks
Polyamide 6.6 V0
Cover plate
Polycarbonate
Type of protection
(IEC 60529)
Housing
IP40
Terminal blocks
IP20
Terminal blocks
Supply and bus
4 pole terminal block
max. AWG 16 (1,5 mm²) solid wire
max. AWG 18 (1,0 mm²) stranded wire
Wire diameter
min. 0.3 mm up to max. 1.4 mm
(terminal block and jumper plug are
included to each packing unit)
Module connection
Input/Output
max. AWG 12 (4.0 mm²) solid wire
max. AWG 14 (2.5 mm²) stranded wire
Wire diameter
min. 0.3 mm up to max 2.7 mm
Protective circuitry
polarity reversal protection of
operating voltage
polarity reversal protection of supply
and bus
Temperature range
Operation
-5 °C ... +55 °C
Storage
-20 °C ... +70 °C
Display
Operating / bus activity
green LED
Error indication
red LED
Status of the inputs
yellow LED
5. Connection Diagram
BUS A-
BUS B+
2
1
3
5
4
9
8
7
6 C1
10
A1
A2
A-
B+
A1
A2
A-
B+
GND
24 V AC/DC
C1
4. Wiring Diagram
BUS A-
BUS B+
C1
1
2
3
4
5
6
7
8
9
10
A2 /GND
A1/+24 V
BACnet MS/TP on RS-485
RISC - CPU
24 V
C1
+24 V
GND
J