Using Interaction Pages
Metso Automation MAX Controls
••••
277573
••••
7-3
Before you can edit configuration data on Interaction Page 9, you must place
the DPU in offline mode. While you may make entries on this page only in
Offline mode, they do not take effect until either Run or Locked mode is
entered.
Any questionable entries on this page are automatically highlighted in red.
For example, you entered a Z instead of an I or O for a DIO module. The
Interaction Page 9 section title, where the questionable entry was made, also
becomes highlighted.
HWY 1 STA 33 INTERACTION PAGE 9
DPU Configuration Page
Revision
Date 14/OC/96
Level
Time 09:32:12
MODE Run
Active
DHW 5.0
Model 585 Configuration
Backup? N
CP 5.0
Stat Page 10
IOM 5.0
DIO Inventory
I = Input,
O = Output,
A = Alarm Only
1
9
17
25
2
10
18
26
Digital
3
11
19
27
Filter Time
4
12
20
28
10 msec
5
13
21
29
6
14
22
30
7
15
23
31
8
16
24
AI Inventory
Address
Alarm
Channels
Linearization
by 16
Only
1-15
QUAD1 ( 1-15)
AI PAGE
14
14
QUAD2 (16-30)
15
15
QUAD3 (33-47)
DATA PT
14
14
QUAD4 (48-62)
15
15
Redundant I/O Address Ranges (R = Redundant, C = Common)
0
16
32
48
64
80
96
112
128
144
160
176
192
208
224
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
SERIAL I/O PORTS
Port
Baud
Link Type
Bits/Char
Stop
Parity
XON/OFF
RTS/CTS
No
Rate
(0-255)
(5,6,7,8)
(1,2)
(O,E,N)
IN OUT
IN OUT
J6
9600
25 MODB
8
1
O
N N
N N
J7
9600
214 Umax
8
2
N
N N
N N
LOCK OUT ACTIONS
MIS?
N HOST?
RELOAD?
SCREENS? N
LOG EDIT ACTIONS
MIS?
N HOST?
RELOAD?
SCREENS? N
Figure 7-2. Interaction Page 9, Operator Station Version.
The DPU will not become active until Interaction Page 9 is completely
configured and the keylock switch is in the Run or Locked position.