Model PDP DPU Installation, Preparation and Adjustment
Metso Automation MAX Controls
••••
277573
••••
7-2
Digital Input Filter Time Field
Digital Input Filter time is in milliseconds; the default is 10 milliseconds.
This digital filter can be used in place of, or with, the jumper enabled
hardware lag filter on the Model IOP DI modules.
Serial Ports Field
You may connect asynchronous serial devices to serial ports 1 and 2. The
protocols and parameters for these devices are configured here. For
additional information about serial links, refer to Publication 277574
, DPU
Embedded Serial Links User's Guide
.
Lockout and Log Options Field
In the Lock position, you may disallow certain data
DPU Bus
operations
from MIS, HOST, REloads, or Screen Edits.
DPU Configuration Page
Revision
Date 14/OC/96
Level
Time 09:32:12
MODE Run
Active
DHW 5.0
Model 530 Configuration
Backup N
CP 5.0
Stat Page
IOM 5.0
DIGITAL
FILTER TIME
10 MSEC
SERIAL I/O PORTS
Port
Baud
Link Type
Bits/Char
Stop
Parity
XON/OFF
RTS/CTS
No
Rate
(0-255)
(5,6,7,8)
(1,2)
(O,E,N)
IN OUT
IN OUT
J6
9600
25 MODB
8
1
O
N N
N N
J7
9600
214 Umax
8
2
N
N N
N N
LOCK OUT ACTIONS
MIS
N HOST?
RELOAD?
SCREENS? N
LOG EDIT ACTIONS
MIS
N HOST?
RELOAD?
SCREENS? N
Figure 7-1. Interaction Page 9 Display with Sample Configuration
.
Using Interaction Page 9 Display with an Operator Station
Use Interaction Page 9 to configure the DPU if a Model 585 Operator
Station is being used instead of a maxSTATION. Refer to Figure 7-2.