metrofires LTD Insert Скачать руководство пользователя страница 6

6

A

185mm

B

36

0mm

17

0mm

55

0mm

59

5mm

65

0mm

Refer 

Chart

Firebox Model

A

B

Width

LTD Insert

500mm

405mm

560mm

Fascia Model

Base Width

Body Width

Trend

810mm

810mm

Insert Raised

LTD Insert

0mm

455mm insulated

10mm

455mm insulated

15mm

445mm insulated

20mm

436mm insulated

25mm

424mm insulated

30mm

408mm insulated

35mm

396mm insulated

40mm

366mm insulated

41mm & above

350mm insulated

45mm
50mm & above

Minimum Floor Protector projection and type

Diagram 4

Floor protector requirements

Metro fireplace inserts are designed to be installed direct 
onto a concrete base. An insulated floor protector is required 
to project in front of the Metro and must extend a minimum 
of 200mm to each side of the door opening, making the 
minimum floor protector width 825mm. The minimum floor 
protector projection forward of the Metro is dependant on the 
height of the fireplace insert above the combustible floor. The 
following schedule of floor protector projections is measured 

from behind the Metro fascia being the total floor protector 
depth as shown in Diagram 4 below. Note, the heights 
specified above the combustible floor can be achieved by: -

•   The thickness of the floor protector

•   Or by raising the fireplace insert 

•   Or a combination of the two

Wetbacks

The Metro LTD Insert can be fitted with either of Pioneer’s 3kW 
or 4kW wetback option. Only Pioneer’s cast jacket wetback 
system as illustrated on page 9 of this manual should be fitted 
to a Metro. Alternative wetbacks will void the Metro’s emission 
approvals and may seriously effect the performance of the 
appliance and will void the owners warranty. 

Both 3kW and 4kW wetback options can be fitted to either side 
of the firebox, with the connection pipe heights illustrated in 
Diagram 4 above, please note: -

•  It is recommended the return pipe has a minimum rise of 

1 in 12. Performance will reduce as the distance to the 
storage cylinder increases.

•  The wetback must be connected to a vented system. To fit 

the wetback proceed as follows: -

1.  Remove the brick from the inside of the firebox from the 

side the wetback is to be fitted too.

2.  Expose the holes in the firebox through which the 

connection pipes will pass. 

 

The LTD Insert has a 3mm pressed washer covering these 
two openings and two 6mm bolts which are fitted inside 
the firebox near the connection holes, remove these also.

3.  Using a hole saw or snips, prepare the cabinet for the 

connection pipes. Note, these holes should be a neat 
fit or have any excess gap covered or filled with high 
temperature insulation.

4.  Using the tube of sealant supplied with the wetback, apply 

a liberal bead of sealant around both connection holes on 
the inside of the firebox. On the rear of the wetback casting 
apply the remaining contents of the tube equally around 
both connection pipes and also the outer circumference 
of the wetback which will face the inside rear wall of the 
firebox. This will completely seal the wetback to the inside 
rear wall of the fire on installation.

5.  Fit the wetback into the firebox and position the connection 

pipes through the connection holes in the firebox.

6.  Fit two bolts through the slots provided in the wetback, align 

the wetback so its front edge is parallel to the door opening 
& secure the bolts. The wetback is ready for connection to 
the storage cylinder by a registered plumber.

Содержание LTD Insert

Страница 1: ...t information 8 Where to install a Metro in your home 9 Optional wetbacks 9 Getting to know your Metro 10 Operating your Metro 10 11 Cleaning and maintenance 11 12 Troubleshooting 13 Metro warranty 14...

Страница 2: ...ATION MISUSE AND OR LACK OF MAINTENANCE WILL VOID THE WARRANTY The appliance and flue system shall be installed in accordance with AS NZS2918 and the appropriate requirements of the relevant building...

Страница 3: ...of the fascia as detailed in Diagram 2 Carefully lift the ashlip panel away from the fascia and place it gently to one side Remove the four screw s and bottom louvre as illustrated in Diagram 2 Reposi...

Страница 4: ...is packed inverted on top of the firebox and fit it into position over the cabinet sides as detailed in Diagram 1 Ensure the rear edge is fitted correctly as shown in Diagram 1 Inset B The rear edge...

Страница 5: ...nsert will fit It is usually necessary to remove the fire bricks from the lower fireplace cavity The base of the fireplace cavity on which the Metro fireplace insert will rest must be level If it is n...

Страница 6: ...appliance and will void the owners warranty Both 3kW and 4kW wetback options can be fitted to either side of the firebox with the connection pipe heights illustrated in Diagram 4 above please note It...

Страница 7: ...ooking down the chimney if not a stainless steel offset or flexi flue will be required 5 Following the instruction sheet supplied with the flue pack proceed and fit the flue with all joints sealed and...

Страница 8: ...operated with cracked or broken door glass Please note the above 3 points require regular inspection maintenance every time the ash bed is cleaned out generally 3 5 times a season and if not maintaine...

Страница 9: ...he performance of the appliance and void its warranty Note Wetback and Boiler systems are not suitable for use in locations where the water supply has lime content Lime build up inside the coil will e...

Страница 10: ...e a quantity of loosely crumpled newspaper on the base of the firebox until it is approximately 50 full of paper or place firelighters on the base of the firebox Add dry kindling and move the air cont...

Страница 11: ...or similar empty the excess ash directly into a steel or non combustible container If the ash is not disposed of immediately be careful where you store it as the ash can retain heat for many days and...

Страница 12: ...which shows illustrations of the baffle location Cleaning and maintenance for your Metro wood fire Parts guide for your Metro Baffle promet and wetback Listed below are the parts and product codes for...

Страница 13: ...l fitted as standard you will also need to add another 600mm of flue pipe to compensate as the H Cowl is shorter in length Directional Cowl designed for high wind areas Air control setting Ensure the...

Страница 14: ...not being regularly maintained and serviced warranty may be declined It is critical that the fire not be operated with over worn faulty or missing door seals Door seals will harden over time and becom...

Страница 15: ...Detectors Metro Visit us online today www metrofires co nz Metro Wood Fire Specifications Metro have a Specifications Brochure available which details relevant compliance data for every model This br...

Страница 16: ...16...

Отзывы: