2
This Metro wood fire has been tested to and complies with
AS/NZS2918:2001 when installed in accordance with this
manual. Please ensure you are fully conversant with this relevant
standard and the contents of this manual. Correct installation is
critical to the safe operation and performance of this wood fire.
Please take particular note of the following:
• It is recommended that Metro’s be installed with a Metro
ECO flue system which has been developed to enhance
the performance of Metro wood fires. Any alternative flue
system must have a minimum flue pipe length of 4.2 metres
of 150mm diameter flue pipe & have been tested to
AS/NZS2918:2001.
• The 150mm active flue pipe must be fully encased from the
ceiling to the underside of the flashing cone at the top of
the flue system, (i.e. there must not be any 150mm flue pipe
exposed).
• All flue pipe joints must be sealed and riveted. The bottom of
the flue pipe in particular MUST be fully sealed into the flue
outlet of the Metro wood fire.
• In New Zealand, the Metro must be bolted through the floor
protector into the floor to comply with the seismic restraint
provisions of AS/NZS2918:2001
• All Metro’s are extremely heavy, varying in weight from 85kgs
up to 150kgs. During the installation process do not lift the
appliance by yourself, and take care not to damage the
panel coating.
• Please take care when lifting the Metro into place onto the
hearth or floor protector as point loading may break tiles
and/or scratch surfaces.
• WE HIGHLY RECOMMEND YOU READ THIS ENTIRE
MANUAL AS INCORRECT OPERATION, MISUSE AND/OR
LACK OF MAINTENANCE WILL VOID THE WARRANTY
• The appliance and flue-system shall be installed in
accordance with AS/NZS2918 and the appropriate
requirements of the relevant building code or codes
• Any modification of the appliance that has not
been approved in writing by the testing authority is
considered to be in breach of the approval granted for
compliance with AS/NZS4013 and will void the warranty
• The appliance must be installed correctly. We recommend
a competent and suitably qualified NZHHA installer
WARNING!
Important Information
• Mixing of appliance or flue-system components
from different sources or modifying the dimensional
specification or components may result in hazardous
conditions. Where such action is considered, the
manufacturer should be consulted in the first instance
• Do not install a Metro fire if there is any sign of visible
damage to the product
• This appliance must be regularly maintained.
• Use authorised Metro replacement parts only. The use of
unauthorised parts may void the warranty
• This manual must be left with the home owner
CAUTION!
Important Information
Parts guide for your Metro – Baffle, promet and wetback
Listed below are the parts and product codes for your Metro
wood fire. The promet/baffle should be regularly checked and
must always be in place during the operation of your fire.
Note: Cracks in the promet are not uncommon and have no adverse
effect on the operation of your Metro. These cracks are the result of
intense heat coupled with expansion and contraction and is normal
wear & tear.
Your Metro wood fire must be regularly maintained and we
recommended it is also serviced annually. If a wood fire is
not regularly maintained and serviced, the life span will be
reduced. If your Metro wood fire has been neglected, by not
being regularly maintained and serviced, with authorised Metro
parts replaced as required, your warranty may be declined.
Clean air models
Type of promet required / Type of steel baffle(s) required
Water heating options
• Ambie One
Ambie One Set 500-1540
Ambie One Complete 500-2030
No wetback if this fire is
installed in a clean air zone.
The LTD wetback can be
fitted on properties 2Ha+
LTD 3kW Wetback 450-0100 or
LTD 4kW Wetback 450-0150
• Ambie Plus
Ambie Plus Set 500-1545
Ambie Plus Front 500-2035
ECO Mega Smart/Ambie Plus Rear
500-2500
ECO Wetback 450-0450
500mm
50
95
70
85
500mm
245mm
420mm
50
120
100
420mm
285mm
500mm
130mm