2.4 Installation
test
When installation has been completed simple test can be done
to verify that the calculator has been installed correctly. Wait
until the flow sensor supplies a pulse. This shall result in the
symbol for flow sensor pulse, a square shown on display will
flashing once. Check the display of the correct temperature.
Check that the built-in real time clock is working correctly. If
there is a need to change anything, see the chapter service.
2.5 Momentary
values
Momentary power, display sequence ”20”, and momentary flow, display sequence ”21”, are calculated as
follows: As long as the time between the flow sensor pulses is longer than four seconds, flow and power are
calculated for each flow sensor pulse. When the time is less than four seconds, the pulses are summated for
approximately four seconds, where after calculation takes place.
Fig. 2.4d, Display sequence temperature sensors, “22” high (H) and “23” low (L)
Fig. 2.4e, Display sequence “24”, temperature difference
Fig. 2.4c, Display sequence “63” pulse value flow sensor “63” flow sensor placing
Fig. 2.4b, Display sequence ”15” error codes
Fig. 2.4a, Flow pulse indicator