background image

  

15 

5 Verifying the calculator 

Verification of the calculator's measurement accuracy is undertaken in the test mode, where the 
energy value/flow sensor pulse is issued via the HF-output at the service adapter. For each flow 
sensor pulse, measurement takes place on the temperature sensors and a pulse burst 
corresponding to the measured energy of the meter is issued.  

To test (verify) the measurement accuracy of the calculator by means of HF-pulses proceed as 
follows:  

1.  While short circuiting the test button with a “Test key”, see fig. 4.1a and 4.1b, hold the “Push 

button” until the display mode changes. 

2.  The calculator now enters test mode. This is indicated by a flash symbol being displayed. 

3.  Connect fixed resistance for simulation of Pt100 via terminal block units Nos. 5-6 (flow) and 

7-8 (return). 

4.  Connect a pulse generator via terminal block unit Nos. 10-11 (connection 11 is ground) in 

order to simulate flow sensor pulses. Note: Voltage level is max. 3V. 

5.  Connect an OPTO-head/interface with HF-pulse interface at the front.  

6.  Simulate a flow sensor pulse after which the meter issues an (approximately) 20 kHz pulse 

burst corresponding to 100*k*dt pulses via the HF-output. “k” is the energy factor. 
(kWh/°C/m3) and dt is the difference between simulated flow and return temperatures. 

Example:

 Rf=138.50  (100.00°C), Rr=127.07  (70.00°C) => dt=30.00°C, k=1.141 gives 

100*1.141*30 = 3423 pulses 

7.  The next flow sensor pulse can be sent immediately after the HF-pulse burst from the meter 

has been dispatched. 

 

To leave test mode proceed as follows: 

1.  While short circuiting the test button hold the “Display Button”, see fig.1.1b. 

2.  The calculator now enters operation mode. 

 

To verify (test) the measurement accuracy of the meter with help of the display, first set up 
connections in accordance with points 3 and 4 above for testing by means of HF-pulses. Testing 
is undertaken in the meter's operation mode. Proceed as follows: 

1.  Supply flow sensor pulses until the energy display is incremented one step. 

2.  Supply flow sensor pulses with a maximum frequency of 12 Hz until the display has been 

stepped appropriate numbers of steps. 

3.  Errors in testing decrease with the number of steps made during the test. If the meter is 

programmed for 1.0 litre/pulse and resolution for display of energy is 0.001MWh, this means 
that 10 steps on the display correspond to 288.85 pulses from the flow sensor with selected 
temperatures in accordance with the above. The testing error is m - 1 pulse, which, 
in the example, corresponds to 0.35%. 

 

 

Содержание SVM F2

Страница 1: ...SVM F2 Calculator A small competent calculator for compact or wall montage Users manual...

Страница 2: ......

Страница 3: ...CALCULATOR 15 6 SEALS 16 7 TECHNICAL DATA 17 7 1 POWER SUPPLY 17 7 2 TEMPERATURE SENSORS 17 7 3 FLOW SENSORS 17 7 4 TEMPERATURE RANGE 17 7 5 AMBIENT TEMPERATURE TEMPERATURE CLASS 17 7 6 FLOW SENSOR PL...

Страница 4: ......

Страница 5: ...icate that the meter has left transport mode no on the display extinguishes and is replaced by 00 service mode 2 Operating mode If so ordered the F2 calculator is set to enter the operating mode direc...

Страница 6: ...or 11 0 Flow sensor 5 F High temperature sensor H 6 F High temperature sensor H 7 R Low temperature sensor L 8 R Low temperature sensor L 16 P1 Pulse input output 1 17 19 0 Pulse input output 1 and 2...

Страница 7: ...fixating the adapter 2 Guide rails 3 Adapter 2 2 Lead through F2 has six holes for connecting cables To obtain the environmental class it is vital that the diameter of cables is of the following sizes...

Страница 8: ...5 Momentary values Momentary power display sequence 20 and momentary flow display sequence 21 are calculated as follows As long as the time between the flow sensor pulses is longer than four seconds...

Страница 9: ...t starts to increment Release the button at the required sequence Change of values in the selected sequence takes place as described above If no button depression occurs during a predetermined period...

Страница 10: ...ly registers3 Accumulated volume pulse input 2 m3 46 Possible error code at time of storage of monthly register 47 Possible accumulated error time at the time of storage Minutes 4x Following monthly r...

Страница 11: ...2 Short circuit in low temperature sensor L 0004 Break in high temperature sensor H 0008 Short circuit in high temperature sensor H 0005 Error code combination 0001 0004 000A Error code combination 00...

Страница 12: ......

Страница 13: ...s necessary to proceed to date before leaving the service mode Manoeuvre in service sequence and changing values By pushing the display button the value for the blinking digit can be altered To chang...

Страница 14: ...e sequence table Table 4 1 Service sequence hh hour mm minute YY Year MM month DD Day Note The display sequence in the Service mode may vary depending on calculator configuration Service sequence Desc...

Страница 15: ...ses via the HF output k is the energy factor kWh C m3 and dt is the difference between simulated flow and return temperatures Example Rf 138 50 100 00 C Rr 127 07 70 00 C dt 30 00 C k 1 141 gives 100...

Страница 16: ...16 6 Seals 1 Service seals 2 Test seal 3 Electronic seal 4 Installation seals SVM SVM SVM SVM SVM 1 2 3 4 Fig 6 Sticker seals...

Страница 17: ...e 7 2 Cable areas for Pt100 7 3 Flow sensors Flow sensor with pulse output Max frequency Hz 12 Pulse value range l p 0 0001 9999 Min pulse length ms 40 Max voltage V 3 Max cable length m 15 Table 7 3...

Страница 18: ...3 25 0 33 0 250 0 330 0 Table 7 7 maximum power at pulse values 7 8 Dynamic behaviour Measurements are undertaken for each flow sensor pulse provided the time between the pulses is five 5 seconds or l...

Страница 19: ...lse outputs or pulse inputs on F2 F2 is equipped with two pulse inputs as standard The pulse inputs can be used for measuring of other meter with pulse outputs such as cold and hot water meters gas el...

Страница 20: ...J m KWh MBTU kW m h m 1 0 0 001 0 001 0 001 0 1 0 001 0 01 0 001 0 001 10 0 01 0 01 0 01 1 0 01 0 1 0 01 0 01 100 0 1 0 1 0 1 0 1 1 0 1 0 1 1000 1 1 1 1 1 1 1 2 5 0 001 0 01 0 01 0 1 0 01 0 01 0 001 0...

Страница 21: ...p dec 1 E Pulse Inputs 250 l p dec 0 E S Pulse Inputs 1 l p dec 3 F 1 Pulse Inputs 10 l p dec 2 F 2 Pulse Inputs 100 l p dec 1 F 3 Pulse Inputs 1000 l p dec 0 F 5 Pulse Outputs F 6 Backlight on displa...

Страница 22: ...11 X Monthly values3 accumulated volume 22 X Account days same as monthly values see above X High resolution energy High resolution volume 11 X High resolution volume 22 X X Relevant error code X X A...

Страница 23: ...AB www metrima se info metrima se Norra Stationsgatan 93 SE 113 64 Stockholm Phone 46 8 23 60 30 Fax 46 8 23 60 31 Metrima AB Stockholm Sweden Created 2003 11 07 Av Johan Tsung Rev Date 2007 09 03 Rev...

Отзывы: