![METREL PowerQ4MI 2592 Скачать руководство пользователя страница 96](http://html1.mh-extra.com/html/metrel/powerq4mi-2592/powerq4mi-2592_instruction-manual_1778984096.webp)
6 Technical specifications
96
Peak value
I
pPk,
I
NPk
, p: [1, 2, 3, 4, N], AC+DC
Measuring range
Resolution Accuracy
Range 1: 50 mV ÷ 280 mV
RMS
2
%
Range 2: 50 mV ÷ 3 Vpk
100
μ
V
2%
I
p½ Rms
, p: [1, 2, 3, 4, N], AC+DC
Measuring range
Resolution Accuracy
Crest factor
Range 1: 20.0 mV
RMS
÷ 200 mV
RMS
1 %
Range 2: 20.0 mV
RMS
÷ 2 V
RMS
100
μ
V
1 %
1.5 min
Crest factor
Cf
Ip
p: [1, 2, 3, 4, N], AC+DC
Measuring
range Resolution
Accuracy
1 ÷ 10
0.01
5 %
Current accuracy with clamps
Measurement accessory
Measuring range
Overall current accuracy
A 1033
1000 A
20 A ÷ 1000 A
1.3 %
A 1227
3000 A
300 A
30 A
300 A ÷ 6000 A
30 A ÷ 600 A
3 A ÷ 60 A
1.5 %
1.5 %
1.5 %
A 1122
5 A
100 mA ÷ 5 A
1.3 %
Note:
Overall accuracy is calculated as:
2
2
t a i n t y
C l a m p U n c e r
e r t a i n t y
P o w e r Q 4 U n c
1 , 1 5
r t a i n t y
S y s t e m U n c e
+
⋅
=
6.2.5 Frequency
Measuring
range Resolution
Accuracy
10.00 Hz ÷ 70.00 Hz
2 mHz
± 10 mHz
6.2.6 Flickermeter
Fl. Type Measuring
range Resolution
Accuracy*
P
lt1min
0.4 ÷ 4
0.001
5 % P
lt1min
P
st
0.4 ÷ 4
0.001
5 % P
st
P
lt
0.4 ÷ 4
0.001
5 % P
lt
* Guaranteed only in 49 ÷ 51Hz frequency range
6.2.7 Power
Measuring
range
(W, VAr, VA)
Resolution Accuracy
Excluding clamps
0.000 k ÷ 999.9 M
± 0.5 %
With A 1227
Flex clamps 3000A
0.000 k ÷ 999.9k
± 1.5 %
Active power
P*
With A 1033
1000 A
000.0 k ÷ 999.9 k
4 digits
± 1.3 %
ive
po
we
Excluding clamps
0.000 k ÷ 999.9 M
4 digits
± 0.5 %