5 Theory and internal operation
88
Frequency and unbalance measurement are always considered as active values for
recording.
Table bellows show number of signal for each parameter group in RECORDER.
Table 5.4: Total number of recorded quantities
1W
3W
4W
U,I,f
13 quantities
52 values per interval
20 quantities
80 values per interval.
35 quantities
140 values per interval.
Power &
Energy
16 quantities
64 values per interval
12 quantities
48 values per interval
60 quantities
240 values per interval
Flicker
3 quantities
12 values per interval
9 quantities
36 values per interval
9 quantities
36 values per interval
Symmetry
–
2 quantities
8 values per interval
4 quantities
16 values per interva
Harmonics
202 quantities
800
303 quantities
1212 values per interval
416 quantities
1628 values per interval
Total
235 347 517
5.1.14 Power and energy recording
Active power is divided into two parts: import (positive-motor) and export (negative-
generator). Reactive power and power factor are divided into four parts: positive
inductive (+i), positive capacitive (+c), negative inductive (-i) and negative capacitive (-
c).
Motor/generator and inductive/capacitive phase/polarity diagram is shown on figure
below: