3 Operating the instrument
55
Table 3.55: Description of measuring setup
Voltage range
Nominal voltage range. Select voltage range
according to the
nominal network
voltage.
1W and 4W
3W
50 ÷ 110V (L-N)
86÷190 V (L-L)
110 ÷ 240V (L-N)
190÷415 V (L-L)
240 ÷ 1000 V (L-N)
415÷1730 V (L-L)
Note:
Instrument can accurate measure at least 50%
higher than selected nominal voltage
Voltage ratio
Scaling factor for voltage transducer.
Use this factor if external voltage transformers or
dividers should be taken into account. All readings
are then related to the primary voltage. See 4.2.2 for
connection details.
Note:
scale factor can be set only when lowest
Voltage range
is selected!
Note:
Maximum value is limited to 4000.
Phase Curr. Clamps
Select phase clamps for phase current
measurements.
Note:
For Smart clamps (A1227, A1281) always
select “Smart type clamps”
Note:
See section 4.2.3 for details regarding further
clamps settings
Neutral Curr. Clams
Select neutral clamps for phase current
measurements.
Note:
For Smart clamps (A1227, A1281) always
select “Smart type clamps”
Note:
See section 4.2.3 for details regarding further
clamps settings
Connection
1W 4W 3W
Method of connecting the instrument to multi phase
systems (see 4.2.1 for details).
•
1W
: 1-phase 2-wire system
•
3W
: 3-phase 3-wire system
•
4W
: 3-phase 4-wire system