MI 2892 Power Master
Operating the instrument
94
Connection check
Check if measurement results comply with given limits.
Connection check is marked with green OK sign ( ) if instrument
is connected properly and measurement comply with given
measurement setup.
Connection check is marked with yellow OK sign (
), indicate
that some measurement are at the edge of instrument technical
specification. This does not mean that something is necessary
wrong, but require user attention to double check connection
and instrument settings. Press F4 to check LIMITS.
Fail sign ( ) indicate that that instrument is connected
incorrectly or measurement setup does not correspond with
measured value. In this case it is necessary to readjust
measurement settings, and check instrument connections.
By pressing ENTER key, detailed Connection check will be shown.
See section 4.2.4 for details, how to use this menu.
Default parameters
Set factory default parameters. These are:
Nominal voltage: 230V (L-N);
Voltage ratio: 1:1;
Δ
: 1
Phase current clamps: Smart Clamps;
Neutral current clamps: Smart Clamps;
Connection: 4W;
Synchronization: U1
System frequency: 50 Hz.
Dip voltage: 90% U
Nom
Interrupt voltage: 5% U
Nom
Swell voltage: 110% U
Nom
Signalling frequency1: 316 Hz
Signalling frequency2:1060 Hz
Signalling record duration: 10 sec
Signalling threshold: 5% of nominal voltage
RVC threshold: 3% of nominal voltage
Clear Alarm setup table