MI 2087 AL2 EasiTEST
Measurement instructions
21
How to carry out the measurement?
Step 1
q
Connect test cable
(Universal test cable) to EasiTest.
q
Set function switch to
RCD MANUAL
position,
Trip-out time initial menu
will
be displayed; see the figure below.
Fig. 13:
Trip-out time initial menu
Step 2
Select
nominal differential current I
∆
N
as follows:
q
Press the
SELECT
key, last set nominal differential current starts to blink.
q
Select appropriate value using the
▲
and
▼
keys. The following values are
available: 10mA, 30mA, 100mA, 300mA, 500mA or 1000mA. The value ×5 is
not available, if nominal current I
∆
N=1000mA.
Step 3
Select
Multiplier
of nominal differential current as follows:
q
Press the
SELECT
key after setting nominal differential current, last set
multiplier starts to blink.
q
Select appropriate value by using the
▲
and
▼
keys. The following values are
available to be selected: ×1/2, ×1, ×2, ×5. The value ×5 is not available, if
nominal current I
∆
N=1000mA.
Step 4
Select
type
of tested RCD as follows:
q
Press the
SELECT
key after setting the multiplier, last set type starts to blink.
q
Select appropriate type using the
▲
and
▼
keys. Standard (general) type (G is
displayed) or selective type (S is displayed) can be selected.
q
Press the
SELECT
key again after setting type of RCD to return to
Trip-out
time initial menu
.
G .........Standard (
G
eneral) type of
RCD is selected.
S
is
displayed, if Selective
type is selected.
∼
.........Start polarity of test
current.
×1 ........Selected multiplier of nominal
differential current.