GUPS 2400A
–104 Operation Manual
1-1
SECTION 1
OVERVIEW AND SPECIFICATIONS
1.1
Introduction
The Elgar Model GUPS 2400A-104 is a 2400 VA Global Uninterruptible Power Supply (GUPS)
that provides regulated 115 VRMS, 60 Hz output power at up to 20.9 Amps RMS load current.
The GUPS 2400A-104 accepts 3-phase AC input line voltages from 159V to 232V at
frequencies from 370 Hz to 430 Hz. A battery backup of five minutes at 2400 VA output is
provided by a removable battery pack. Output power is continuous when transferring from AC to
battery or battery to AC.
1.2
General Description
The GUPS 2400A-104 is contained in a rack-mount enclosure. All input and output connections
are made at the rear panel. Cooling air is drawn in through a filter on the front panel and
exhausted out the rear panel. Operational and input/output power status is indicated by front
panel LEDs. An AC input circuit breaker and control pushbutton switches also are located on
the front panel. There are no operator adjustments.
1.3
Specifications
(Specifications Subject to Change Without Notice)
AC Input Voltage:
115/200V, 3-phase, 3-wire plus ground, neutral not used;
159V to 232V, line voltage;
92V to 134V, phase voltage
AC Input Current:
9.8A, maximum at 200V, 2400VA/1920W load, fully charged battery;
12.5A, maximum at 159V, 2400VA/1920W load, charging battery
AC Input Frequency:
370Hz to 430Hz
Batteries:
192VDC, sealed, maintenance-free, lead-acid
Battery Hold-Up Time:
5 minutes with a 2400VA/1920W load at 25°C
Battery Recharge Time:
4 hours to 90% full charge following discharge
at 2400VA/1920W and 25°C