61
5.1 UNIT PARAMETER CONFIGURATION - Parameters Pressure Regulator I5FC0...I5FCF
Pressure Regulator Number: it is sequential starting with the Regulator installed closest to the POWERLINK terminal.
NB: the changes to the parameters can be made via the POWERLINK Master or from the keyboard.
The keyboard settings are temporary, when the system is restarted, the settings of the Master are restored.
Settings from the keyboard
In the version with the display, Press OK and ESC together to access the setting menu.
Select the parameter using the arrow keys.
Press ESC to return to the previous page.
During setting, pressure regulation is NOT active.
5.2 DISPLAY
5.2.1 LANGUAGE - Display Language I5FCx_S0B
0 = Italiano
1 = Deutsch
2 = English
3 = Español
4 = Français
5.2.2 UNIT OF MEAS - Measure Unit I5FCx_S02
0 = bar
1 = MPa
2 = psi
N.B.:
Pressure settings, like pressure regulated, dead band, full scale and minimum pressure, when set by the Master, are always defined in mbar.
5.2.3 CONTRAST - The function is only available from the keyboard
• Manual display contrast adjustment.
• Select
CONTRAST
using the arrow keys, then press OK.
• Select the value using the arrow keys, then press OK.
• Compensation as a function of temperature is automatic.
5.3 SET UP
5.3.1 INPUT - Control Type I5FCx_S0C
0 = Bus
1 = Keypad
• For the type of keypad input, set the pressure value using the arrow keys. When you press the display buttons, the set pressure appears;
when you release them, the preset pressure is displayed.
5. SETTING
5.3.2 DEAD BAND - Dead Band mbar I5FCx_S03
This indicates the pressure range in proximity to the set pressure, within which regulation is active. The deadband is + and - the set value.
It is expressed in mbar, the minimum settable value is10 mbar, the maximum value is 300 mbar.
It is advisable to enter low values, 10 or 15 mbar, only if high regulation accuracy is required. High accuracy involves more work for the
solenoid valves.