Alarm
limits
and
Current
Ranges
A
guaranteed
linear
over
‐
range
is
provided.
Device
malfunction
can
be
indicated
by
up
‐
scale
current.
Current
values
are
shown
in
the
table
below.
Direction
Values
(percent
of
range)
Values
(mA
or
V)
Linear
over
‐
range
Down
‐
0.6%
0.1%
3.89
to
3.92
mA
Up
+105.0%
1.0%
20.64
to
20.96
mA
Device
malfunction
indication
Down:
less
than
‐
1.8%
3.70
mA
Up:
greater
than
+115.0%
22.50
mA
Maximum
current
+115.0%
22.50
mA
Multi
‐
Drop
current
draw
4.0
mA