Metal Samples MS2901E Скачать руководство пользователя страница 12

8

 

 

e.

  

Wiring

 

for

 

a

 

Hazardous

 

Area

 

Installation

 

 

 

CAUTION:

  

This

 

section

 

provides

 

general

 

guidelines

 

for

 

hazardous

 

area

 

wiring.

  

However,

 

regardless

 

of

 

anything

 

stated

 

here,

 

the

 

MS2901E

 

must

 

be

 

installed

 

in

 

full

 

compliance

 

with

 

the

 

control

 

drawing

 

located

 

on

 

page

 

18

 

and

 

all

 

of

 

the

 

local

 

area

 

requirements.

 

ATTENTION

:

 

Cette

 

section

 

fournit

 

des

 

directives

 

générales

 

pour

 

le

 

câblage

 

en

 

zone

 

dangereuse.

 

Cependant,

 

indépendamment

 

de

 

tout

 

ce

 

qui

 

est

 

indiqué

 

ici,

 

le

 

MS2901E

 

doit

 

être

 

installé

 

conformément

 

au

 

schéma

 

de

 

contrôle

 

situé

 

à

 

la

 

page

 

18

 

et

 

à

 

toutes

 

les

 

exigences

 

locales.

 

 
 

Whenever

 

an

 

electrically

 

driven

 

sensor

 

or

 

measuring

 

device

 

is

 

used

 

in

 

a

 

potentially

 

explosive

 

environment

 

the

 

measuring

 

system

 

must

 

be

 

installed

 

in

 

such

 

a

 

way

 

that

 

electrical

 

energy

 

is

 

either

 

effectively

 

isolated

 

from

 

the

 

explosive

 

environment

 

(via

 

explosive

proof

 

containers,

 

cable

 

conduits,

 

etc.)

 

or

 

the

 

amount

 

of

 

electrical

 

energy

 

produced

 

in

 

the

 

hazardous

 

area

 

must

 

be

 

limited

 

to

 

a

 

permitted

 

level.

 

 

Limiting

 

electrical

 

energy

 

is

 

the

 

most

 

practical

 

method

 

of

 

protecting

 

the

 

MS2901E

 

measuring

 

system

 

when

 

the

 

Transmitter

 

is

 

installed

 

in

 

a

 

hazardous

 

area.

 

In

 

the

 

MS2901E

 

system,

 

electrical

 

energy

 

limits

 

are

 

maintained

 

using

 

a

 

power

 

supply

 

with

 

Um

 

of

 

28V

 

installed

 

in

 

the

 

4

20

 

mA

 

current

 

loop

 

per

 

standard

 

practice.

 

The

 

voltage

 

shall

 

be

 

maintained

 

all

 

the

 

time

 

in

 

accordance

 

with

 

the

 

guidance

 

given

 

in

 

IEC

 

60079

14.

 

 

Caution:

 

In

 

general

 

Safety

 

barriers

 

are

 

not

 

necessary

  

but

 

when

 

a

 

safety

 

barrier

 

is

 

used

 

with

 

the

 

MS2901E

 

system,

 

the

 

current

 

loop

 

cable

 

must

 

be

 

connected

 

to

 

the

 

barrier’s

 

hazardous

 

area

 

terminals

 

and

 

the

 

barrier

 

output

 

voltage

 

should

 

not

 

exceed

 

28V

 

at

 

any

 

circumstances.

 

All

 

other

 

connections

 

must

 

be

 

made

 

to

 

the

 

barrier’s

 

safe

 

area

 

terminals.

 

The

 

type

 

of

 

repeater

 

safety

 

barrier

 

employed

 

in

 

the

 

MS2901E

 

system

 

depends

 

on

 

the

 

specific

 

classification

 

of

 

the

 

hazardous

 

environment

 

in

 

question.

 

Metal

 

Samples

 

will

 

provide,

 

upon

 

request,

 

assistance

 

and

 

technical

 

advice

 

in

 

the

 

selection

 

of

 

a

 

repeater

 

safety

 

barrier

 

or

 

its

 

equivalent.

 

 

The

 

maximum

 

length

 

of

 

the

 

current

 

loop

 

cable

 

that

 

connects

 

the

 

MS2901E

 

Transmitter

 

to

 

the

 

repeater

 

safety

 

barrier

 

is

 

as

 

follows:

 

 
 

Example:

 

17.5

 

Volts

 

22

 

AWG

 

Cable

 

=

 

5,434

 

feet

 

maximum

 

16

 

AWG

 

Cable

 

=

 

21,788

 

feet

 

maximum

 

 

CAUTION:

  

For

 

hazardous

 

area

 

installations,

 

the

 

maximum

 

inductance

 

and

 

capacitance

 

of

 

the

 

loop

 

wiring

 

between

 

the

 

safety

 

barrier

 

and

 

the

 

transmitter

 

cannot

 

exceed

 

the

 

entity

 

parameters

 

of

 

the

 

selected

 

barrier.

 

ATTENTION

:

 

Pour

 

les

 

installations

 

en

 

zone

 

dangereuse,

 

l'inductance

 

et

 

la

 

capacité

 

maximales

 

du

 

câblage

 

de

 

la

 

boucle

 

entre

 

la

 

barrière

 

de

 

sécurité

 

et

 

le

 

transmetteur

 

ne

 

peuvent

 

pas

 

dépasser

 

les

 

paramètres

 

d'entité

 

de

 

la

 

barrière

 

sélectionnée.

 

 

 
 

Содержание MS2901E

Страница 1: ...0mA HART Transmitter Operator s Manual Metal Samples Company A Division of Alabama Specialty Products Inc 152 Metal Samples Rd Munford AL 36268 Phone 256 358 4202 Fax 256 358 4515 E mail msc alspi com...

Страница 2: ......

Страница 3: ...T at Hazardous locations 9 3 Setup and Operation 10 a Probe Selection Switches 10 b Testing the Current Loop 11 i Calibration 11 ii Testing loop output zero 4mA and span 20mA 12 iii Testing the MS2901...

Страница 4: ......

Страница 5: ...S2901E to be mounted independently from but in close proximity to the ER probe It is then connected to the probe via a short probe cable See page 5 for mounting diagrams and specifications B Principle...

Страница 6: ...faster to corrosion events and upsets compared to traditional ER meters At 16 bit resolution the MS2901E can measure metal loss amounts as small as 0 0015 of the probe life Metal loss readings taken b...

Страница 7: ...20mA without alarm 22 5mA with alarm Electrical Connection NPT entry with Ex Gland or other entries are available withadaptors Maximum Probe Cable Distance 30 ft 9 1 m Output Data Output Signal 4 20m...

Страница 8: ...el d utilisation pour les instructions d installation et les param tres d entr e et de sortie lectriques maximum Installation of the MS2901E Transmitter involves the following steps 1 Physical Mountin...

Страница 9: ...be and for foreign material in the female sockets of the transmitter connector Gently straighten any bent pins and clear any foreign material that may be found Align Key Insert Connector Tighten Coupl...

Страница 10: ...r Stem or Probe Cable 1 2 FNPT Conduit Port for Field Wiring Entry Figure 4 MS2901E current Loop Connector The maximum permissible length of the current loop wiring between the MS2901E Transmitter and...

Страница 11: ...communicate with the computer in a safe area Connect the modem across 250 Ohms resistor in line with current loop supply as shown in figure Any certified handheld terminal can be connected to the curr...

Страница 12: ...4 20 mA current loop per standard practice The voltage shall be maintained all the time in accordance with the guidance given in IEC 60079 14 Caution In general Safety barriers are not necessary but w...

Страница 13: ...m voltage applied to the instrument should be below or equal to Um 28 V Any certified handheld terminal can be connected to the current loop supply of the instrument to communicate and access the vari...

Страница 14: ...cation of the current loop connection and DCS program Figure 5 Connector and Switch Details Setting Switch 1 Switch 2 Switch 3 Switch 4 Operating Positions Wire Loop Off On On Off Tube Loop Flush On O...

Страница 15: ...oggle will increase loop current by 0 025mA h To decrease the loop current in steps of 0 025 mA toggle the Switch 3 to Up and Down Each Toggle will decrease loop current by 0 025mA i Ensure current re...

Страница 16: ...e probe extension cable from the probe 3 Connect the Meter Prover to the MS2901E probe connector stem or to the probe extension cable if the MS2901E is remote mounted 4 Loosen the MS2901E Enclosure Lo...

Страница 17: ...fe can be found in Table 1 and is also listed on the Metal Samples probe tag as the Multiplier Figure 6 Metal Samples Probe Tag Figure 7 illustrates the relationship between Loop Current and Metal Los...

Страница 18: ...nterval that is too long may give results that are insensitive to system upsets The ideal time period depends on many factors and will vary from system to system It may take some trial and error to se...

Страница 19: ...urrent Current values are shown in the table below Direction Values percent of range Values mA or V Linear over range Down 0 6 0 1 3 89 to 3 92 mA Up 105 0 1 0 20 64 to 20 96 mA Device malfunction ind...

Страница 20: ...is in good condition Then thread the enclosure lid onto the base fully Once the lid has been threaded into place tighten the Lock Screw to prevent unauthorized tampering Figure 10 Enclosure Lock Scre...

Страница 21: ...ry Annually Inspect the probe connector o ring for any signs of damage Replace as necessary Annually Inspect all electrical connections for signs of corrosion mechanical damage or foreign matter that...

Страница 22: ...AIBLES One Device Variable is implemented Meaning Units DV Loop Current mA DYNAMIC VARIABLES One Dynamic Variable is implemented Meaning Units PV Metal Loss mils 1 Power Up On power up the transmitter...

Страница 23: ...t 4 More Status Available is set whenever any failure is detected Byte Bit Description Class Device Status bits Set 0 0 PV out of Limits 1 Not Used 2 Analog Output Saturated 3 Analog output Current Fi...

Страница 24: ...Set 6 0 Not Used 1 Not Used 2 Not Used 3 Not Used 4 Not Used 5 Not Used 6 Not Used 7 Not Used Device Operating Mode Not used bits are always set to 0 Byte Bit Description Class Devie Status bits Set 7...

Страница 25: ...Dynamic Variable class 9 Read Dynamic Variable with Status 11 Read UID Associated with Tag 12 Read Message 13 Read Tag Descriptor Date 14 Read Transducer Information 15 Read Device Information 16 Read...

Страница 26: ...set Device 44 Write PV Units 45 Trim Loop Zero 46 Trim Loop Gain Fixed Current Mode Fixed current mode is implemented using Command 40 This mode is cleared by power loss or reset Burst Mode This field...

Страница 27: ...193 Read probe Life 195 Enter Access Password 196 Write New Access Password 197 Disable Password 198 Write Alarm Mode 199 Read Alarm Mode 200 Write HART Serial Number 201 Write Serial Number 202 Read...

Страница 28: ...nd Specific Response Code Code Class Description 0 Success No Command Specific Errors 7 Error Write Protection 11 Error Entered Value not Valid Command 191 Read Probe Type This command allows the mast...

Страница 29: ...ific Response Code Code Class Description 0 Success No Command Specific Errors 5 Error Too few Data bytes Received 7 Error Write Protection 11 Error Entered Value not Valid Command 193 Read Probe Life...

Страница 30: ...te Format Description None Unsigned Char 8 As ASCII Password Command Specific Response Code Code Class Description 0 Success No Command Specific Errors 5 Error Too few Data bytes Received 16 Error Acc...

Страница 31: ...e Command 197 Disable Password This command allows the master to reset disable the password entry Request Bytes Byte Format Description 0 Unsigned Char 1 As ASCII Disable Password 0 Password access Le...

Страница 32: ...Format Description 0 Unsigned Char Alarm Mode Command Specific Response Code Code Class Description 0 Success No Command Specific Errors 5 Error Too few Data bytes Received 7 Error Write Protection N...

Страница 33: ...Number First 3 bytes consists of serial number and 4th byte consists of hardware revision level Level 2 password entry is required Request Bytes Byte Format Description 0 3 Unsigned Char HART Serial N...

Страница 34: ...ber Command Specific Response Code Code Class Description 0 Success No Command Specific Errors 5 Error Too few Data bytes Received 7 Error Write Protection Note Default Value Command 202 Read MS Seria...

Страница 35: ...fic Response Code Code Class Description 0 Success No Command Specific Errors 5 Error Too few Data bytes Received 7 Error Write Protection Command 204 Read Commission Date This command allows the mast...

Страница 36: ...password entry is required Request Bytes Byte Format Description Change Parameters to Factory Defaults Response Bytes Byte Format Description Change Parameters to Factory Defaults Command Specific Re...

Страница 37: ...ar as an RS 232 com port to Windows and your HART software A rugged design makes MicroLink an ideal choice for field engineers and technicians who service HART devices in an industrial environment Mic...

Страница 38: ...r to uninstall the driver from your system With the modem connected to the USB port locate the MicroLink modem in the Device Manager hardware tree under Ports COM LPT Right click on MicroLink HART Pro...

Страница 39: ...the window Unplug the MicroLink modem from the USB port and then reconnect it to allow Windows to update the USB device parameters Click OK again to close the Properties window d Software setup Make...

Страница 40: ...36 MicroLink HART modem connected across the HART device MicroLink HART modem connected across the HART device...

Страница 41: ...robe being used Confirm the probe type and refer to Table 2 on page 9 to verify the appropriate switch settings 3 Perform a visual inspection of the circuit boards to look for any signs of mechanical...

Страница 42: ...ntrol B Obtaining Service and Returning the Instrument for Repair If you experience problems with your instrument please contact the factory at 256 358 4202 and ask for customer support for instrument...

Страница 43: ...wn Contact Information for Repair Contact Name Company Phone Number E mail Address Return Shipping Information Recipient Name Company Return Address If different than above Reason for Return Provide a...

Страница 44: ...vision Date Changes 0 10 23 20 Initial Release A 01 14 2021 Comments in French corrected B 09 28 2021 Updated Switch Settings HART Modem and DD file info added C 04 25 2022 Updated HART DD details D 0...

Страница 45: ...41 Appendix B Hazardous Area Certification Details...

Страница 46: ...42...

Страница 47: ...43...

Страница 48: ...44...

Страница 49: ...45...

Страница 50: ...46...

Страница 51: ...47...

Страница 52: ...48 Appendix C Drawings A Wiring Diagrams Control Drawing Hazardous Area Wiring Diagram...

Страница 53: ...01E MS2951E HIGH RESOLUTION ER 4 20mA TRANSMITTER F 2 3 V V J2 J2 S1 2 1 S1 J2 ER Probe Simple Device Sold Separately OR Probe Cable Assembly Sold Separately ER Probe Simple Device Sold Separately CN2...

Отзывы: