mechanical ventilation, activated periodically during fuel filling and slagging of boilers, ensuring a
minimum of 10 full air changes per hour;
●
natural lighting shall be provided in the boiler room, illuminating the boiler from the front, and the
window area shall be a minimum of 1/15 of the boiler room floor area; half of the installed windows
shall be operable; electric lighting and an electric socket, of a voltage not exceeding 24 V, shall also be
provided in the room;
●
there shall be a sump in the floor to allow cooling of the water and its volume shall be equal to the water
capacity of the largest boiler but not more than 2 m
3
;
●
in the boiler room, the thermal pipes should be insulated;
●
The boiler position with the minimum required distances is shown in the boiler room diagram below.
Minimum distances for placing the boiler in the boiler room