pipes  not  resistant  for  high  temperatures.  In  such  cases  it  is 
recommended to set the mixer operation for FLOOR switched on. 

  Floor On 

It  is  being  used  when  the  mixer  circuit  is  loading  floor  heating 
installation.  The  maximum  mixer  circuit  temperature  is  limited  to  the 
value of max. mixer set temperature. 
Attention:  after  choosing  the  option 

–  FLOOR  switched  on  the 

parameter of max. mixer set temperature should be so edited, that the 
floor  heating  will  be  not  damaged  and  there  would  be  no  danger  of 
scalding.  

  Pump only 

By  the  moment  when  the  mixer  circuit  temperature  exceeds  the  set 
temperature in the parameter mixer set temperature, the mixer pump 
supply will be shut down. When the circuit temperature will drop by 2˚C 
then the pump will again be switched on. This option is usually be used 
for  control  of  floor  heating  pump  in  situation,  when  this  pump  is 
operating together with thermostatic valve without actuator.  

Thermostat select* 

Options to choose from: 
Off: (it cuts the influence of room thermostat upon the boiler operation.) 
Universal:  (it  turns  on  the  NO-NC  room  thermostat  coupled  to  42-43 
contacts, it is required to use thermostats with 1K hysteresis.) 
ecoSTER: (this option is available after remote control device ecoSTER 
TOUCH is being connected, thermostat signal is being send from room 
panel.) 

Min. mixer temperature 

It is the parameter used for limitation of choosing too low value of set 
mixer  circuit  temperature  by  the  user.  Automatic  regulation  (e.g. 
periodic  temperature  reduction)  also  does  not  cause  the  reduction  of 
set temperature value below the value given in this parameter. 

Max. mixer temperature 

This parameter has two functions: 
_  it  enables  the  limitation  of  choosing  too  high  value  of  set  mixer 
temperature by the user. Automatic regulation (correction upon heating 
curve,  that  comes  from  outside  temperature)  also  does  not  cause 
crossing the set temperature above the value given for this parameter.  
_ when the

 

Mixer support = On

then the mixer pump will shut down by 

max.  mixer  temperature  +5˚C,  which  protects  the  floor  against 
destruction.  For  the  floor  heating  it should  be  set  for  the  value  below 
45+/-

50 ˚C or even lower, when the thermal resistance of this floor is 

lower. Attention: setting too lower value of this parameter can lead to 
unnecessary shut down of the pump.

  

 

Valve opening time 

The time of valve full opening should be entered 

– this time can be read 

from the nameplate of valve actuator, e.g. 140s. 

Proportionality range 

This parameter affects the movement of the mixer actuator. Increasing 
this  value  results  in  the  mixer  reaching  the  set  temperature  faster. 
Setting this parameter to excessive values causes deregulation of the 
temperature and unnecessary actuator movement. The proper values 
is  set  experimentally.  It  is  recommended  to  set  this  parameter  in  the 
range of 2-6 [3]. 

Constant for integration time 

The  greater  the  value  of  this  parameter,  the  slower  is  the  actuator 
reaction for temperature deviation. Setting too lower values can lead to 
unnecessary  actuator  movements,  too  high  value  extending  the  time 
needed  to  find  set  value  of  the  temperature.  The  right  value  is  being 
edited  according  to  research  results.  It  is  recommended  to  set  this 
parameter value between 100 and 180 [160]. 

Pump Off by thermostat 

Setting  this  parameter  to  “YES”  results  in  closing  the  mixer  and 
deactivating the mixer pump after opening the room thermostat contact 
(the  room  is  warm).  This  setting  is  not  recommended  because  the 
heated room may cool down too much. 

Mixer input dead zone 

This parameter determines the value of temperature insensitivity (dead 
zone) of the mixer control system. The regulator controls the mixer so 
that the measured temperature in the mixer circuit sensor is equal to 
the  set  temperature.  In  order  to  avoid  frequent  actuator  movements 
which  can  wear  it  down  unnecessarily,  the  parameter  should  only  be 
regulated when the measured temperature of the mixer circuit is lower 

Содержание ecoMAX 860P

Страница 1: ...room panel ecoSTER200 and internet module ecoNET300 are not part of standard equipment regulator USER MANUAL AND INSTALLATION ISSUE 1 1 APPLIES TO SOFTWARE MODULE PANEL v 01 XX XX v 01 XX XX 02 2017 e...

Страница 2: ...ed to water PRINCIPLES INDIVIDUAL FUZZY LOGIC The regulator must be programmed individually for the given type of boiler and fuel It is inadmissible to change the type of gear motor fan and to make ot...

Страница 3: ...WEATHER SENSORS CONNECTION 26 12 8 CONNECTING EXHAUST SENSOR 26 12 9 CHECKING TEMPERATURE SENSORS 27 12 10 CONNECTION OF BOILER ROOM THERMOSTAT 27 12 11 CONNECTION OF MIXER S ROOM THERMOSTAT 28 12 12...

Страница 4: ...for boiler manufacturers Before applying the regulator a boiler manufacturer should check if the regulator s mating with the given boiler type is proper and whether it can cause danger The regulator...

Страница 5: ...al is a supplement for the boiler manual In particular except for this manual the boiler manual should also be observed The regulator manual is divided into two parts for user and fitter Yet both part...

Страница 6: ......

Страница 7: ...INSTRUCTION MANUAL ecoMAX 860P...

Страница 8: ...dule Night time decrease boiler On No Yes Reduction value Schedule HUW settings HUW preset temperature HUW pump mode Off Priority No priority HUW container hysteresis HUW disinfection Night time decre...

Страница 9: ...increase from mixer circulation increasing preset temperature for loading buffer warning HUW disinfection mode is active 4 way valve partially closed active return protection 5 fan operation symbol 6...

Страница 10: ...itionally adjusted with individual fuel feeding times and fan speeds affecting the actual output of the boiler The output level parameters are accessible through the menu Boiler Settings Output modula...

Страница 11: ...HUW container parameter Off set HUW priority using the Priority parameter in this case the CH pump is deactivated to speed up filling of the HUW container set simultaneous operation of the CH and HUW...

Страница 12: ...a room thermostat which will equalize the inaccuracy of selecting heating curve if the selected heating curve value is too high In such case it is necessary to set the value of preset mixer temperatu...

Страница 13: ...e selected heating curve value is too high if the outdoor temperature drops and the room temperature drops as well the selected heating curve value is too low if during frosty weather the room tempera...

Страница 14: ...el is burned off In order to change modes turn the regulator off and on by clicking Work mode in the Current information tab 8 19 Manual control Regulator offers possibility to manual start of working...

Страница 15: ...f done properly will set the parameters Feeder efficiency and Tank capacity which can be found in Service Settings Boiler settings 8 21 Information Information menu allows to preview temperatures bein...

Страница 16: ...16...

Страница 17: ...17 INSTALLATION AND SERVICE SETTINGS ecoMAX 860P...

Страница 18: ...re set a high set temperature of the boiler In order to improve the water circulation in natural systems highlighted circuit in the figure use large nominal diameter pipes and four way valve avoid unn...

Страница 19: ...temperature 55 C menu Service settings CH and HUW settings CH pump boiler pump YES menu Service settings CH and HUW settings Mixer 1 support CH activated menu Service settings Mixer 1 control Max pres...

Страница 20: ...ings Buffer settings Loading start temperature 50 C menu Service settings Buffer settings Loading stop temperature 75 C menu Service settings Buffer settings Mixer 1 support CH activated menu Service...

Страница 21: ...he controller in proximity of explosive gases or dust Moreover the controller cannot be used in conditions of water steam condensation or be exposed to effects of water 12 2 Mounting requirements Regu...

Страница 22: ...e terminals and the leads Connection cables should not have contact with surfaces which temperature exceeds cables nominal operating temperature Terminals 1 22 are designed to connect devices supplied...

Страница 23: ...the lead from the connector it is not allowed to coil excess of the cable and to leave not connected leads inside the casing of the regulator 1 cable outlets 2 holdfasts placing should be broken out...

Страница 24: ...pper buffer temp sensor type CT4 BL lower buffer temp sensor type CT4 WS weather temp sensor type CT6 P FT exhaust temp sensor type CTS2 TR universal boiler thermostat NO NC H output to control the si...

Страница 25: ...l sensor used with the BU feeder RM3 mixer 3 room thermostat RM4 mixer 4 room thermostat H2 voltage output for controlling the reserve boiler or alarm signalling or HUW circulation pump RELAY relay L...

Страница 26: ...ensors and hot parts of the boiler and the heating installation Wires of sensors are resistant to temperature not exceeding 100 C 12 7 Weather sensors connection The regulator cooperates solely with t...

Страница 27: ...74 2 CT2S PT1000 exhaust Temp C Min Nom Max 0 999 7 1000 0 1000 3 25 1096 9 1097 3 1097 7 50 1193 4 1194 0 1194 6 100 1384 2 1385 0 1385 8 125 1478 5 1479 4 1480 3 150 1572 0 1573 1 1574 2 12 10 Conne...

Страница 28: ...serve boiler gas or oil eliminating the necessity of enabling or disabling this boiler manually The reserve boiler will be enabled if the temperature of the pellet boiler drops and disabled when the p...

Страница 29: ...iler circuit pipes Use pipes of large cross section for gravitational boiler circuit Electric diagram for switching valve of the reserve boiler where 1 regulator 2 reserve boiler 3 4 relay RM 84 2012...

Страница 30: ...umentation of valve manufacturer and check whether the valve is properly connected calibrate factor of mixer valve opening To do this disconnect power supply of the regulator and set the selector on h...

Страница 31: ...two wire connection power supply of 12V DC and rated current of min 200mA is required Disconnect GND and 12V wires from the module 2 and re connect them to external power supply unit arranged near eco...

Страница 32: ...there should be written new software in the pfc format as a 2 files a file with the panel software and a file with the module A software Software files should be placed directly on the memory card do...

Страница 33: ...nly water and exhaust Exhaust temperature fan reduction Return protection 4 way return protection Return hysteresis Min return temperature Valve closing Min boiler temperature Max boiler temperature B...

Страница 34: ...parameter is hidden Manufacturer menu Reset counters Reset alarms Exhaust alarm temperature Flame return feed time Flame return detection delay Flame return alarm feed time Hall sensor control Min RP...

Страница 35: ...ERATION cycle time OPERATION feed time feeder standstill time Feeder efficiency Efficiency of the fuel feeder in kg h Entered a measured amount of fuel in constant feed feeder working constantly The p...

Страница 36: ...These times may be edited in a special menu accessible only to the manufacturer of the boiler 14 2 BOILER Boiler settings Grate Max ignition time When this time is exceeded ant the exhaust temperatur...

Страница 37: ...the status of the thermostat are sent from the room panel Pump Off by thermostat Available options No the CH boiler pump is not switched off when the room thermostat is activated YES the CH boiler pu...

Страница 38: ...nsion time value Circulation pump standstill time It is the time between periods of circulation pump operation and it is defined by the parameter circulation standstill time recommended setting is bet...

Страница 39: ...sing the set temperature above the value given for this parameter _ when the Mixer support On then the mixer pump will shut down by max mixer temperature 5 C which protects the floor against destructi...

Страница 40: ...SETUP Show advanced setup Available options YES shows hidden parameters which edition is not recommended NO hides hidden parameters 14 7 RESTORE DEFAULT SETTINGS Restore default settings Restoring th...

Страница 41: ...function of protection against flame recession is inoperative if the feeder sensor is disconnected or damaged The function of protection against flame recession is inoperative if the regulator is not...

Страница 42: ...the encoder TOUCH and PLAY knob or restarting the power supply 15 9 Boiler overheating STB open contact This alarm occurs after activation of independent safety thermostat that secures the boiler agai...

Страница 43: ...d by scale deposit To do this these components are periodically every 167h switched on for few seconds In this way the pumps are protected from immobilization caused by scale deposits Therefore during...

Страница 44: ...44...

Страница 45: ......

Страница 46: ......

Страница 47: ......

Страница 48: ...Jacek Kucharewicz ul Sikorskiego 66 16 100 Sok ka Poland tel 48 85 711 94 54 www metalfachtg com pl...

Отзывы: