Metal-Fach ecoMAX 860P Скачать руководство пользователя страница 22

22 

 

 

In case of using the version with STB 
device  before  making  the  montage 
and 

wiring 

it 

is 

strongly 

recommended  to  take  out  the  STB 
capillary  from  inside  the  clamp  box 
using cable opening as described on 
the picture below.  
Attention!  This  capillary  cannot 
be  smashed  or  bend  with  acute 
angle.
 

 

1-   Cable  opening  2  –  The  STB  capillary  cable, 
which was being correctly taken out from the clamp 
box. 

12.4

 

IP protection rate 

The  regulator  casing  provides  the  IP20 
protection  rating.  The  casing  on  the 
connectors  cover  side  provides  IP00  rating, 
and  because  of  that  connectors  must  be 
unconditionally covered with the cover. 
If  there  is  a  need  to  gain  an  access  to  the 
terminals side, it is a must to disconnect the 
mains  voltage  and  make  sure  there  is  no 
dangerous voltage on regulator terminals. 

12.5

 

Electric connection 

The  regulator  is  designed  to  be  fed  with 
230V~,  50Hz  voltage.  The  electrical  system 
should be: 

 

three core (with protective wire PE), 

 

in accordance with applicable regulations. 

 

Caution:  After  the  regulator  is 
turned  off  using  the  keyboard, 
dangerous voltage can occur on the 
terminals.  Before  starting  any 
assembly 

works, 

you 

must 

disconnect  the  mains  supply  and 
make  sure  that  there  is  no 
dangerous voltage on the terminals 
and the leads.  

Connection  cables  should  not  have  contact 
with  surfaces  which  temperature  exceeds 
cables  nominal  operating  temperature. 
Terminals  1-22  are  designed  to  connect 
devices supplied by the mains 230V~ voltage. 
Terminals  25–48  are  designed  to  work  with 
low-voltage devices (<12V). 

 

Connection  of  the  230V~  mains 
voltage  to  terminals  25-48  or  to 
transmission  terminals  G2,  G3,  B 
and  USB  results  in  the  regulator 
damage  and  poses  a  threat  of 
electrocution. 

Tips  of  connection  cables,  especially  mains 
voltage  cables  should  be  secured  from 
splitting  by  e.  g.  insulated  clamp  sleeves  in 
accordance  with  the  picture  below:  a  – 
properly secured, b – improperly secured.  

 

 

Unconditionally check if any lead of 
the  insulated  cable,  or  the  cable 
itself  DO  NOT  have  electrical 
connection 

with 

the 

metal 

grounding  strip  (which  is  placed 
near to high voltage terminals of the 
regulator). 

The feeder cable should be connected to the 
terminals marked with an arrow. 

 

All  peripherals  (such  like:  pumps, 
RE-marked  relays  and  connected 
recipients)  may  be  connected  only 
by  qualified  person  in  accordance 
with  applicable  regulations.  Safety 
precautions to prevent electrocution 
shall be observed.  
Regulator  shall  be  equipped  with  a 
set  of  pins  connected  to  230V  AC 
mains. 

Protection lead of the power supply cable and 
protection leads of connected devices should 
be  connected  to  the  grounding  strip  placed 

Insulated clamp sleeve, 6mm lenght. 

Содержание ecoMAX 860P

Страница 1: ...room panel ecoSTER200 and internet module ecoNET300 are not part of standard equipment regulator USER MANUAL AND INSTALLATION ISSUE 1 1 APPLIES TO SOFTWARE MODULE PANEL v 01 XX XX v 01 XX XX 02 2017 e...

Страница 2: ...ed to water PRINCIPLES INDIVIDUAL FUZZY LOGIC The regulator must be programmed individually for the given type of boiler and fuel It is inadmissible to change the type of gear motor fan and to make ot...

Страница 3: ...WEATHER SENSORS CONNECTION 26 12 8 CONNECTING EXHAUST SENSOR 26 12 9 CHECKING TEMPERATURE SENSORS 27 12 10 CONNECTION OF BOILER ROOM THERMOSTAT 27 12 11 CONNECTION OF MIXER S ROOM THERMOSTAT 28 12 12...

Страница 4: ...for boiler manufacturers Before applying the regulator a boiler manufacturer should check if the regulator s mating with the given boiler type is proper and whether it can cause danger The regulator...

Страница 5: ...al is a supplement for the boiler manual In particular except for this manual the boiler manual should also be observed The regulator manual is divided into two parts for user and fitter Yet both part...

Страница 6: ......

Страница 7: ...INSTRUCTION MANUAL ecoMAX 860P...

Страница 8: ...dule Night time decrease boiler On No Yes Reduction value Schedule HUW settings HUW preset temperature HUW pump mode Off Priority No priority HUW container hysteresis HUW disinfection Night time decre...

Страница 9: ...increase from mixer circulation increasing preset temperature for loading buffer warning HUW disinfection mode is active 4 way valve partially closed active return protection 5 fan operation symbol 6...

Страница 10: ...itionally adjusted with individual fuel feeding times and fan speeds affecting the actual output of the boiler The output level parameters are accessible through the menu Boiler Settings Output modula...

Страница 11: ...HUW container parameter Off set HUW priority using the Priority parameter in this case the CH pump is deactivated to speed up filling of the HUW container set simultaneous operation of the CH and HUW...

Страница 12: ...a room thermostat which will equalize the inaccuracy of selecting heating curve if the selected heating curve value is too high In such case it is necessary to set the value of preset mixer temperatu...

Страница 13: ...e selected heating curve value is too high if the outdoor temperature drops and the room temperature drops as well the selected heating curve value is too low if during frosty weather the room tempera...

Страница 14: ...el is burned off In order to change modes turn the regulator off and on by clicking Work mode in the Current information tab 8 19 Manual control Regulator offers possibility to manual start of working...

Страница 15: ...f done properly will set the parameters Feeder efficiency and Tank capacity which can be found in Service Settings Boiler settings 8 21 Information Information menu allows to preview temperatures bein...

Страница 16: ...16...

Страница 17: ...17 INSTALLATION AND SERVICE SETTINGS ecoMAX 860P...

Страница 18: ...re set a high set temperature of the boiler In order to improve the water circulation in natural systems highlighted circuit in the figure use large nominal diameter pipes and four way valve avoid unn...

Страница 19: ...temperature 55 C menu Service settings CH and HUW settings CH pump boiler pump YES menu Service settings CH and HUW settings Mixer 1 support CH activated menu Service settings Mixer 1 control Max pres...

Страница 20: ...ings Buffer settings Loading start temperature 50 C menu Service settings Buffer settings Loading stop temperature 75 C menu Service settings Buffer settings Mixer 1 support CH activated menu Service...

Страница 21: ...he controller in proximity of explosive gases or dust Moreover the controller cannot be used in conditions of water steam condensation or be exposed to effects of water 12 2 Mounting requirements Regu...

Страница 22: ...e terminals and the leads Connection cables should not have contact with surfaces which temperature exceeds cables nominal operating temperature Terminals 1 22 are designed to connect devices supplied...

Страница 23: ...the lead from the connector it is not allowed to coil excess of the cable and to leave not connected leads inside the casing of the regulator 1 cable outlets 2 holdfasts placing should be broken out...

Страница 24: ...pper buffer temp sensor type CT4 BL lower buffer temp sensor type CT4 WS weather temp sensor type CT6 P FT exhaust temp sensor type CTS2 TR universal boiler thermostat NO NC H output to control the si...

Страница 25: ...l sensor used with the BU feeder RM3 mixer 3 room thermostat RM4 mixer 4 room thermostat H2 voltage output for controlling the reserve boiler or alarm signalling or HUW circulation pump RELAY relay L...

Страница 26: ...ensors and hot parts of the boiler and the heating installation Wires of sensors are resistant to temperature not exceeding 100 C 12 7 Weather sensors connection The regulator cooperates solely with t...

Страница 27: ...74 2 CT2S PT1000 exhaust Temp C Min Nom Max 0 999 7 1000 0 1000 3 25 1096 9 1097 3 1097 7 50 1193 4 1194 0 1194 6 100 1384 2 1385 0 1385 8 125 1478 5 1479 4 1480 3 150 1572 0 1573 1 1574 2 12 10 Conne...

Страница 28: ...serve boiler gas or oil eliminating the necessity of enabling or disabling this boiler manually The reserve boiler will be enabled if the temperature of the pellet boiler drops and disabled when the p...

Страница 29: ...iler circuit pipes Use pipes of large cross section for gravitational boiler circuit Electric diagram for switching valve of the reserve boiler where 1 regulator 2 reserve boiler 3 4 relay RM 84 2012...

Страница 30: ...umentation of valve manufacturer and check whether the valve is properly connected calibrate factor of mixer valve opening To do this disconnect power supply of the regulator and set the selector on h...

Страница 31: ...two wire connection power supply of 12V DC and rated current of min 200mA is required Disconnect GND and 12V wires from the module 2 and re connect them to external power supply unit arranged near eco...

Страница 32: ...there should be written new software in the pfc format as a 2 files a file with the panel software and a file with the module A software Software files should be placed directly on the memory card do...

Страница 33: ...nly water and exhaust Exhaust temperature fan reduction Return protection 4 way return protection Return hysteresis Min return temperature Valve closing Min boiler temperature Max boiler temperature B...

Страница 34: ...parameter is hidden Manufacturer menu Reset counters Reset alarms Exhaust alarm temperature Flame return feed time Flame return detection delay Flame return alarm feed time Hall sensor control Min RP...

Страница 35: ...ERATION cycle time OPERATION feed time feeder standstill time Feeder efficiency Efficiency of the fuel feeder in kg h Entered a measured amount of fuel in constant feed feeder working constantly The p...

Страница 36: ...These times may be edited in a special menu accessible only to the manufacturer of the boiler 14 2 BOILER Boiler settings Grate Max ignition time When this time is exceeded ant the exhaust temperatur...

Страница 37: ...the status of the thermostat are sent from the room panel Pump Off by thermostat Available options No the CH boiler pump is not switched off when the room thermostat is activated YES the CH boiler pu...

Страница 38: ...nsion time value Circulation pump standstill time It is the time between periods of circulation pump operation and it is defined by the parameter circulation standstill time recommended setting is bet...

Страница 39: ...sing the set temperature above the value given for this parameter _ when the Mixer support On then the mixer pump will shut down by max mixer temperature 5 C which protects the floor against destructi...

Страница 40: ...SETUP Show advanced setup Available options YES shows hidden parameters which edition is not recommended NO hides hidden parameters 14 7 RESTORE DEFAULT SETTINGS Restore default settings Restoring th...

Страница 41: ...function of protection against flame recession is inoperative if the feeder sensor is disconnected or damaged The function of protection against flame recession is inoperative if the regulator is not...

Страница 42: ...the encoder TOUCH and PLAY knob or restarting the power supply 15 9 Boiler overheating STB open contact This alarm occurs after activation of independent safety thermostat that secures the boiler agai...

Страница 43: ...d by scale deposit To do this these components are periodically every 167h switched on for few seconds In this way the pumps are protected from immobilization caused by scale deposits Therefore during...

Страница 44: ...44...

Страница 45: ......

Страница 46: ......

Страница 47: ......

Страница 48: ...Jacek Kucharewicz ul Sikorskiego 66 16 100 Sok ka Poland tel 48 85 711 94 54 www metalfachtg com pl...

Отзывы: