Mestek TUBULAR GAS FIRED DIRECT SPARK PROPELLER UNIT HEATERS Скачать руководство пользователя страница 9

9

INSTALLATION (continued) - PIPE INSTALLATION

Figure 4 - Pipe Installation, Standard Controls

 Never use an open fl ame to detect 

gas leaks. Explosive conditions may exist which 
may result in personal injury or death!

The appliance and its individual shutoff valve must be 
disconnected from the gas supply piping system during 
any pressure testing of that system in excess of 1/2 psig 
(3.5 kPa).

The appliance must be isolated from the gas supply 
piping system by closing its individual manual shutoff 
valve during any pressure testing of the gas supply 
piping system at test pressures equal to or less than 
1/2 psig (3.5 kPa).

Table 4 - Gas Piping Requirements

SINGLE STAGE GAS PIPING REQUIREMENTS*

GasType  

 

Natural Gas  

Propane (LP) Gas

Manifold 

 

3.5 inch WC 

10.0 inch WC

Pressure 

 

(0.9 kPa) 

(2.5 kPa)

 

 

14.0 inch WC Max. 

14.0 inch WC Max.

Supply Inlet   

(3.5 kPa) 

(3.5 kPa)

Pressure

 

 

5.0 inch WC Min. 

11.0 inch WC Min.

 

(1.2 kPa) 

(2.7 kPa)

*For single stage application only at normal altitudes.

   

1.  Install the gas piping in accordance with applicable 

local codes.

2.  Check gas supply pressure. Each unit heater must 

be connected to a manifold pressure and a gas 
supply capable of supplying its full rated capacity as 
specifi ed in Table 4. A fi eld LP tank regulator must be 
used to limit the supply pressure to a maximum of 14 
inches W.C. (3.5 kPa). All piping should be sized in 
accordance with the latest edition of ANSI Standard 
Z223.1 (NFPA 54), National Fuel Gas Code; in 
Canada, according to CSA B149. See Tables 1 & 3 
for correct gas piping size. If gas pressure is 
excessive on natural gas applications, install a 
pressure regulating valve in the line upstream from 
the main shutoff valve.

3.  Adequately support the piping to prevent strain on 

the gas manifold and controls.

4.  To prevent the mixing of moisture with gas, run the 

take-off piping from the top, or side, of the main.

5.  Standard Unit Heaters, optional two-stage units are 

supplied with a combination valve which includes:

 

a. Manual "A" valve

 

b. Manual "B" valve

 

c. Solenoid valve

 

d. Pressure regulator

 

Pipe directly into the combination valve (see Figure 
4).

6.  Gas valve has a pressure test post requiring a 

3/32 inch hex head wrench to read gas supply and 
manifold pressures. Open 1/4 turn counterclockwise 
to read, turn clockwise to close and reseat. A 5/16 
inch ID hose fi ts the pressure post.

7.  Provide a drip leg in the gas piping near the gas 

unit heater. A ground joint union and a manual gas 
shutoff valve should be installed ahead of the unit 
heater controls to permit servicing. The manual 
shutoff valve must be located external to the jacket 
(See  Figure 4).

8.  Make cer tain that all connections have been 

adequately doped and tightened.

 Do not over tighten the inlet gas 

piping into the valve. This may cause stresses that 
will crack the valve!

NOTICE: Use pipe joint sealant resistant to the 
action of liquefied petroleum gases regardless of 
gas conducted.

 Check all pipe joints for leakage 

using a soap solution or other approved method.  
Never use an open flame or severe personal 
injury or death may occur!

D3631C

Содержание TUBULAR GAS FIRED DIRECT SPARK PROPELLER UNIT HEATERS

Страница 1: ...t any problem that may be found RECEIVING INSTRUCTIONS Inspect shipment immediately when received to determine if any damage has occurred to the unit during shipment After the unit has been uncrated c...

Страница 2: ...on Air 5 7 Proper Clearances 5 7 Suspension of Units 5 7 Heat Throw Data 6 Gas Piping 8 9 ELECTRICAL CONNECTIONS 10 11 12 VENTING 13 14 15 16 17 OPERATION Explanation of Controls and Operation 18 Main...

Страница 3: ...t Start Up Sheet located in this manual Use only the fuel for which the heater is designed see rating plate Using LP gas in a heater that requires natural gas or vice versa will create risk of gas lea...

Страница 4: ...9 279 311 311 311 E Hanging Distance Width 18 5 8 18 5 8 18 5 8 30 5 8 30 5 8 30 5 8 48 5 8 48 5 8 48 5 8 473 473 473 778 778 778 1235 1235 1235 F Discharge Opening Width 18 3 4 18 3 4 18 3 4 30 3 4 3...

Страница 5: ...ve the floor must be equipped with an OSHA approved fan guard Refer to the latest edition of NFPA 88A Parking structures In Canada installation must be in accordance to the latest edition of CSA B149...

Страница 6: ...NR NR 44 47 58 66 71 75 6 1 13 4 14 3 17 7 20 1 21 6 22 9 60 8 75 80 85 90 95 110 125 130 138 2 4 22 9 24 4 25 9 27 4 29 0 33 5 38 1 39 6 42 1 10 65 70 75 79 83 95 109 115 120 3 0 19 8 21 3 22 9 24 1...

Страница 7: ...ere is a possibility of distortion or discoloration of adjacent materials Make certain that the lifting methods used to lift the heater and the method of suspension used in the field installation of t...

Страница 8: ...vity Gas Nominal Iron Internal Length of Pipe Feet meters Pipe Size Diameter 10 20 30 40 50 60 70 80 90 100 125 150 175 200 Inch Inch 3 0 6 1 9 1 12 2 15 2 18 3 21 3 24 4 27 4 30 5 38 1 45 7 53 3 61 0...

Страница 9: ...al Fuel Gas Code in Canada according to CSA B149 See Tables 1 3 for correct gas piping size If gas pressure is excessive on natural gas applications install a pressure regulating valve in the line ups...

Страница 10: ...tical vibration free surface free from air currents and in accordance with the furnished instructions Mount the thermostat approximately 5 feet 1 5m above the floor in an area where it will be exposed...

Страница 11: ...11 ELECTRICAL CONNECTIONS continued Figure 5d Tubular Units Equipped with Natural Gas and Propane LP Gas...

Страница 12: ...12 ELECTRICAL CONNECTIONS continued Figure 5e Tubular Unit Sizes with Optional 2 Stage Ignition...

Страница 13: ...operating the gas unit heater will result in the spillage of flue gas into the occupied space 9 Avoid installing units in areas under negative pressure due to large exhaust fans or air conditioning W...

Страница 14: ...isance or hazard or could be detrimental to the operation of regulators relief valves or other equipment The vent pipe equivalent length must not exceed 50 feet 15 2m Equivalent length is the total le...

Страница 15: ...r in the absence of local codes with current CSA B149 1 Installation Codes for Natural Gas Burning Appliances and Equipment or CSA B149 2 Installation Codes for Propane Gas Burning Appliances and Equi...

Страница 16: ...16 Figure 8A Figure 8B VENTING continued D3620F D3619C...

Страница 17: ...17 VENTING continued Figure 9A Figure 9B D3661F D3662D...

Страница 18: ...motor is de energized 6 The fan operation is delayed 30 seconds once the thermostat is closed and continues operation for 30 seconds after the thermostat opens NOTICE The start up fan delay must not e...

Страница 19: ...eaters must be field derated to 90 of the normal altitude rating and be so marked in accordance with ETL certification See Table 6A for field deration information Check the gas input rate as follows R...

Страница 20: ...Refer to Installation Instruction section on Adjustments Gas Input Rate for adjusting the manifold pressure Manifold Pressure Inc WC PROPANE LP GAS NATURAL GAS Heating Value BTU Hr Altitude Feet 8 6...

Страница 21: ...t openings 3 Clean heat exchanger Refer to Installation 4 Determine cause and repair accordingly 1 Inspect all gas piping and repair 2 Check to ensure gas test ports are seated 3 Clean heat exchanger...

Страница 22: ...tat 1 Replace or tighten 2 Clean power ventor wheel 3 Realign power ventor wheel 1 Check and tighten wires on fan circuit 2 Test for 115v on terminal ACB Heat and L2 if voltage is present replace moto...

Страница 23: ...heat If not present and all checks are normal replace 1 Check power ventor circuit per wiring diagram 2 Check motor voltage and amp draw to motor name plate replace if motor found defective 3 Check f...

Страница 24: ...er 3 5 Amp fuse on circuit board 1 Common side of transformer grounded to chassis 2 Loose spark ignitor 1 Gas supply off or gas supply pressure too low 2 Flame sense rod contaminated or loose wire 3 G...

Страница 25: ...supplied with your unit NOTICE The heater and vent system should be checked once a year by a qualified technician All Maintenance Service information should be recorded accordingly on the Inspection...

Страница 26: ...ing halogenated hydrocarbons precipitated in the air d to any workmanship of the installer of the Product 3 This limited warranty is conditional upon a advising the installing contractor who in turn n...

Страница 27: ...ICATION OF PARTS PROPELLER UNIT HEATERS Figure 13 Heat Exchanger Assembly Figure 14 Electrical Control Panel Figure 11 Propeller Parts Figure 12 Component Parts D4430 Fan Guard Fan Blade Hardware Hard...

Страница 28: ...Venter Assembly 300 400 Unit Sizes Shown HOW TO ORDER REPLACEMENT PARTS Please send the following information to your local representative if further assistance is needed contact the manufacturer s cu...

Страница 29: ...29 NOTES...

Страница 30: ...30 NOTES...

Страница 31: ...11 Supply Voltage SV 1 115 1 60 5 230 3 60 2 208 1 60 6 460 3 60 3 230 1 60 7 575 3 60 4 208 3 60 Z Other Note Supply Voltage SV 2 7 include field mounted step down transformer 12 Motor Type MT 1 Ope...

Страница 32: ...s equipment unless you fully understand the controls GAS EQUIPMENT START UP GENERAL With power and gas off Make certain all packing has been removed Tighten all electrical terminals and connections Ch...

Отзывы: