![Mestek HWL2-1116 Скачать руководство пользователя страница 48](http://html1.mh-extra.com/html/mestek/hwl2-1116/hwl2-1116_installation-operation-and-maintenance-manual_1775638048.webp)
Page 47 of 57
SK2016 HW-V-AECM-001
F.3.
Onboard configuration
There is 1 DIP switch set on the PCB:
DIPB (4 positions)
SW1: configured for different modulating signal
SW2 – SW4: brushless DC fan motor configuration.
Code
State
Description
SW1
0
PCB configured for 0~5VDC modulating signal input.
1
PCB configured for 0~10VDC modulating signal input.
MODEL
SW2
SW3
SW4
Hi
Med
Low
HW-04
0
0
0
700
600
500
HW-06
0
0
1
900
700
600
HW-12
0
1
0
950
700
600
HW-15
0
1
1
1100
800
700
HW-18
1
0
0
1300
1100
900
HW-20
1
0
1
1100
900
800
HW-24
1
1
0
1200
1100
900
HW-30
1
1
1
1350
1200
900
Default RPM
1
1
1
Set by customer requirement