8  Faultfinding and remedy

Fault

Cause

Remedy

The motor will not start

supply voltage missing

check all fuses are good and supply voltage are
present

there is no current

drive not enable

Terminal X1/Pin5 should be connected to 0VDC
(op24V) for power stage enable

Motor wiring open

check the wiring for the armature circuit

The motor runs at an uncontrollably high
speed after switching on.

The control circuit is polarised

Change the polarity of the tachometer or the
motor.

The motor will not start although current
is present

The motor is blocked (mechanically)

Shorted motor circuit

Release the brake, if there is one; if necessary
dismantle the motor and run no-load test.
Check the wiring of the armature circuit

The motor runs unevenly

P-portion too high
I-portion too small

Turn P2 counter clockwise
Increase C8

Wiring fault at control leads or tachometer
leads

Check the shielding and check wiring

After enable the amplifier

Choke are not wired in the armature

check wiring

the red fault LED is lit

choke and/or motor inductance too low

the value must amount to, at least, the value for
the corresponding amplifier

short circuit in the motor, wiring or chokes

check wiring, motor and chokes

After turn on amplifier the red LED is lit
without enable amplifier

power stage is defective

exchange amplifier

the red LED is on after a long running
time

power stage overheat

let the module cool down

Red LED goes on when the motor is
decelerating

over voltage caused by high system inertia A braking regulator board needs to be added to

insure proper amplifier use

Red LED goes on immediately after
power up

Over voltage caused by high bus voltage

check transformer and net

9  Commissioning and terminal description

9.1  Front connector X 1

PIN

Signal direction Function

Remark

1
2

-  IN
+ IN

Set value

differential , Ri = 20 K

 , max. input voltage

20 V ,max. input Voltage to GND +/- 30 V

3
4

+ IN
-  IN

Tacho input

differential, Ri = 54 K

 , max. input voltage

65 V , max. input voltage to GND +/- 70 V
Att. BEMF control for output voltage higher then 60V

5

IN

Enable

negative Logic: open Drive disable
                         0V (GND) Drive enable
Attention! do not connect to source
positive Logic:  open or 0V(GND) Drive disable
                         + 24 V   Drive enable

6
7

OUT
OUT

drive healthy
signal

relay contact
closed if Drive OK

8

OUT

(IN)

+ 15 V
(Limit switch)

Auxiliary Voltage  max. load with 20 mA,  not available if using OPT E
input for OPT E Limit switch Logic level set by factory

9

0V

E

 (GND)

Electronic ground

10

OUT

(IN)

- 15 V
(Limit switch)

see PIN 8

11
12

+ OUT
-  OUT

Motor   A1
Motor   A2

notice diameter , never short to ground or A2 or power input

ATTENTION  !

Apply no  Voltage

13
14

IN
IN

+ Ucc
- Ucc/

Содержание MQC 0506

Страница 1: ...PWM SERVO CONTROLLERS SERIES MQC Operating Manual Issue September 05...

Страница 2: ...fier corresponds to or is properly rated in terms of rated voltage and current for the type of motor which is to be driven The descriptive label affixed to the amplifier specifies electrical ratings S...

Страница 3: ...FUNCTION IARMS 7 5 6 BEMF FEEDBACK SPEED CONTROL WITH I X R COMPENSATION 7 5 7 VARIABLE COMPONENTS 8 5 8 SPEED CONTROLLER COMPONENTS BLOCK DIAGRAM 8 5 9 CURRENT CONTROL 9 6 PROTECTION AND FAULT SIGNAL...

Страница 4: ...network PI D correction with potentiometer or components Speed control range 1 20000 static Error 30 3000 rpm 0 1 1 30 rpm 2 0 1 rpm 5 0 Current controller Band width 1 kHz Compensation network Pl Cur...

Страница 5: ...tion of brush DC motors The MQC is equipped with an internal power supply From dc voltage the amplifier is producing the current for the motor Output current is PWM controlled and due to high chopper...

Страница 6: ...MESA Automation GmbH MQC 05 V 3 EM 4 3 Block diagram...

Страница 7: ...e isolated and NOT connected to earth A three phase transformer is recommended for current higher than 10 A continuos overall The factory or your dealer should be consulted to specify the proper size...

Страница 8: ...Personality card must be checked P Gain P2 Standard range Right side 160 Left side 8 adjustment of the standard range with R21 A Response when correctly adjusted Demand Signal t1 t3 acceleration IDC I...

Страница 9: ...ture current control point via a threshold value switch The I rms Current is adjusted with P5 and is maintained irrespective of the curve shape of the armature current actual value I IAmax t1 accelera...

Страница 10: ...k IxR compensation R12 Standard not used 5 8 Speed controller components Block diagram lntegral part C2 Standard C2 0 1 F Proportional part P2 R 21 Standard R21 82 k TN R21 x C2 KNS R21 R111 x K comma...

Страница 11: ...that the amplifier Rack or stand alone is properly earthed If the amplifier is not earthed then if an earth fault occurs in the motor circuit the output of the amplifier will be destroyed Each motor...

Страница 12: ...or and chokes After turn on amplifier the red LED is lit without enable amplifier power stage is defective exchange amplifier the red LED is on after a long running time power stage overheat let the m...

Страница 13: ...0 Enable CMOS level 15 V 21 Error over voltage 0 Error 22 Error over current 1 OK 23 Error over temperature 24 Error input from Option subprint Attention All test points refer to 0VE GND power and log...

Страница 14: ...m calculate before the max power 9 6 Additional Dates Type Fuse F2 A internal choke mH Lmin FAN Size mm Min distance mm Wight Kg RV in K 0 25 W 1 R211 212 MQC 0506 6 3 1 1 50 80 30 1 3 MQC 0510 10 0 5...

Страница 15: ...MESA Automation GmbH MQC 05 V 3 EM 13 10 Drawings 10 1 Amplifier input 10 2 DC Power supply Attention Do not ground the secondary winding MQC 05 XX L1 L2 L2 DC Input...

Страница 16: ...MESA Automation GmbH MQC 05 V 3 EM 14 10 3 Components location...

Страница 17: ...MESA Automation GmbH MQC 05 V 3 EM 15 10 4 Mechanical style...

Страница 18: ...MESA Automation GmbH MQC 05 V 3 EM 16 The manual is subject to modifications or misprint Please call our service for further technical questions...

Страница 19: ...MESA Automation GmbH MQC 05 V 3 EM 17...

Страница 20: ...utomation GmbH MQC 05 V 3 EM 18 Mesa Automation GmbH Member of Infranor group 12045 Berlin Maybachufer 48 51 Tel 49 0 30 6139080 Telefax 49 0 30 6231766 http www mesa berlin de Email service mesa berl...

Отзывы: