Installation proposal:
1. Connect the Easy shutter actuator
REG-K/4x(1x230)/6 as shown in the
connection example and mount on the
DIN rail EN 50022 from below.
2. Push the Easy shutter actuator REG-K/
4x(1x230)/6 up (push springs toge-
ther) and lower it onto the DIN rail.
Note
A data rail is not required.
Bus line:
In order to avoid loops (over-voltage), the
bus line should be laid without a gap to the
power line. The minimum gap between the
insulated wire of the bus line and the insu-
lated wire of the power line is 4 mm.
Fig. H:
Note
Further information on laying the bus
line can be found in the ”base unit”
operating instructions and in the ZVEI/
ZVEH ”Building management system,
Basic principles” handbook.
Anleitung_777204.book Seite 19 Montag, 14. Oktober 2002 7:37 19
20
After wiring the actuator:
1
Switch on bus voltage
- Green operation indicator comes on
- All relays are switched off
2
Switch on voltage for motors
The bus voltage is switched on.
Automatic recognition:
Choose the menu option ”New function” or
”Edit function” in the Easy base unit.
The device is automatically recognised by
the base unit and displayed in the channel
list with the allocated device number.
Manual recognition:
If the device is no longer in the delivery sta-
tus, you should press the programming key
briefly
(< 2 seconds) for recognition. The
red LED lights up during the recognition
process.
The device is recognised by the base unit
and displayed in the channel list with the
allocated device number.
Start-up with shutter actuator
Start-up with the Easy base unit
Anleitung_777204.book Seite 20 Montag, 14. Oktober 2002 7:37 19
21
Start-up:
If the device has been recognised, the 4
channels of the device appear in the chan-
nel overview of the Easy base unit.
Press the relevant channel key on the de-
vice in order to connect (select) the chosen
shutter channel. The relay output switches
in the position up and down. For stopping
the drive press the channel key again. The
channel of the device is marked in the
channel overview.
Further information can be found in the
operating instructions for the Easy base
unit or in the relevant documents for other
external EIB Easy setting devices.
Behaviour when bus voltage is esta-
blished/returns
The drives are switched off.
Behaviour when bus voltage fails
No reaction.