SR10k    Doc. 10107-0007   

Rev 1.08  

  Page 

16

          

DIODE 1N4001 (50V/1A) TYPICAL

Installation

Find a suitable location to anchor the reader mounting bracket. The mounting of the reader does not 
require a junction box. However, rigid conduit is required for outdoor application. A single gang junc-
tion box may used to provide transition to rigid conduit.  If a single gang junction box is used, a wall 
plate (optional) may be used to cover the junction box. The reader is then secured to the mounting 
bracket using a screw. Refer to fi gures for reader dimensions and typical junction box usage.
Connect door hardware/power according to the confi guration selected. Wires of 22AWG or larger 

are recommended for fi eld wiring. See local electrical code.

 

DIODE SELECTION:

DIODE CURRENT RATING > 1X STRIKE CURRENT
DIODE BREAK DOWN VOLTAGE : 4X STRIKE VOLTAGE

Coat reader connector with the silicone grease supplied to seal off moisture for outdoor mounting.
To avoid  having ESD (electrostatic discharge) interfering with the operation of the reader, the reader 
casing shall be grounded. This can be accomplished be tying the mounting bracket to earth ground 
locally (e.g. grounded conduit).

Reader DIP switch setting:   
S1:  

 4      3      2       1 

Factory Preset

 

 

OFF OFF OFF  ON

S3:  

ON   ON   ON   ON 

Factory Preset

Relay Contact Protection/Noise Suppression

Load switching can cause contact transfer, welding, and abnormal wear, which can cause premature 
contact failure.  The switching of an inductive load (strike) can also cause EMI (electromagnetic 
interference).  To prolong contact life and increase total system reliability, contact protection circuit 
must be used. The following two circuits are recommended.  For DC application, use a diode circuit; 
for AC application, use a MOV 

(metal oxide varistor)

 

circuit.  Locate the protection circuit as close 

to the load as possible, as the effectiveness of the circuit will decrease if it is located to far away.  
As a guideline, the distance should be within 12 inches (30 cm).  Mag Locks may have internal 
noise suppression, please refer to the manufactures documentation.  Mag Locks should be wired 

to Output K1 normally closed (NC) terminal.

Содержание SR10k

Страница 1: ...Mercury Security 2013 SR10k Doc 10107 0007 Rev 1 08 Page 1 SR10k Mag Stripe Access System Users Guide www mercury security com 2355 MIRA MAR AVE LONG BEACH CA 90815 1755 562 986 9105 FAX 562 986 9205...

Страница 2: ...ed Restricted Access 14 Mode 6 Two Door Access Control 14 Mode 7 Access Control with Door Bell Feature 15 Mode 8 Dual Output Toggle on Valid Access 15 Installation 16 Maintenance 17 Specifications 17...

Страница 3: ...s mode allows the use of any magnetic stripe card with standard track 2 encod ing such as the MS SR10CC25 pre encoded packs of 25 cards or cards from many other access systems or even bank cards Store...

Страница 4: ...ection of these functions intended for a specific application The Operating Modes are described in detail later in this document Changing the Operating Mode resets the door strike held open and auxili...

Страница 5: ...nes the installation wiring details and User Level assignment Lost Master Card Follow the steps outlined below to set a new Master Card in case the current Master Card is lost remove power from the SR...

Страница 6: ...card using the card 1 2 select Command 12 user card read the card to be deleted from that slot Command 13 Delete a range of cards 1 3 select Command 13 0 9 0 9 select the first user number to delete...

Страница 7: ...ct the user level 1 3 0 1 0 9 0 9 0 9 enter the first user slot to activate 0000 through 1599 0 1 0 9 0 9 0 9 enter the last user slot to activate 0000 through 1599 Command 23 Delete a range of cards...

Страница 8: ...block mode card database 1 600 users may take up to 1 minute The completion of a successful transfer is indicated with the long beep A transfer error condition is signalled with three short beeps alo...

Страница 9: ...ase Mode 4 The Block Number Command 94 must be set for Block Database Mode operation 5 In Facility Code Database Mode the digit count specifies the the number of card digits to read and verify For exa...

Страница 10: ...d will pulse Output K1 no effect if the door is unlocked A upward read will toggle the state of Output K1 locking or unlocking the door Configuration Input assignments Input I1 is connected to a door...

Страница 11: ...f Input I2 User Level 2 and 3 A downward read will pulse Output K1 no effect if the door is unlocked A upward read will toggle the state of Output K1 locking or unlocking the door Configuration Input...

Страница 12: ...ses Output K2 allowing the momentary closure to simulate a key switch input to an alarm panel User Level Specifications User Level 1 Both downward and upward read will pulse Output K1 User Level 2 and...

Страница 13: ...to simulate a key switch input to an alarm panel User Level Specifications User Level 1 Cards having this User Level are rejected if the contact on Input I2 is open If the contact on Input I2 is close...

Страница 14: ...to Output K2 and functions as the access control input User Level 1 users are valid only when a closed contact is presented to this input Upper LED assignment The upper LED follows Input I2 displaying...

Страница 15: ...efinition Description This mode is intended for applications where the outputs need to be toggled instead of the standard momentary pulse operation Both outputs are toggled Level 1 users alter the out...

Страница 16: ...ESD electrostatic discharge interfering with the operation of the reader the reader casing shall be grounded This can be accomplished be tying the mounting bracket to earth ground locally e g grounded...

Страница 17: ...from a number of sources e g Clean Team Co 800 888 8830 www cleanteam com KIC Products 207 514 7030 www kicproducts com System ID 1 888 648 4452 www systemid com The reader exterior surface is covere...

Страница 18: ...any other warranties implied warranties and expressly excludes and disclaims all implied warranties of merchantability of fitness for a particular purpose Returns must be accompanied by a Return Mater...

Страница 19: ...l RS 485 termination jumper J4 on the first and last units only 1 2 3 4 5 6 7 8 J2 TB1 GND J3 TR TR VO D0 DAT GND D1 LED DAT BZR TB4 J4 B A U1 J6 TB3 TB2 K2 K1 I1 I1 I2 I2 GND VIN C NC NO C NO NC K2 K...

Отзывы: