Operating Mode 03:
Access Control and Alarm Panel Control
Description
The Access Control and Alarm Panel Control confi guration provides for basic access con-
trol and gives some users the ability to send a pulse to arm and disarm alarm panels.
Both a downward and an upward read of all User Cards pulse Output K1, the strike con-
trol relay, to allow entry. In addition, the upward read of a Level 2 card pulses Output K2,
allowing the
momentary closure to simulate a key-switch input
to an alarm panel.
User Level Specifi cations
User Level 1
Both downward and upward read will pulse Output K1.
User Level 2 (and 3)
A downward read will pulse Output K1
An upward read will pulse both Output K1 and Output K2.
Confi guration
Input assignments:
Input I1 is connected to the armed/disarmed status output from the alarm panel.
Input I2 is connected to a “request to exit” button. Closing the contact initiates the
request.
Upper LED assignment:
The upper LED follows Input I1, displaying the status of the alarm panel:
Open Contact is displayed as RED
Closed Contact is displayed as GREEN