![mercor mcr ZIPP Скачать руководство пользователя страница 6](http://html.mh-extra.com/html/mercor/mcr-zipp/mcr-zipp_operation-and-maintenance-manual_1772894006.webp)
mcr ZIPP
fire protection shut-off valve
MERCOR SA –
The company reserves the right to modify and change the document. Version 20.10.20.5
6/14
6. DEVICE INSTALLATION ___________________________________________
NOTE
During the installation of valve and the finishing works, take into account the possibility of
access to the device later and the disassembly of release and control mechanism in order to
carry out the possible service works and technical inspections.
The mcr ZIPP valve can be installed in the following partitions (walls or ceilings):
masonry walls – concrete with a thickness of at least 110 mm
masonry walls from bricks or blocks at least 120 mm thick
walls from panels at least 125 thick
ceilings of at least 150 mm
Additionally, the valve can be installed:
outside walls
in batteries (multiple sets)
The mcr ZIPP shut-off valve may also be installed in partitions with lower fire resistance class In case of such an
installation, valves have fire protection equal to the fire protection of the partition, maintaining the smoke tightness
criteria.
6.1. INSPECTION BEFORE THE INSTALLATION
___________________________________
Each valve is inspected before packaging and transporting by the manufacturer. After unpacking at the recipient,
inspect visually in terms of possible deformation of the casing or damper damage during transport.
The valve is delivered in the closed position. Before installation, it should be armed.
In order to arm the RST mechanism, the following actions have to be taken:
-
screw the valve from the connection stub pipe
-
rotate the valve so that the mushroom is on top
-
simultaneously release the locking sheet and press the valve nozzle at its circumference (fig. 4a)
-
push the fuse element onto the catches (fig. 4b)
a)
b)
Figure 4. Arming the release and control mechanism:
a) points of applying the force; b) place of setting the thermal release.