mcr ZIPP
fire protection shut-off valve
MERCOR SA –
The company reserves the right to modify and change the document. Version 20.10.20.5
3/14
NOTE
With the date of publication of the operation and maintenance manual, the previous versions are
no longer valid.
The operation and maintenance manual does not concern the dampers manufactured before the
date of its publication.
1. INTRODUCTION ____________________________________________________
The purpose of this operation and maintenance manual is to get the user acquainted with the intended use, design,
the principle of operation, correct installation and operation of the product.
The manual also includes additional information about the operating conditions, maintenance and warranty
conditions of the product.
2. THE SUBJECT OF THE MANUAL __________________________________
This operation and maintenance manual concerns the entire group of fire protection shut-off valves of type ZIPP.
Observing recommendations included in the manual ensures correct function of the device in terms of fire
protection of rooms as well as safety of the system users.
3. DEVICE INTENDED USE ___________________________________________
Application ________________________________________________________________________
A mcr ZIPP type valve may be used as a fire protection shut-off valve with a duct connection as well as a transfer
valve (installation without ventilation ducts).
The valve may not work in systems exposed to dust, except for when they are included in a special, individually
developed programme of service and technical inspections.
Fire resistance ____________________________________________________________________
The mcr ZIPP type fire protection shut-off valve has the following fire resistance:
EI120S for duct installation in walls and ceilings
EI120 for installation without ducts in ceilings
Performance versions ____________________________________________________________
The mcr ZIPP valve can be used as:
a valve with a thermal release – variant:
o
RST – (automatic release)
valve with an electromagnetic release – variant:
o
EK I - (remote release by operation of a "current pulse" – applying supply voltage)
o
EK P - (remote release by operation of a "current gap" – removing supply voltage)
The thermal release always has a principal role and ensures that the safe position of a valve is reached (activated)
regardless of the operation of the electromagnetic release.
Optionally, there is a possibility to provide the valve with WK1 limit switches that signal the valve operation status
(open/closed).
NOTE
As a default, the valve release temperature equals 72°C. In case another temperature value, it has to be
specified in the order,
after prior confirmation of the temperature value with the Sales Department.
Dimension range _________________________________________________________________
The mcr ZIPP type valve is manufactured in the following dimensions - diameters:
Ø100
Ø125
Ø160
Ø200