7.4. Commissioning_____________________________________________________________ 

Before commissioning your installed smoke exhaust fan, do the following: 

  Check that the smoke exhaust fan is properly and firmly fastened. 

  Check all seals for tightness. 

  Check that all electrical wiring is properly and firmly connected. 

  Check that the phase connection sequence and PE/neutral wiring is properly connected. 

  Check that the smoke exhaust fan and its connected ducting are free of foreign bodies. 

  Check that all protective/safety components have been installed. 

  If the checks are positive, start the fan and do a functional test. 

  When  starting  the  smoke  exhaust  fan,  verify  the  motor  sense  of  rotation  against  the  direction 

arrow on the enclosure. 

 
 

8. TRANSPORT & STORAGE CONDITIONS __________________ 

During transport and storage, the mcr Pasat smoke exhaust fans are placed on pallets. Do not topple or 
throw the packaging during loading and transport. The smoke exhaust fans can be handled and shipped 
on  any  means  of transport,  provided  that  they  are  secured  against  weather  and  elements.  The smoke 
exhaust  fans  on  transport  vehicles  must  be  secured  against  shifting.  Visually  inspect  each  piece  of 
equipment following transport and handling. 

Store in sheltered rooms, where: 

  there is no exposure to dust particulates, gases, corrosive vapours and other aggressive 

chemical emissions detrimental to insulation parts and structural components of the fan and/or its 
motor; 

  the maximum relative humidity is 80% at 20°C; 

  the ambient temperature does not exceed the range of – 20ºC to + 40 ºC; 

  no vibrations are present.  

 

 

9. SAFETY MANUAL________________________________________________ 

Read and understand this Technical Manual before commissioning and servicing the product.  
The smoke exhaust fan is not hazardous when firmly attached to a ventilation system and the ventilator 
support structure. 
Make the electrical connections according to the enclosed electrical wiring diagram and the guidelines in 
Section  7.3.  Electrical  connections  shall  be  made  by  personnel  with  relevant  qualifications  which  have 
been certified as required by current laws. 
Inspect the PE wire connection of the smoke exhaust fan during the operating life. 
Disconnect the smoke exhaust fan from electrical power before any inspections or checks. 

 
CAUTION: 

1. Do not clean smoke exhaust fans of deposits with pressure or steam washers. 
2. Loss of seal at the fan connections or flexible ends may result in hazards due to 
 release of the forced medium and requires immediate replacement of leaking components. 
 
If  the  equipment  is  malfunctioning  (e.g.  excessive  noise,  vibration  and/or  erratic  operation  is  found), 
disconnect  the  fan  from  electrical  power  supply,  and  call  the  manufacturer's  technical  service  or  an 
inspection and repair contractor authorised by the manufacturer. 

 

 

 

Содержание mcr Pasat

Страница 1: ...ul Grzegorza z Sanoka 2 80 408 Gdańsk tel 48 58 341 42 45 tel fax 48 58 341 39 85 TECHNICAL MANUAL Roof smoke exhaust fan mcr Pasat Version Pasat 19 06 27 3 FIRE VENTILATION SYSTEMS ...

Страница 2: ...n 6 5 3 Dimensions 6 5 4 Accesories 7 6 IDENTIFICATION MARKING 9 7 INSTALLATION 9 7 1 Pre assembly inspection 9 7 2 Location and assembly 9 7 3 Electrical connections 11 7 4 Commissioning 12 8 TRANSPORT STORAGE CONDITIONS 12 9 SAFETY MANUAL 12 10 MAINTENANCE SERVICING 13 11 WARRANTY TERMS CONDITIONS 13 VENTILATOR MEASUREMENT REPORT 15 Technical Manual designations available option unavailable opti...

Страница 3: ...ISO 12100 1 2005 Safety of machinery Basic concepts general principles for design Part 1 Basic terminology methodology PN EN ISO 12100 2 2005 Safety of machinery Basic concepts general principles for design Part 2 Technical principles PN EN 60204 1 2001 Safety of machinery Electrical equipment of machines Part 1 General requirements The smoke exhaust fan design also meets the state of the art in t...

Страница 4: ...tion of persons from the area on fire protect the building structure and its furnishing from high temperature facilitate fire fighting and inhibit spreading of fire to adjacent fire zones The available versions include single functional with single speed motors two functional i e for general and fire ventilation and with two speed motors The fans can be installed outdoors on suitable consoles roof...

Страница 5: ...0o C for 120 minutes Class F600 fire resistance at 600o C for 60 minutes 4 3 Versions Single speed single functional fans Two speed two functional fans 5 DESIGN AND OPERATING PRINCIPLE 5 1 Design ______________________________________________________________________ 1 Fan base 2 Cooling duct 3 External housing 4 Motor housing 5 Inlet port 6 Motor base 7 Radial rotor 8 Electric box service switch o...

Страница 6: ...________________________________________ The single functional fans do not run in standby When 3 phase voltage is present on the electric box terminals the fan is started and running The two functional fans run at low speed RPM to handle general ventilation under normal conditions When the fan receives an alarm signal it automatically starts running with the second speed which is higher than the f...

Страница 7: ...It acts as a vibration damper It is also used to compensate for thermal elongation The fan integrated in a ventilation system should feature the flexible joint on the suction side Type KD flexible joint Fan Type Type D mm A mm B mm L mm C nxd mm m kg mcr Pasat 35 KD 31 315 385 356 150 45 8x9 6 1 0 mcr Pasat 35 KD 35 355 425 395 150 45 8x9 6 1 1 mcr Pasat 40 KD 40 400 470 438 150 30 12x9 6 1 3 mcr ...

Страница 8: ...heat losses when the fan is in standstill The automatic non return damper is intended for vertical installation with the damper blade axis is horizontal The damper needs precise levelling to operate correctly Type KS V automatic non return damper Fan Type Type D mm A mm B mm L mm C nxd mm m kg mcr Pasat 31 KS V 31 315 385 356 220 45 8x9 6 5 7 mcr Pasat 35 KS V 35 355 425 395 240 45 8x9 6 6 6 mcr P...

Страница 9: ..._________________________________________ Locate the mcr Pasat smoke exhaust fan outdoor and beyond the fire zone The equipment installation orientation must be horizontal i e with the motor axis in the vertical at a minimum height of 250 mm above the roof plane Prior to installation verify the load bearing capacity of the roof structure on which the equipment is to be located Prepare and secure a...

Страница 10: ...ust fan or other components of the assembly The ventilation duct must be supported by independent bearing slings Secure the smoke exhaust fan suction intake with type SO safety mesh When installing the smoke exhaust fan secure the installation site and all involved structures and prepare passage and access ways for all personnel not involved in the installation The smoke exhaust fan must be assure...

Страница 11: ... inadvertent shutdown of the smoke exhaust fan with the sole exception of the fan dedicated service switch with remote indication of current circuit switching The smoke exhaust fan control cabinets must be powered directly from mail switchboards with guaranteed uninterrupted power supply even if the entire building is cut off from the power grid If a main fireman s switch is installed to isolate p...

Страница 12: ...ases corrosive vapours and other aggressive chemical emissions detrimental to insulation parts and structural components of the fan and or its motor the maximum relative humidity is 80 at 20 C the ambient temperature does not exceed the range of 20ºC to 40 ºC no vibrations are present 9 SAFETY MANUAL________________________________________________ Read and understand this Technical Manual before c...

Страница 13: ...85 from 8 AM to 4 PM Mo Fri 11 WARRANTY TERMS CONDITIONS ___________________________ 1 MERCOR SA grants 12 months of warranty for the equipment quality from the date of purchase unless the sales contract states otherwise 2 Submit each warranty claim to MERCOR SA in 7 days from the date of discovery of a warranty eligible defect 3 Submit warranty claims by calling at tel 48 58 341 42 45 by fax 48 5...

Страница 14: ...ressive external influence specifically chemical or biological in nature or when the origin of which is related to the production processing or activity carried out within the facility protected by the equipment or in its direct vicinity Wearing parts and consumables e g gaskets seals unless they have defects of workmanship and or material Damage caused by improper transport handling unloading and...

Страница 15: ...f the equipment MEASUREMENT RESULTS A U1 V1 W1 U2 V2 W2 NOTES Full name of the measuring technician Date measured Signature Return this Report immediately after completion of measurements to MERCOR SA Fire Ventilation Systems Ul Grzegorza z Sanoka 2 80 408 Gdańsk and not later than in 8 weeks from the date of equipment purchase equivalent to the date of the VAT sales invoice THE EQUIPMENT WARRANTY...